500 KVA 3-theem Distribution Transformer-13.2/0.208 KV|USA 2024

500 KVA 3-theem Distribution Transformer-13.2/0.208 KV|USA 2024

Lub Tebchaws xa tuaj: Tebchaws USA 2024
Peev xwm: 500kVA
Qhov hluav taws xob: 13.2 / 0.208kV
Feature: DOE 2016
Xa kev nug

 

500 kVA 3-phase distribution transformer

High -kev ua tau zoo 3-theem tis transformer kom ruaj khov voltage thiab kho yooj yim.

 

 

01 General

1.1 Project Description

Qhov no500kVA peb theem ncoo mounted transformertau xa mus rau Tebchaws Meskas hauv xyoo 2024. Nws tau tsim thiab sim raws li IEEE Std C57.12.34-2022. Lub transformer ua tau raws li DOE 2016 tus qauv kev siv hluav taws xob. Nws efficiency yog 99.35%. Thawj qhov voltage yog 13.2kV, thiab theem nrab voltage yog 0.208kV. Nws hloov siab voltage mus rau qhov tsis tshua muaj hluav taws xob rau kev lag luam thiab kev siv teeb pom kev lag luam. Nws yog UL teev thiab ua raws li US cov qauv kev nyab xeeb thiab kev ua haujlwm.

Pawg vector Dyn1 lav qhov sib npaug theem kev sib raug zoo thiab ruaj khov theem nrab voltage kev ua tau zoo nyob rau hauv load. Ib qho tsis muaj -load kais hloov pauv (NLTC) muab ± 2 × 2.5% voltage hloov kho rau cov kev cai meej nyob rau hauv cov kab sib txawv.

Cov tub ntxhais siv peb -limb tsim los ntawm qib siab- qib txias- dov silicon steel laminations, txo cov tub ntxhais poob thiab suab nrov. Aluminium windings yog ua hauj lwm rau thermal conductivity zoo heev, corrosion kuj, thiab nqi efficiency thaum tswj hluav taws xob ua tau zoo. ONAN (Oil Natural Air Natural) cua txias system ua kom ruaj khov ua haujlwm raws li kev thauj khoom tag nrho yam tsis tas yuav tsum tau ua kom txias.

Qhov no transformer yog siv nyob rau hauv industrial thiab lag luam fais fab tshuab. Nws muab lub zog rau cov chaw tsim khoom, cov chaw khaws ntaub ntawv, thiab cov chaw ua haujlwm substations. Nws ua haujlwm zoo hauv av thiab ncoo -mounted installations. Nws yog tsim rau cov chaw uas qhov chaw me me, thiab kev nyab xeeb thiab kev ntseeg siab yog qhov tseem ceeb. Kev sib xyaw ua ke ntawm cov voj voog pub thiab tuag- kev teeb tsa pem hauv ntej tso cai rau kev pabcuam tsis cuam tshuam thiab kev saib xyuas yooj yim, ua tau raws li cov kev cai niaj hnub rau kev nyab xeeb thiab kev siv hluav taws xob.

 

 

1.2 Technical Specification

500 kVA 3-theem transformer specification thiab cov ntaub ntawv ntawv

Xa rau
Teb chaws USA
Xyoo
2024
Hom
Peb theem pad mount transformer
Txuj
IEEE Std C57.12.34-2022
Rated zog
500 KVA ua
Ntau zaus
60 tzs
Pub
Loop
Pem hauv ntej
Tuag
Theem
Peb
Hom cua txias
ONAN
Ua kua insulating
Mineral Roj
Thawj Voltage
13.2 kV 2
Secondary Voltage
0.208 kV
Efficiency thiab poob
Xyoo 2016, 99.35%
Vector Group
Dyn 1
Cov khoom siv winding
Aluminium
Impedance
4%
Coj mus rhaub Changer
NLTC
Tapping Range
±2*2.5%
Tsis Load Loss
0 ,71kv
Ntawm Load Loss
4, 1kv
Khoom siv
Standard Configuration

 

1.3 Cov duab kos

500 kVA 3-theem faib transformer kos duab thiab npe daim ntawv

500 kVA 3-phase distribution transformer drawing 500 kVA 3-phase distribution transformer nameplate

 

 

02 Kev tsim khoom

2.1 Core

500 kVA 3-phase distribution transformer iron core

Lub 500 kVA 3-theem faib transformer muaj peb-theem peb-limb core ua los ntawm high-qib txias-silicon steel. Nws muab qis tsis muaj-load poob thiab suab nrov tsawg. Cov tub ntxhais siv cov lamination meej thiab cov kauj ruam-plab pob qij txha kom txo cov hlau nplaum tiv thaiv. Cov qauv clamping pab txo kev vibration. Qhov kev tsim no ua rau lub transformer ua haujlwm zoo dua thiab ruaj khov thaum lub sijhawm ua haujlwm ntev.

 

2.2 Cua txias

Cov windings yog ua los ntawm high -conductivity aluminium nrog txheej winding. Lawv siv Class H rwb thaiv tsev thiab nruj winding khoob los txhim kho lub zog dielectric. Aluminium winding muab cov cua kub zoo thiab muaj zog tiv thaiv luv luv - lub zog hluav taws xob. Nws kuj ua rau lub transformer sib dua thiab txhim kho kev ua haujlwm kub.

 

2.3 Tank

Lub tank yog tag nrho welded steel qauv nrog ONAN ntuj roj txias. Qhov saum npoo yog sandblasted, ces coated nrog primer thiab epoxy xim rau muaj zog corrosion tiv thaiv. Qhov kev tsim no ua rau lub transformer txhim khu kev qha hauv kev siv sab nraum zoov thiab kev lag luam.

500 kVA 3-phase distribution transformer oil tank

 

2.4 Kev sib dhos zaum kawg

500 kVA 3-phase distribution transformer active part

Cov tub ntxhais thiab cov coil sib dhos yog ntxuav, tshuaj xyuas, thiab ua tib zoo ua raws, nrog aluminium windings securely clamped thiab insulated. Thaum lub sij hawm tanking, lub active ib feem yog muab tso rau hauv ib tug huv si tank, grounded, thiab zoo positioned rau stability.

Cov khoom siv xws li siab- thiab qis-voltage bushings, radiators, pressure relief valve, lifting lugs, thiab off-circuit tap changer are installed and sealed. Cov khoom siv ntxiv muaj xws li bayonet fuse nrog CLFs, 2- txoj haujlwm LBOR hloov, ntsuas qib ua kua, ntsuas lub tshuab nqus tsev siab, tus ntsuas kub dial, thiab lub ntsuas dej thiab cov qauv valve.

Lub tshuab nqus tsev vacuum - puv nrog cov roj ntxhia, kuaj xyuas qhov kev sib khi, thiab kuaj xyuas hluav taws xob, suav nrog kev ua haujlwm, qhov sib piv, qhov hluav taws xob tiv thaiv, rwb thaiv tsev, thiab kev ntsuas hluav taws xob. Tom qab kev ntxuav thiab tshuaj xyuas zaum kawg, cov ntaub ntawv teev npe thiab cov cim raug txheeb xyuas ua ntej xa khoom xa tuaj.

 

 

03 Kev Xeem

Kev xeem Standard

IEEE C57.12.00-2021

IEEE Standard Requirements General Requirements for Liquid-Immersed Distribution, Fais Fab, thiab Regulating Transformers

IEEE Std C57.12.34-2022

IEEE Standard Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Peb-Phase Distribution Transformers, 10 MVA thiab me; High-Voltage, 34.5 kV Nominal System Voltage thiab hauv qab; Tsawg-Voltage, 15 kV Nominal System Voltage thiab hauv qab

IEEE C57.12.90-2021

IEEE Standard Test Code rau kua-Immersed Distribution, Fais Fab, thiab Regulating Transformer 􀀯

 

Routine Test

1. Kev ntsuas ntsuas
2. Kev ntsuas qhov sib piv
3. Theem -kev sib txheeb xeem
4. Tsis muaj Load Losses thiab Tsis Muaj Load Tam Sim No
5. Load Losses Impedance Voltage thiab Efficiency
6. Applied Voltage Test
7. Induced Voltage Withstand Test
8. Kev ntsuas dej nrog lub siab rau cov kua Immersed Transformers
9. Kev ntsuas kev tiv thaiv rwb thaiv tsev
10. Roj Dielectric Test

500 kVA 3-phase distribution transformer test
500 kVA 3-phase distribution transformer testing

 

Cov qhabnias xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Txais

Tus nqi

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

Maximum kuj unbalance tus nqi

4.55

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Dyn1

-0.02% ~ 0.05%

Hla

3

theem- kev xeem sib txheeb

/

Dyn 1

Dyn 1

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

 

/

I0 :: muab ntsuas tus nqi

0.25%

Hla

P0: muab ntsuas tus nqi (t: 20 degree)

0.638 kWm

qhov kam rau tsis muaj load poob yog +10%

/

5

Load poob impedance voltage thiab efficiency

/

t:85 ua

Qhov kam rau ua impedance yog ± 7.5%

qhov kam rau tag nrho load poob yog +6%

/

Hla

Z%: ntsuas tus nqi

4.12%

Pk: ntsuas tus nqi

4, 062 kWm

Pt: ntsuas tus nqi

4.700 kWm

Kev ua haujlwm tsis tsawg dua 99.35%

99.38%

6

Applied Voltage Test

kV ua

HV: 34kV 60s

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

kV ua

Kev siv hluav taws xob (KV): 2Ur

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

Induced voltage (KV): 0.416

Duration(s): 40

Zaus (HZ): 180

8

Kev Xeem Leakage

kPa ua

Kev siv siab: 20kPA

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

Duration: 12h

9

Rwb thaiv tsev Resistance Measurement

HV-LV to Av:

21.3

/

LV-HV to Av:

29.8

HV & LV rau hauv av:

25.6

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 45

55.2

Hla

 

 

04 Packing thiab Shipping

500 kVA 3-phase distribution transformer packing
 
500 kVA 3-phase distribution transformer shipping
 

05 Site thiab Summary

500 kva 3-phase distribution transformer-right-view

Scotech 500kVA 3-theem tis transformer yog tsim thiab tsim los rau IEEE Std C57.12.34-2022 thiab DOE 2016 cov qauv kev ua haujlwm, muab 99.35% kev ua haujlwm siab thiab txhim khu kev qha fais fab. Nws hloov 13.2kV ​​mus rau 0.208kV rau kev lag luam thiab kev lag luam teeb pom kev zoo hauv kev siv hluav taws xob niaj hnub.

Lub tank welded ruaj khov, corrosion-cov txheej txheem tiv taus, thiab cov khoom siv txheem tau lees paub kev nyab xeeb thiab ua haujlwm tau zoo. Cov txheej txheem accessories ua rau lub transformer muaj kev nyab xeeb thiab zoo. Txhua chav tsev yog lub tshuab nqus tsev- puv nrog cov roj ntxhia. Nws yog kuaj rau hluav taws xob kev ua tau zoo, rwb thaiv tsev, thiab xau.

Scotech transformersmuab kev ntseeg siab, lub zog-txuag, thiab qis- nqi zog rau kev faib khoom thoob ntiaj teb.

 

Cim npe nrov: 3-theem faib transformer, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug