Earthing Transformer

SCOTECH muab lub ntiaj teb transformer mus txog 5 MVA 35 kV

Hu rau Muag
  • Kev nthuav qhia
  • Cov ntaub ntawv
Tshawb nrhiav
Earthing Transformers rau Neutral Grounding Systems
Mus txog 5 MVA 35 kV
Lub earthing transformer, tseem hu ua grounding transformer lossis nruab nrab grounding transformer, muab cov khoom nruab nrab nruab nrab hauv peb theem hluav taws xob uas qhov chaw nruab nrab siv tau tsis muaj lwm yam. Nws ua rau lub kaw lus tau txais ib qho kev txiav txim siab nruab nrab hauv av.
Thaum lub ntiaj teb ua txhaum, lub earthing transformer muab txoj hauv kev rau xoom-sequence tam sim no, tso cai rau cov av thiab cov khoom siv tiv thaiv cuam tshuam ua haujlwm raws li qhov xav tau. Nws winding configuration thiab xoom-sequence impedance raug xaiv raws li lub tshuab hluav taws xob tsim thiab xav tau kev ua haujlwm hauv av.
Raws li qhov yuav tsum tau ua ntawm qhov project, qhov nruab nrab ntawm qhov nruab nrab tuaj yeem txuas ncaj qha lossis txuas los ntawm qhov nruab nrab grounding resistor (NGR / NER), grounding reactor, lossis arc-suppression coil. Qhov kev xaiv tau txiav txim siab seb lub ntiaj teb-tam sim no raug txwv lossis tswj tau li cas thiab yuav tsum tau koom tes nrog lub network hauv av thiab tsim kev tiv thaiv.
SCOTECH tsim lub ntiaj teb transformers raws li qhov project-tshwj xeeb hluav taws xob tsis, installation tej yam kev mob, thiab pom zoo kev specifications.
Tau txais ib daim Quote Download tau daim ntawv qhia

Earthing Transformer Up to 5 MVA 35 kV

 

IEC
ANSI
IEEE
CSA
National Electrical Manufacturers Association

 

 

Hom

 

Hom Earthing Transformers

 

SCOTECH earthing transformers muaj nyob rau hauv sib txawv winding configurations kom tau raws li qhov yuav tsum tau grounding

nruab nrab-voltage fais fab system. Ob qho kev teeb tsa yog Zig-Zag thiab Star-Delta.

Zig-Zag Earthing Transformer (ZN)

Zig-Zag earthing transformer siv interconnected windings teem nyob rau hauv ib tug zig-zag configuration los tsim ib qho khoom nruab nrab point. Nws txoj kev sib tw winding muab txoj hauv kev rau xoom-ib ntu ntu tam sim no thaum lub ntiaj teb ua txhaum thaum raug tsim los ua kom tau raws li qhov xav tau hauv av impedance.

Qhov kev teeb tsa no feem ntau suav hais tias yog rau peb-theem systems uas tsis muaj cov ntsiab lus nruab nrab nkag tau. Qhov ntsuas nruab nrab tam sim no, lub sijhawm luv luv tam sim no, xoom-sequence impedance, thiab rwb thaiv tsev yuav tsum tau txiav txim siab los ntawm qhov project tsim.

Lub hnub qub-Delta Earthing Transformer (YNd)

Lub Hnub Qub-Delta earthing transformer siv lub hnub qub txuas nrog winding nrog rau qhov nruab nrab nkag tau thiab lub delta-txuas winding. Qhov nruab nrab taw tes muab kev sib txuas uas yuav tsum tau ua rau qhov kev npaj hauv av.

Nyob ntawm tus qauv tsim, delta winding tuaj yeem ua haujlwm ruaj khov lossis ua kom haum raws li qhov yuav tsum tau muaj winding ntxiv rau qhov project. Kev teeb tsa tiag tiag thiab kev ua haujlwm yuav tsum tau lees paub thaum lub sijhawm tshuaj xyuas engineering.

Kev siv

 

Earthing Transformer Project References

Tshawb SCOTECH cov phiaj xwm hauv av transformer rau nruab nrab-voltage fais fab tuag. Cov ntaub ntawv no
taw qhia peb cov kev paub dhau los hauv kev muab cov phiaj xwm tshwj xeeb hauv av transformers.

370 kVA Grounding A Transformer-22/0.11 kV|South Africa 2024
370 kVA Grounding A Transformer-22/0.11 kV|South Africa 2024
Lub teb chaws: South Africa 2024
Peev xwm: 370kVA
Lub hwj chim: 22/0.11kV
Feature: nrog CT
6.9 MVA Zig Zag Transformer-22 / KV|Australia 2025
6.9 MVA Zig Zag Transformer-22 / KV|Australia 2025
Lub Tebchaws xa tuaj: Australia 2025
Peev xwm: 6900kVA
Lub cev muaj zog: 22 kV
Feature: 6350A / 10s nruab nrab tam sim no
3000 KVA IEC 60076 Fais fab Transformers-88/11 KV|South Africa 2025
3000 KVA IEC 60076 Fais fab Transformers-88/11 KV|South Africa 2025
Lub teb chaws: South Africa 2025
Peev xwm: 3000 kVA
Lub Zog: 88/11kV
Feature: Tsawg-voltage sab outgoing cable box
Specifications

 

Earthing Transformer Specifications

 

3

Parameter

Specification

Rated zog

Mus txog 5 MVA

Rated High Voltage

Mus txog 35 kV

Rated Zaus

50 Hz / 60 Hz

Winding Configuration

Zig-Zag (ZN) thiab lwm yam kev teeb tsa raug tsim los lees paub

Zero-Sequence Impedance

Tsim raws li cov kev cai hauv av

Magnetizing impedance

Txiav txim siab los ntawm kev tsim hluav taws xob

Kev ntsuas nruab nrab tam sim no

Customized raws li qhov xav tau hauv ntiaj teb-tam sim no

Short-Time Duty

10 s / 30 s / 60 s lossis lwm lub sijhawm teev tseg

Txoj kev txias

ONAN / UA

Rwb thaiv tsev Level

Raws li qhov ntsuas hluav taws xob thiab cov qauv siv tau

Ambient Kub

-30℃rau +55 degree, raws li kev pom zoo tsim

Kev teeb tsa

Sab hauv / Sab nraum zoov

Insulating kua

Mineral roj, FR3 ntuj ester, silicone kua, hydrocarbon-raws li kua, los yog lwm yam kev xaiv muaj raws li kev pom zoo

Tank Khoom

Me me hlau / Stainless hlau

Enclosure thiab Accessories

Kev ntsuas IP tshwj xeeb; CT, VT, thiab kev rho tawm hloov pauv muaj raws li kev pom zoo ntawm cov khoom siv

Cov qauv siv tau

IEC, ANSI/IEEE, NEMA, CSA, lossis lwm yam kev qhia tshwj xeeb

 

 

Kev kho kom haum

 

Customized Earthing Transformers rau Project Requirements

 

SCOTECH muab cov phiaj xwm tshwj xeeb earthing transformer tsim raws li kev pom zoo hluav taws xob

parameters, installation tej yam kev mob, thiab cov khoom siv uas yuav tsum tau muaj.

Hluav taws xob tsim

• System voltage thiab ntsuas zaus
• Zig-Zag, Star-Delta, lossis lwm yam kev pom zoo winding configuration
• Yuav tsum muaj nruab nrab tam sim no thiab lub sij hawm luv luv tam sim no
• Zero-sequence impedance thiab cov kev xav tau hauv av
• Rwb thaiv tsev theem thiab cov qauv kev siv tau

Kev tsim kho thiab kev teeb tsa

• Kev teeb tsa sab hauv lossis sab nraum zoov
• Cov khoom siv hauv lub tank thiab qhov chaw kaw
• Insulating kua xaiv yuav raug lees paub
• Terminal thiab bushing npaj
• Project-specific mounting thiab dimensional yuav tsum tau

 

Sib tham txog koj qhov project yuav tsum tau

 

 

Daim duab

 

Earthing Transformer Diagram

 

Cov duab kos tau pom yog los ntawm 370 kVA earthing transformer ntsuas 22/0.11 kV, muab rau ib qhov project tshwj xeeb. Lawv muab cov ntaub ntawv siv rau kev ntsuas kev sib txuas thiab chaw teeb tsa.

 

Hu rau SCOTECHrau daim duab sib txuas thiab cov duab kos duab sib txuam nrog koj qhov system voltage, winding configuration, thiab installation yuav tsum tau.

370 kVA Earthing Transformer Connection Diagram

 

 

Daim ntawv thov

 

Daim ntawv thov ntawm Earthing Transformers

 

Earthing transformers yog siv nyob rau hauv peb-theem fais fab system qhov twg yuav tsum tau ib qho khoom nruab nrab taw tes rau qhov teev

kev npaj hauv av. SCOTECH muab cov phiaj xwm tshwj xeeb hauv av transformers rau cov chaw siv hluav taws xob, txuas ntxiv mus

lub zog hluav taws xob, kev lag luam fais fab sib txuas, thiab kev sib txuas hluav taws xob.

Kev siv hluav taws xob substations thiab hluav taws xob faib

Earthing transformers tuaj yeem muab qhov chaw nruab nrab nruab nrab hauv nruab nrab-voltage tes hauj lwm uas tsis muaj kev sib txuas hauv nruab nrab. Lawv cov qauv tsim txhawb nqa txoj hauv kev hauv ntiaj teb-kev txhaum tam sim no thiab kev sib koom tes nrog lub network hauv av thiab kev tiv thaiv.

Renewable Energy Systems

Hauv kev siv hnub ci thiab cua tshuab hluav taws xob, earthing transformers tuaj yeem tsim ib qho kev siv hauv av rau cov khoom siv hluav taws xob uas xav tau los ntawm kev tsim hluav taws xob. Qhov kev xav tau ntawm lub ntiaj teb transformer nyob ntawm lub ntsiab transformer kev sib txuas, network configuration, thiab grounding kawm.

Industrial Power Systems

Kev tsim cov nroj tsuag, kev ua haujlwm mining, refineries, thiab lwm qhov chaw muaj kev lag luam yuav xav tau lub ntiaj teb transformers los tsim cov ntsiab lus nruab nrab hauv lawv qhov nruab nrab-voltage tis systems. Lub luag haujlwm tam sim no, impedance, kev teeb tsa, thiab kev tiv thaiv cuam tshuam nyob ntawm qhov tsim tshwj xeeb.

Transformer thiab Switchgear Installations

Earthing transformers tuaj yeem koom ua ke rau hauv kev teeb tsa hluav taws xob nrog rau lub zog hloov pauv, hloov pauv, cov khoom siv hauv av, thiab kev tiv thaiv. Terminal kev npaj, cov khoom siv nruab nrab hauv av, thiab kev tswj xyuas kev sib txuas yuav tsum tau ua haujlwm nrog kev pom zoo tsim qauv.

 

 

FAQ

 

Q: Dab tsi cuam tshuam rau tus nqi ntawm Earthing Transformer?

A: Tus nqi nyob ntawm qhov ntsuas hluav taws xob, xav tau nruab nrab tam sim no, lub sijhawm luv luv tam sim no, xoom-sequence impedance, winding configuration, rwb thaiv tsev yuav tsum tau, txias txoj kev, enclosure tsim, accessories, kuaj yuav tsum tau, thiab tus me nyuam tej yam kev mob. Muab cov lus qhia tshwj xeeb lossis daim duab kab ib kab pab cov neeg tsim khoom npaj cov lus hais kom raug.

Q: Kuv puas tuaj yeem tau txais cov khoom lag luam Digital?

A: Thov hu rau SCOTECH thov kom muaj cov khoom lag luam catalogs thiab cov ntaub ntawv qhia txog kev cuam tshuam rau koj qhov project yuav tsum tau ua.

Q: Puas yog SCOTECH muab Kev Pabcuam Tomqab Muag Khoom?

A: Yog. SCOTECH muab kev txhawb nqa kev muag khoom tom qab muag, suav nrog kev daws teeb meem kev taw qhia, kev sab laj kev txawj ntse, thiab kev pab kho. Kev them nyiaj yug ntawm qhov chaw nyob ntawm qhov chaw nyob ntawm qhov project thiab pom zoo qhov kev pabcuam.

Q: SCOTECH puas tuaj yeem muab kev cob qhia neeg ua haujlwm rau Earthing Transformers?

A: SCOTECH muaj kev cob qhia los pab cov neeg siv khoom nkag siab txog kev ua haujlwm thiab kev saib xyuas. Kev cob qhia kev npaj rau qhov project earthing transformer tshwj xeeb tuaj yeem tham thiab lees paub thaum lub sijhawm tshuaj xyuas.

Q: SCOTECH puas tuaj yeem tsim Earthing Transformers Raws li cov neeg siv khoom kos duab?

A: Yog. Cov neeg siv khoom tuaj yeem xa lawv cov duab kos duab thiab cov kev qhia tshwj xeeb rau kev tshuaj xyuas engineering.

 

 

Kev tsim khoom

 

Earthing Transformer Manufacturing Txheej txheem

 

SCOTECH's earthing transformer manufacturing txheej txheem npog engineering xyuas, core processing, winding ntau lawm,

tank fabrication, active-ib feem los ua ke, thiab zaum kawg los ua ke. Txhua theem ua raws li kev pom zoo tsim kos duab thiab

qhov project specifications los xyuas kom meej tias cov transformer ua tiav raws li qhov kev pom zoo

hluav taws xob thiab mechanical xav tau.

1. Kev tshuaj xyuas engineering thiab kev npaj cov khoom

Ua ntej pib tsim khoom, peb pab neeg ua haujlwm engineering yuav tshuaj xyuas qhov kev lees paub qhov system voltage, nruab nrab qhov ntsuas tam sim no, lub sijhawm luv luv tam sim no muaj peev xwm tiv taus, xoom-sequence impedance, thiab winding configuration.

2. Core Processing

Peb pab neeg txiav thiab sib sau ua ke cov ntawv hlau hluav taws xob raws li kev pom zoo sib nqus hluav taws xob tsim. Core qhov ntev, stacking, thiab sib dhos yog tswj kom ua tau raws li qhov tsim nyog tsim nyog thiab txhawb nqa cov khoom siv hluav taws xob.

3. Winding ntau lawm

Raws li kev tsim hluav taws xob tau teev tseg, peb ua cov tooj liab lossis aluminium conductors rau hauv windings. Qhov kev sib tw winding, qhov ntev ntawm tus neeg xyuas pib, cov txheej txheem rwb thaiv tsev, thiab kev sib txuas hluav taws xob yog txiav txim siab los ntawm qhov xav tau Zig-Zag (ZN), Star-Delta (YNd), lossis lwm yam kev pom zoo.

4. Tank Fabrication thiab Surface Treatment

Rau cov roj-immersed grounding transformers, peb cov tso tsheb hlau luam tau tsim raws li kev pom zoo kos duab, nrog rau kev teeb tsa ua ntej mounting txoj haujlwm rau terminals, bushings, txias Cheebtsam, thiab cov khoom siv tshwj xeeb. Vuam, deg pretreatment, tiv thaiv txheej, thiab accessory mounting kev npaj yog ua raws li cov kev tsim kho thiab installation yuav tsum tau.

5. Active-Part Assembly thiab ziab

Peb pab pawg engineering sib sau ua tiav cov windings mus rau hauv cov tub ntxhais transformer thiab nqa tawm cov kev sib txuas hauv hluav taws xob raws li cov qauv tsim. Ua ntej muab tso rau hauv lub tank, lub transformer los ua ke undergoes ib txoj kev ziab kom tswj nws cov dej noo.

6. Kev sib dhos zaum kawg thiab roj puv

Peb pab neeg txhim kho thiab ruaj ntseg transformer active ib feem (core thiab winding los ua ke) nyob rau hauv lub tank, ua raws li los ntawm lub installation ntawm bushings, terminals, nruab nrab kev twb kev txuas, thiab teev accessories. Tsis tas li ntawd, cov kua dej insulating tau ua tiav raws li cov txheej txheem tsim khoom tau pom zoo thiab tom qab ntawd muab ntim rau hauv lub tank.

wmpage07.webp
wmpage08.webp
wmpage09.webp
wmpage10.webp
wmpage11.webp
wmpage11.webp
wmpage11.webp
wmpage07.webp
 
 

 

 

Kuaj

 

Kev Tswj Xyuas Zoo thiab Kev Ntsuas rau Earthing Transformers

 

SCOTECH ua kev tshuaj xyuas thiab kev ntsuas hluav taws xob ntawm lub ntiaj teb transformers raws li qhov

pom zoo technical specifications thiab cov qauv siv tau.

Cov Kev Ntsuas Hluav Taws Xob niaj hnub

• Kev ntsuas qhov ntsuas cua
• Voltage ratio thiab winding kev twb kev txuas pov thawj, qhov twg muaj feem xyuam
• Tsis muaj-load poob thiab excitation tam sim no ntsuas
• Short-circuit impedance thiab load poob ntsuas, qhov twg muaj feem xyuam
• Zero-sequence impedance ntsuas
• Kev ntsuam xyuas Dielectric, suav nrog kev ntsuas lub zog-zaus muaj zog

Hom Kev Xeem

Hom kev ntsuam xyuas yog siv los xyuas qhov kev tsim qauv kev ua haujlwm raws li kev khiav hauj lwm lossis kev ntxhov siab hauv hluav taws xob. Nyob ntawm tus qauv tsim thiab siv tau, lawv tuaj yeem suav nrog kev ntsuas kub-nce, kev ntsuas hluav taws xob, lossis lwm yam kev ntsuas hom.
Cov kev xeem uas xav tau yog txiav txim siab los ntawm cov qauv siv tau, kev tsim qauv transformer, thiab cov ntawv cog lus pom zoo.

Kev kuaj tshwj xeeb

Cov kev ntsuam xyuas ntxiv tuaj yeem teev tau raws li qhov yuav tsum tau ua thiab qhov kev sim pom zoo. Cov no tuaj yeem suav nrog kev ntsuas luv luv tam sim no tiv thaiv kev ntsuas, ntsuas qhov tso tawm ib nrab, ntsuas lub suab nrov nrov, thiab kev ntsuas luv luv uas siv tau rau cov qauv tsim hluav taws xob.

1
2
3
4
5
6

 

 

Tiv tauj peb

 

Tau txais Daim Ntawv Tso Cai ntawm Earthing Transformer

Thov sau daim foos, thiab ib tus ntawm peb pab neeg yuav hu rau koj hauv 24 teev.

 

 
Finished single phase pad-mounted transformer units

 

Jiangshan Scotech Hluav Taws Xob Co., Ltd yog ib qho ntawm cov ua lag luam thiab cov chaw muag khoom ntawm lub ntiaj teb transformer hauv Suav teb. Peb sov siab txais tos koj mus yuav tus nqi-npaum hluav taws xob transformer rau muag ntawm no los ntawm peb lub hoobkas. Yog tias koj muaj lus nug txog kev hais lus lossis cov duab kos, thov koj xa email tuaj rau peb.