750 kVA Pad Mounted Transformer-13.2/0.48 kV|USA 2024

750 kVA Pad Mounted Transformer-13.2/0.48 kV|USA 2024

Lub teb chaws: America 2024
Peev xwm: 750kVA
Qhov hluav taws xob: 13.2 / 0.48kV
Feature: nrog OCTC
Xa kev nug

 

 

750 kva pad mounted transformer

 

01 General

1.1 Project Background

Qhov no 750 kVA Pad mounted transformer tau xa mus rau Asmeskas hauv xyoo 2024. Lub zog ntsuas ntawm lub transformer yog 750 kVA, nrog thawj voltage 13.2GrdY / 7.62 kV rau theem nrab voltage 0.48GrdY / 0.277 kV. Cov pab pawg sib txuas yog YNyn0, ncoo mounted transformer tau txais sai sai vim nws qhov zoo ntawm cov qauv compact, yooj yim installation, hloov tau yooj yim, kev nyab xeeb thiab txhim khu kev qha, yooj yim txij nkawm thiab lwm yam.

Pad mounted transformer muaj qhov zoo hauv qab no:

kev ua tau zoo heev: qib kev ua haujlwm siab, kev siv 10, 11 series lossis amorphous alloy series, tsis tshua muaj suab nrov, muaj zog luv luv -circuit resistance.

Ua kom tiav cov haujlwm, yooj yim thiab txhim khu kev qha: tuaj yeem txiav tawm cov khoom thauj tam sim no, tag nrho cov kev tiv thaiv tam sim no, cov kab hluav taws xob siab nkag tau yooj yim (ntiv nplhaib network, davhlau ya nyob twg), tuaj yeem ua tiav theem tawg (kev tiv thaiv undervoltage), nrog rau kev ua haujlwm yooj yim ntawm substation.

 

 

1.2 Technical Specification

750 kVA transformer specifications hom thiab cov ntaub ntawv ntawv

Xa rau
Asmeskas
Xyoo
2024
Hom
Pad mounted transformer
Txuj
IEEE C57.12.34
Rated zog
750kVA ua
Ntau zaus
60 tzs
Theem
3
Pub
Loop
Pem hauv ntej
Tuag
Hom cua txias
ONAN
Thawj Voltage
13.2 GrdY / 7.62 kV
Secondary Voltage
0.48 / 0.277 kV
Cov khoom siv winding
Aluminium
Angular tshem tawm
yNyj 0
Impedance
5±7.5%
Kev ua tau zoo
99.32%
Coj mus rhaub Changer
NLTC
Ua kua Insulant
Mineral roj
Tapping Range
±2*2.5%
Tsis Load Loss
0.89 kWm
Ntawm Load Loss
7.5 kWm
Khoom siv
Standard Configuration

 

1.3 Cov duab kos

750 kVA ncoo mounted transformer daim duab kos duab thiab loj.

750 kva pad mounted transformer diagram 750 kva pad mounted transformer nameplate

 

 

02 Kev tsim khoom

2.1 Core

Lub transformer ua los ntawm lub tiaj tus coil hlau core muaj ib tug kiag li kaw sib nqus Circuit Court yam tsis muaj hlau nplaum to. Hais txog cov khoom siv raw, SCOTECH txais yuav lub ntiaj teb thawj-chav kawm siab- zoo taw qhia silicon steel ntawv, uas yog nyias nyias thiab muaj cov yam ntxwv ntawm siab sib nqus induction thiab tsis tshua muaj hlau tsis zoo, ua kom muaj kev ua haujlwm zoo ntawm cov tub ntxhais hlau. Nyob rau hauv cov nqe lus ntawm cov qauv, lub tiaj tus coil core yog symmetrically raug mob nrog txawv dav thiab txheej, thiab tus ntoo khaub lig seem yog ib tug symmetrical kauj ruam kwv yees li ncig. Thaum siv nyob rau hauv transformers, lub kauj tuaj yeem raug mob ncaj qha rau ntawm cov tub ntxhais hlau, yog li txo qhov coil tig ntev.

amorphous steel core transformer

 

2.2 Cua txias

primary secondary coil

Tsawg-voltage foil winding yog hais txog kev siv cov ntawv hlau nyias los ua cov khoom siv hluav taws xob, los ntawm kev sib tshooj ntawm txoj kev mus rau cua. Txoj kev no feem ntau yog siv nyob rau sab qis voltage ntawm lub transformer. Foil winding siv thaj chaw loj ntawm tus neeg xyuas pib kom txo cov coil tsis kam thiab eddy tam sim no poob, tshwj xeeb tshaj yog nyob rau hauv tsawg- daim ntawv thov zaus. Foil winding siv thaj chaw loj ntawm tus neeg xyuas pib kom txo cov coil tsis kam thiab eddy tam sim no poob, tshwj xeeb tshaj yog nyob rau hauv tsawg- daim ntawv thov zaus. Cov qauv ntawm cov ntawv ci winding yog cov compact, uas muaj peev xwm ua tau ntau dua hluav taws xob conductivity nyob rau hauv ib tug txwv qhov chaw, uas yog tshwj xeeb tshaj yog tseem ceeb rau me me transformers. Cov ntawv ci- cov qauv kab mob tuaj yeem tiv thaiv kev cuam tshuam ntawm electromagnetic cuam tshuam thiab txo cov suab nrov electromagnetic, yog li txhim kho kev ua haujlwm ruaj khov ntawm transformer.

High-voltage wire winding yog hais txog kev siv lub voj voog lossis lub voj voos xaim rau winding, feem ntau yog siv nyob rau hauv siab -voltage sab ntawm transformer. High voltage xaim winding siv cov khoom siv rwb thaiv tsev coated hlau, tuaj yeem tiv taus hluav taws xob ntau dua, nrog kev rwb thaiv tsev zoo dua, tsim nyog rau kev ua haujlwm siab. Cov hlau- cov qauv kab mob yog qhov muaj zog thiab tuaj yeem tiv taus qhov cuam tshuam ntawm ib puag ncig sab nraud, xws li ya raws thiab qhov kub thiab txias hloov pauv, ncua kev pab cuam lub neej ntawm transformer. High voltage hlau winding tuaj yeem tsim raws li qhov sib txawv thiab cov duab kom tau raws li qhov yuav tsum tau muaj ntawm ntau lub tshuab hluav taws xob.

 

2.3 Tank

Cov roj tank raug txiav, xuas nrig ntaus thiab khoov los ntawm cov khoom siv laser lej tswj kom paub tseeb tias kev ua haujlwm raug. Qhov saum npoo ntawm lub thawv txais kev tiv thaiv kev tiv thaiv- tsim kev xeb thiab kev kho tshwj xeeb tshuaj pleev xim, uas tsim nyog rau ntau qhov chaw hnyav. Sab saum toj ntawm lub thawv tuaj yeem raug tso tawm, thiab lub kaum sab xis ntawm lub hau npog sab saum toj tsis pub tsawg dua 3 degree.

anti-corrosion oil tank

 

2.4 Kev sib dhos zaum kawg

750 kva pad mounted transformer assembled
transformer bushing

 

 

03 Kev Xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Kev txais txiaj ntsig

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

Kev tiv thaiv siab tshaj plaws tsis sib npaug tsawg dua lossis sib npaug li 5%

2.55

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: YNyn0

0.02% ~ 0.04%

Hla

3

theem- kev xeem sib txheeb

/

yNyj 0

yNyj 0

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

%

kW

t: 20 qib

I0: muab ntsuas tus nqi

P0: muab ntsuas tus nqi

qhov kam rau tsis muaj load poob yog +10%

0.22

0.918

Hla

5

Load poob impedance voltage thiab efficiency

%

kW

kW

t:85 ua

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

Qhov kam rau ua impedance yog ± 7.5%

lub kam rau tag nrho load poob yog +6%

Kev ua haujlwm tsis tsawg dua 99.32%

4.83

6.918

7.836

99.34

Hla

6

Applied Voltage Test

kV ua

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

kV ua

Kev siv hluav taws xob (KV): 0.995

Duration(s): 48

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

8

Kev Xeem Leakage

kPa ua

Kev siv siab: 20kPA

Duration: 12h

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

9

Rwb thaiv tsev Resistance Measurement

HV & LV rau hauv av:

30.4

/

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 45

54.50

Hla

11

Nrov xeem

dB

51-55

53.6

Hla

12

xob laim impulse test

kV ua

full wave, Half wav

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

 

high voltage bushing
low voltage bushing

 

 

04 Packing thiab Shipping

packaging of transformer
750kva transformer loading

 

 

05 Site thiab Summary

Peb Theem Pad Mounted Transformer, nrog rau nws cov kev ua tau zoo, kev ntseeg siab, thiab kev hloov pauv, tau siv dav hauv ntau yam kev faib hluav taws xob, muab cov neeg siv tau zoo, nyab xeeb, thiab tus nqi - cov kev daws teeb meem zoo. Txawm hais tias nyob rau hauv kev lag luam, kev lag luam, lossis pej xeem kev siv vaj tse, nws pab cov neeg siv khoom kom muaj zog ruaj khov thiab kev ua kom zoo zog. Xaiv Peb Theem Pad Mounted Transformer los nqa lub zog ruaj khov thiab txhim khu kev qha rau koj cov haujlwm thiab nqis mus rau lub sijhawm tshiab ntawm lub zog ntse ua ke.

China transformer supplier

 

Cim npe nrov: 750kva pad mounted transformer, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug