75 kVA Pad Mount-23/0.208 kV|USA 2025

75 kVA Pad Mount-23/0.208 kV|USA 2025

Lub teb chaws: America 2025
Muaj peev xwm: 75 kVA
Qhov hluav taws xob: 23GRDY / 13.28-0.208 / 0.12kV
Feature: nrog lub qhov txhab core
Xa kev nug

 

 

pad mount

Muaj tawv, Utility Smart - Pad-Mounted Transformers rau Kev Thov Loads.

 

 

01 General

1.1 Project Description

75 kVA peb theem pad mounted transformer tau xa mus rau Asmeskas xyoo 2025. Lub zog ntsuas ntawm lub transformer yog 75 kVA nrog ONAN txias. Thawj qhov hluav taws xob yog 23GRDY / 13.28 kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov nruab nrab voltage yog 0.208y / 0.12 kV, lawv tsim ib pawg vector ntawm YNyn0.

Pad-mounted transformers yog compact, hauv av-theem hluav taws xob faib chav tsev tsim kom muaj kev nyab xeeb thiab siv hluav taws xob xa hluav taws xob hauv nroog, suburban, thiab chaw lag luam. Encased nyob rau hauv ruaj, tamper- tiv thaiv enclosures, cov transformers no muab kev ntseeg siab voltage hloov dua siab tshiab thaum txo hneev taw thiab ib puag ncig. Lawv cov hauv qab no - qhov muag - theem kev teeb tsa ua rau lawv zoo tagnrho rau qhov chaw - txwv tsis pub cov kab hla saum taub hau tsis zoo lossis tsis zoo nkauj.

Engineered rau ob qho tib si kev nyab xeeb thiab kev ua tau zoo, niaj hnub ncoo- mounted transformers feature advanced rwb thaiv tsev systems, corrosion{1}}cov ntaub ntawv resistant, thiab xaiv ntse soj ntsuam muaj peev xwm rau tiag tiag - lub sij hawm kuaj mob. Txawm hais tias lub zog siv hluav taws xob hauv zej zog, cov chaw lag luam, lossis cov chaw tsim khoom, cov chav no xa cov kev ua haujlwm ntsiag to nrog cov kev xav tau txo qis dua piv rau cov ncej qub- mounted lwm txoj.

 

 

 

1.2 Technical Specification

75 KVA ncoo mounted transformer specifications hom thiab cov ntaub ntawv ntawv

Xa rau
Asmeskas
Xyoo
2025
Hom
Pad mounted transformer
Txuj
IEEE StdC57.12.34-2022
Rated zog
75 kVA ua
Ntau zaus
60 tzs
Theem
3
Pub
Radial
Pem hauv ntej
Tuag
Hom cua txias
ONAN
Thawj Voltage
23 GrdY/13.28 kV
Secondary Voltage
0.208GrdY/0.12 kV
Cov khoom siv winding
Aluminium
Angular tshem tawm
yNyj 0
Impedance
3.25%
Coj mus rhaub Changer
NLTC
Tapping Range
±2*2.5%
Tsis Load Loss
0.08 kWm
Ntawm Load Loss
1.27 kWm
Khoom siv
Standard Configuration

 

 

1.3 Cov duab kos

75 kVA ncoo mounted transformer daim duab kos duab thiab loj.

pad mount diagram pad mount nameplate

 

 

02 Kev tsim khoom

2.1 Core

Lub ncoo no-mounted transformer nta ib qho tshiab tsib- lub cev nqaij daim tawv nqaij nrog peb lub caj dab winding (A / B / C theem) thiab ob lub flux- rov qab nqua, xa cov khoom sib nqus zoo dua thiab ua haujlwm zoo. Lub seamless kauv-mob nplej- taw qhia silicon steel core txo tsis muaj-load poob los ntawm 25-30% piv rau cov qauv tsim.

Cov txiaj ntsig tseem ceeb muaj xws li:

• Txhim kho qhov sib npaug thiab luv -circuit tiv taus

• Ultra- suab nrov tsawg thiab cua sov tsawg heev

grain-oriented silicon steel core

 

2.2 Cua txias

low-voltage windings

Qhov no peb winding transformer nta ib tug optimized tsim nrog aluminium foil tsawg-voltage windings thiab tooj liab hlau siab-voltage windings, xa superior efficiency thiab thermal kev ua tau zoo. Qhov thib peb winding muab cov kev cai hloov hluav taws xob hloov pauv lossis muaj peev xwm pab txhawb lub zog. Kev sib xyaw ua ke ntawm cov ntawv ci thiab hlau winding thev naus laus zis, chav tsev compact no muaj cov kev faib tawm zoo tshaj plaws tam sim no, luv luv -circuit tiv taus, thiab tshav kub dissipation - ua rau nws zoo tagnrho rau niaj hnub fais fab kev faib tes hauj lwm uas yuav tsum tau txhim khu kev qha peb winding transformer kev daws teeb meem hauv kev siv hluav taws xob, kev lag luam thiab kev lag luam.

 

2.3 Tank

Qhov kev hloov pauv no muaj lub zog ruaj khov, huab cua tsis muaj roj tank tsim los ntawm qib siab -qib corrosion- cov hlau tsis muaj zog rau kev ua haujlwm zoo tshaj plaws hauv kev teeb tsa sab nraum zoov. Cov roj tank suav nrog ntau yam kev tsim kho kev nyab xeeb xws li:

• Leak- pov thawj welded seams nrog siab- kuaj kev ncaj ncees

• Expansion conservator nrog roj theem taw qhia rau kev tswj thermal

• Tiv thaiv corrosion los ntawm sandblasting thiab multi- txheej epoxy txheej

weatherproof oil tank

 

2.4 Kev sib dhos zaum kawg

pad mount transformer final assembly

1. Winding Installation:Precisely mount lub HV / LV windings mus rau lub qhov txhab ntawm lub qhov txhab, xyuas kom zoo rwb thaiv tsev kawm ntawv.

2. Kev sib txuas hluav taws xob:Txuas winding ua rau kais hloov pauv, bushings, thiab lwm yam khoom, ces ruaj ntseg thiab kuaj conductivity.

3. Core-Coil ziab:Muab cov khoom sib dhos ua ke rau hauv qhov cub kom qhuav rau lub tshuab nqus tsev kom tshem tawm cov dej noo thiab txhim khu kev rwb thaiv tsev.

4. Tank Insertion:Hoist thiab muab qhov chaw qhuav qhuav rau hauv lub tank, ua kom nws ruaj khov thaum tswj kom zoo rwb thaiv tsev clearance.

5. Accessory Installation:Txuas cov bushings, cov cuab yeej tiv thaiv siab, roj ntsuas, thiab lwm yam, thiab kaw tag nrho cov interfaces.

6. Roj Sau & Sealing:Lub tshuab nqus tsev- sau cov roj insulating mus rau qib uas tau teev tseg, xyuas cov roj zoo thiab lub tank nruj, tom qab ntawd ua tiav kaw.

 

 

03 Kev Xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Kev txais txiaj ntsig

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

Maximum kuj unbalance tus nqi

1.07

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

-0.03~0.01

Hla

3

Theem -kev xeem sib txheeb

/

yNyj 0

yNyj 0

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

%

I0 :: muab ntsuas tus nqi

0.31

Hla

kW

P0: muab ntsuas tus nqi

0.0795

/

Kev kam rau ua tsis muaj load poob yog ± 10%

/

5

Load poob, impedance voltage, tag nrho poob thiab efficiency

/

t:85 ua

Qhov kam rau ua impedance yog ± 7.5%

kev kam rau tag nrho load poob yog ± 6%

/

Hla

%

Z%: ntsuas tus nqi

3.29

kW

Pk: ntsuas tus nqi

1.156

kW

Pt: ntsuas tus nqi

1.2355

%

Kev ua haujlwm tsis tsawg dua 99.03%

99.10

6

Applied Voltage Test

/

HV: 10kV 60s

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

/

Kev siv hluav taws xob (KV): 0.624

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

Duration(s):30

Zaus (HZ): 240

8

Rwb thaiv tsev Resistance Measurement

GΩ

HV-LV to Av:

190

Hla

LV-HV to Av:

311

9

Kev Xeem Leakage

/

Kev siv siab: 20kPA

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

Duration: 12h

10

Roj Xeem

kV ua

Dielectric zog

57.3

Hla

mg/kg

Cov ntsiab lus noo noo

10.6

%

Dissipation Factor

0.155

mg/kg

Furan Analysis

Tsawg dua los yog sib npaug li 0.1

/

Gas Chromatography Analysis

/

 

Applied Voltage Test
Induced Voltage Withstand Test

 

 

04 Packing thiab Shipping

4.1 Ntim

Lub ncoo mounted transformer yog ntim rau hauv ib lub crate ntoo nrog ib txheej ntxiv ntawm aluminium ntawv ci hnab npog sab nrauv, tsim kom muaj kev tiv thaiv dual - qauv. Cov ntoo crate muab kev txhawb zog thiab kev cuam tshuam, thaum lub hnab aluminium ntawv ci sab nrauv zoo tiv thaiv chav tsev los ntawm cov dej noo, plua plav, thiab lwm yam khoom paug ib puag ncig, tiv thaiv corrosion thiab hluav taws xob kev ua haujlwm tsis zoo thaum thauj thiab khaws cia. Txoj kev ntim khoom no muab cov khoom siv ua haujlwm ntev nrog kev sib khi ib puag ncig, ua rau nws haum rau ntev - kev thauj mus los lossis kev cia hnyav.

 wooden crate of transformer

 

4.2 Shipping

international shipping standards

Lub ncoo-mounted transformer raug xa mus raws li CIF (Cov Nqi, Kev Pov Hwm, thiab Kev Thauj Khoom), nrog rau qhov chaw nres nkoj yog Memphis, TN, USA. Chav tsev yog ntim rau hauv ib lub thawv ntoo qhwv nrog ib lub hnab aluminium foil rau ya raws, plua plav, thiab kev tiv thaiv kev puas tsuaj. Cov khoom xa tuaj yuav raug thauj los ntawm hiav txwv freight mus rau qhov chaw nres nkoj, nrog tus neeg muag khoom lub luag haujlwm rau kev tuav pov hwm thiab cov nqi thauj khoom mus txog thaum cov khoom thauj khoom thauj mus los ntawm qhov chaw. Tag nrho cov txheej txheem kev thauj mus los ua raws li cov qauv kev thauj mus los thoob ntiaj teb kom ntseeg tau tias muaj kev nyab xeeb thiab kev ncaj ncees ntawm cov khoom siv thaum caij tsheb npav.

 

 

05 Site thiab Summary

Raws li ib qho tseem ceeb hauv kev faib hluav taws xob, Pad-Mounted Transformer sawv tawm rau nws cov qauv tsim, kev ua haujlwm siab, thiab kev ntseeg tau tshwj xeeb, ua rau nws zoo tagnrho rau cov phiaj xwm hauv nroog, thaj chaw muaj kev lag luam, thiab cov phiaj xwm hluav taws xob tauj dua tshiab. Tsim los ntawm kev ua raws li cov qauv thoob ntiaj teb, txhua lub tsev xa tawm kev lag luam - ua haujlwm hauv kev nyab xeeb, kev siv hluav taws xob, thiab kav ntev. Txawm hais tias ntsib ib puag ncig hnyav lossis xav tau lub zog nyuaj, peb cov transformers kom ruaj khov thiab ua haujlwm tau zoo. Rau cov kev daws teeb meem los yog kev pab txhawb nqa, thov hu rau peb pab neeg -Peb tau cog lus tias yuav muab kev pabcuam kws tshaj lij raws li koj xav tau.

compact design of pad mount transformer

 

Cim npe nrov: pad mount, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug