315 kVA Vpi Qhuav Hom Transformer-11/0.55 kV|South Africa 2025
Peev xwm: 315kVA
Lub hwj chim: 10/0.55kV
Feature: nrog cov kiv cua thiab H rwb thaiv tsev theem

VPI Qhuav-Hom Transformers: Qhov Kev Nyab Xeeb, Lub Hwjchim Muaj Zog Muaj Zog.
01 General
1.1 Project Description
Lub 315 kVA qhib winding qhuav hom transformer tau xa mus rau South Africa hauv 2025. Lub zog ntsuas ntawm qhov qhib winding qhuav hom transformer yog 315 kVA nrog AN / AF txias, thawj qhov hluav taws xob yog 11 kV nrog ± 2 * 2.5% tapping ntau (NLTC), theem nrab voltage yog 0.55 kV pawg ntawm lawv cov vector,
Cov khoom no yog qhib -hom, Class H qhuav- hom transformer tsim nrog advanced Vacuum Pressure Impregnation (VPI) thev naus laus zis, tshwj xeeb yog tsim los rau kev xav tau kev lag luam ib puag ncig. Nws cov windings tau dhau los ua ntau yam kev kho VPI los tsim cov txheej txheem H rwb thaiv tsev ntom ntom, muab qhov tshwj xeeb tiv thaiv kom ya raws, plua plav, thiab xeb. Tsim los nrog Class H rwb thaiv tsev cov ntaub ntawv thiab qhov kub siab tshaj 100K, nws muaj cov txheej txheem thermal zoo, ua kom lub neej ntev kev pab cuam thiab muaj peev xwm ua tau zoo dua txawm tias nyob rau hauv siab - qhov kub thiab txias. Qhov tshwj xeeb qhib-style tsim, ua ke nrog cov kiv cua txias ua haujlwm, ua kom tsis siv neeg kub- tswj cua txias, ua kom muaj peev xwm luv luv - lub sij hawm overload thiab ua kom ntseeg tau kev ua tau zoo raws li kev cuam tshuam. Featuring cov roj-dawb, nplaim taws- qauv tsim, nws muab kev nyab xeeb siab tshaj plaws thiab kev ntseeg siab, yog qhov zoo tshaj plaws rau 110V lub zog hluav taws xob, thiab tau siv dav hauv cov chaw tsim khoom, cov ntaub ntawv chaw, tsheb thauj mus los, thiab lwm yam kev siv uas xav tau kev nyab xeeb thiab kev ntseeg siab hauv kev xa hluav taws xob.
1.2 Technical Specification
315 kVA VPI qhuav hom transformer specification thiab cov ntaub ntawv ntawv
|
Xa rau
South Africa
|
|
Xyoo
2025
|
|
Hom
Qhib winding qhuav hom transformer
|
|
Cov khoom siv tseem ceeb
Grain oriented silicon steel ntawv
|
|
Txuj
IEC60076
|
|
Rated zog
315 kVA ua
|
|
Ntau zaus
50 HZ
|
|
Vector pawg
Dyn 11
|
|
Theem
3
|
|
Hom cua txias
ONAN/ONAV
|
|
Thawj Voltage
11kv ua
|
|
Secondary Voltage
0,55kv :ua
|
|
Cov khoom siv winding
Aluminium
|
|
Impedance
4%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
± 2 * 2.5% @ thawj sab los ntawm tapping txuas
|
|
Tsis Load Loss
1.1 KW TSI
|
|
Ntawm Load Loss
4.1 KW TSI
|
|
Rwb thaiv tsev theem
H
|
|
Winding kub nce @rated pab sab
100K
|
1.3 Cov duab kos
315 kVA VPI qhuav hom transformer daim duab kos duab thiab loj.
![]() |
![]() |
02 Kev tsim khoom
2.1 Core
Cov tub ntxhais yog tsim los ntawm qib siab - zoo lis- qhia txog silicon steel ntawv. Cov khoom siv tshwj xeeb no yog laminated meticulously thiab lub qhov txhab kom txo cov tub ntxhais poob thiab ua kom muaj kev sib nqus zoo. Nws cov nplej -cov qauv taw qhia txo qis hysteresis thiab eddy tam sim no poob, kom ntseeg tau zoo heev sib nqus permeability thiab tsis muaj -load fais fab noj. Cov tub ntxhais kawm tiav engineering pab txhawb rau lub transformer ua haujlwm siab, tsis muaj suab nrov, thiab tag nrho lub zog-txuag kev ua haujlwm.
2.2 Cua txias
Cov coils siv high-purity aluminium conductors, nqus tsev vacuum-pressure impregnated (VPI) nrog siab - qib insulating kua roj vanish. Cov txheej txheem no tsim cov khoom ruaj khov, noo noo- tiv thaiv rwb thaiv tsev uas ua kom zoo thermal stability, txhua yam muaj zog, thiab txhim khu kev qha ua haujlwm raws li qhov xav tau.

2.3 Kev sib dhos zaum kawg

Qhov kawg sib dhos ntawm VPI qhuav- hom transformer integrates impregnated core thiab coils mus rau hauv ib tug robust mechanical qauv, ruaj ntseg mounted nrog vibration-resistant fasteners. Kev sib txuas hluav taws xob yog qhov tseeb- txiav nrog siab- lub zog txuas, thaum cov kiv cua txias thiab cov ntaub thaiv npog tau teeb tsa kom ntseeg tau tias kev tswj xyuas thermal zoo thiab kev nyab xeeb ntawm kev ua haujlwm.
03 Kev Xeem
Kev ntsuam xyuas ntawm VPI qhuav hom transformer (315kVA-11/0.55kV) ntawm 2024/12/5, raws li IEC cov qauv, npog winding kuj (tsim nyog tsis sib npaug), voltage ratio/theem (me me sib txawv, Dyn11), luv-circuit/no-load parameters, tsis tshua muaj voltage (tsis muaj qhov sib npaug) thiab tsis sib npaug 10 npC). Tag nrho cov txiaj ntsig tau raws li qhov xav tau, tsim nyog.
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Kev txais txiaj ntsig |
Ntsuas Tus Nqi |
Xaus |
|
|
1 |
Kev ntsuas ntawm winding kuj |
/ |
Maximum kuj unbalance tus nqi Kab tsis kam: Tsawg dua lossis sib npaug li 2% |
HV (kab) |
LV (kab) |
Hla |
|
0.37% |
0.58% |
|||||
|
2 |
Kev ntsuas qhov sib piv ntawm qhov voltage thiab xyuas cov theem hloov chaw |
/ |
Kev kam rau siab ntawm qhov sib piv ntawm tus thawj tapping: ± 1/10 Cov cim kev sib txuas: Dyn11 |
0.02% ~ 0.18% Dyn 11 |
Hla |
|
|
3 |
Kev ntsuas luv- Circuit Court Impedance thiab Load Poob |
/ kW kW |
t: 120 degree Z%: ntsuas tus nqi Pk: ntsuas tus nqi Pt: ntsuas tus nqi |
4.27% 2.390 3.329 |
Hla |
|
|
4 |
Kev ntsuas tsis muaj -load poob thiab tam sim no ntawm 90% thiab 110% ntawm qhov ntsuas hluav taws xob |
/ kW |
I0 :: muab ntsuas tus nqi P0: muab ntsuas tus nqi |
90% ua |
0.81 0.9198 |
Hla |
|
100% Yog |
0.90 1.022 |
|||||
|
110% Yog |
0.99 1.124 |
|||||
|
5 |
Applied Voltage Test |
/ |
HV: 35kV 60s lwv: 3kv60 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
|
6 |
Induced Voltage Withstand Test |
/ |
Kev siv hluav taws xob (KV): 2 ua Induced voltage (KV): 1.1 Duration(s): 40 Zaus (HZ): 150 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
|
7 |
Kev kuaj qhov tso tawm ib nrab |
pC ua |
Qhov siab tshaj plaws ntawm kev tso tawm ib nrab yuav tsum yog 10 pC |
<10 |
Hla |
|


04 Packing thiab Shipping
4.1 Ntim
VPI qhuav- hom transformer yog ntim ruaj ntseg siv huab cua- tiv taus thiab poob siab- cov ntaub ntawv nqus. Lub transformer yog ruaj khov nyob rau hauv ib qho kev cai ntoo crate, nrog ntxiv tiv thaiv padding kom tsis txhob txav mus los. Cov khoom tseem ceeb tau npog nrog cov dej noo- pov thawj cov teeb meem, thiab tag nrho cov pob tau sau meej meej nrog kev tuav cov lus qhia thiab cov kev qhia tshwj xeeb los xyuas kom muaj kev nyab xeeb thiab ua haujlwm tau zoo.
4.2 Shipping
Raws li CIF (Cov Nqi, Kev Pov Hwm, thiab Kev Xa Khoom) cov nqe lus, VPI qhuav - hom transformer yuav raug xa mus rau qhov chaw nres nkoj ntawm Durban, South Africa. Tus neeg muag khoom tuav lub hiav txwv freight thiab marine insurance coverage, kom muaj kev tiv thaiv kev thauj mus los hauv huab cua -resistant, maritime- qib ntim. Tag nrho cov ntaub ntawv xa khoom tsim nyog (daim nqi ntawm daim ntawv tso cai, daim ntawv pov thawj, daim ntawv them nyiaj ua lag luam) yog muab rau kev lis kev cai zoo ntawm qhov chaw. Kev pheej hmoo hloov mus rau tus neeg yuav khoom thaum thauj khoom ntawm Durban chaw nres nkoj.
05 Site thiab Summary
VPI qhuav-hom transformer sawv ua lub hauv paus ntawm lub tshuab hluav taws xob niaj hnub, sib txuas kev ntseeg siab tsis sib xws nrog kev txiav- ntug engineering. Los ntawm Lub Tshuab Nqus Tsev Siab Impregnation (VPI) thev naus laus zis, Chav H rwb thaiv tsev, thiab kev tswj xyuas cov cua sov ntse, nws muab kev ua haujlwm tshwj xeeb, nplaim taws- tiv thaiv kev nyab xeeb, thiab kev ua haujlwm zoo hauv qhov chaw xav tau tshaj plaws. Los ntawm kev lag luam hluav taws xob faib khoom thiab kev sib txuas ua hluav taws xob txuas ntxiv mus rau cov ntawv thov tseem ceeb, VPI qhuav -hom transformer ua haujlwm nrog kev ua haujlwm ntsiag to, ua kom huv thiab ruaj khov xa hluav taws xob thoob ntiaj teb. Xaiv qhov transformer no txhais tau tias kev nqis peev hauv kev ruaj ntseg ntawm lub zog thiab kev ua haujlwm zoo rau yav tom ntej.
Cim npe nrov: vpi qhuav hom transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
1000 kVA Vpi Transformer-11/0.55 kV|South Africa 2024
630 kVA Qhuav Hom Step Down Transformer-11/0.55 kV|S...
630 kVA Qhuav Hom Fais Fab Transformer-11/0.55 kV|So...
630 kVA General Electric Dry Type Transformers-11/0....
630 kVA Nqus Siab Impregnated Transformer-11/0.55 kV...
630 kVA Vpi Hom Transformer-11/0.55 kV|South Africa ...
Xa kev nug