630 kVA VPI Type Transformer

Kev nyab xeeb tau ntsib kev ruaj khov: Xaiv cov tshuab qhuav hom hloov rau ib tus greener, roj {{free daws!

 

 

01 dav dav

1.1 phiaj xwm kev qhia

Lub 630 kva qhib winding qhuav hom transformer tau xa mus rau South Africa yog 0.55kv, lawv tsim ib pawg vector ntawm dyn11.

VPI (nqus plua plav impregnated) cov tshuab hloov cua qhuav yog ua rau muaj kev cuam tshuam nrog kev ua kom muaj zog thiab kev lag luam muaj txiaj ntsig zoo. Tsim los ua kom muaj kev phom sij tua hluav taws vim lawv cov kev hloov pauv qis, cov kev hloov pauv no txo ​​qis kev ua haujlwm ib puag ncig thaum muaj kev ruaj khov nyob rau hauv cov kev sib tw ntawm huab cua. Siv cov khoom lag luam siab siab ua haujlwm, peb VPI Transformers xa cov hluav taws xob develess thiab txhim kho cua sov xa cov hluav taws xob kev nyab xeeb thiab resilience los ntawm dej nyab.

Txawm tias yuav siv cov tsev kawm ntawv, kev saib xyuas kev noj qab haus huv, lossis cov qauv siv hluav taws xob, VPI qhuav hom kev ruaj ntseg thiab tus nqi {{0} {{0} {{0} {{0} {{0} {}}}} {}}}}}}}}} Cov kev daws teeb meem zoo. Nrog rau kev tsim tshwj xeeb thiab cov khoom siv zoo, cov hloov pauv no yog qhov zoo tshaj plaws rau cov ntawv thov uas xav tau kev nyab xeeb thiab ua tau zoo.

 

 

 

1.2 Kev Qhia Txuj Ci

630 KVA VPI Cov hom hloov pauv hloov kho cov ntaub ntawv tshwj xeeb thiab cov ntaub ntawv cov ntaub ntawv

Xa mus rau
Jamaica
Lub xyoo
2025
Ntaus
QHIB WINDING qhuav hom transformer
Cov Khoom Siv Tseem Ceeb
Lis Oriented Silicon Daim Ntawv
Lub hom phiaj
Iec60076
Rated zog
630 KVA
Hov ntau
50 hli
Vector Group
Dyn11
Caij
3
Cua Txias Hom
Onan / onaf
Thawj qho voltage
11 kv
Qhov hluavtaws theem ob
0.55 kv
Khoom siv winding
Tooj dawb
Kev yuam
6%
Tus kais hloov tsheb
Nltc
Tapping ntau
±2*2.5%@primary sab los ntawm tapping txuas
Tsis muaj nra poob
1.1kw
Ntawm kev thauj khoom poob
8.3kw
Kev thaiv kev theem
H

 

 

1.3 Daim Duab

630 KVA VPI DAB HLOOV DEBRAM kos duab thiab qhov loj me.

630 kVA VPI dry type transformer diagram

 

02 kev tsim khoom

2.1 Tub ntxhais

Cov tub ntxhais ntawm VPI (lub tshuab nqus tsev siab impregnated) qhuav {}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}

Featuring txias- rolled, oriented Lamations, nws minimizes zog poob thiab ua haujlwm tau zoo hauv qab qib. Qhov precision-}}}}}}-s enterints tshem tawm cov khoob khoob, kom nruj haum rau kev ua tau zoo.

Lub kaw lus ruaj khov ua rau muaj kev ruaj khov thiab txhawb nqa rau kev sib dhos rau kev sib dhos. Cov kev xaiv siv muaj xws li txheem lub pob tw- lap lossis mitered kev teeb tsa. Kev co - Dampening pads cais tawm cov tub sab los ntawm kev ntxhov siab sab nraud, thaum lub sij hawm tiv thaiv ruaj khov thiab kev ntseeg tau nyob rau hauv ntau yam kev ua haujlwm.

non-aging silicon steel iron core

 

2.2 cua

VPI dry-type transformer winding

Lub kauj ntawm VPI (nqus plua plav impregnated) qhuav - hom transformer yog tsim rau kev ua tau zoo thiab kev ntseeg tau. Qhov qis - voltage coil yog qhov txhab siv cov tshuab welfing, uas ua kom muaj kev ua tau zoo ntawm lub kauj thiab txo qis zog ntawm lub zog. Cov coil no insulated nrog shs (silicon siab lub zog) cov khoom siv hluav taws xob, muab cov hluav taws xob hluav taws xob zoo.

Lub siab - voltage coil, ntawm qhov tod tes, yog tsim siv siv cov qauv hlau winding.

Txhua qhov siab - voltage winding yog ua tib zoo qhwv nrog cov khoom insulating nrog kev nyab xeeb thiab ua haujlwm zoo. Tsis tas li ntawd, tag nrho cov rooj sib txoos hauv lub tshuab nqus tsev siab impregnation (vpi) los tiv thaiv kev ua kom muaj kev sib cais thiab ruaj khov thiab muaj kev ruaj ntseg nyob rau hauv kev sib txawv.

 

2.3 Zaum Kawg

1. Chev kho:Kev nyab xeeb nruab ua ntej - Casting Coils mus rau cov qauv raws li cov qauv tsim qauv los lav qhov ntsuas hluav taws xob.

2. Kev sib txuas hluav taws xob:Txuas lub siab - voltage thiab qis {{- voltage cables, kom txhua yam sib txuas muaj zog thiab ua raws cov qauv.

3. Lub siab loj thiab qis clamping joke los ua ke:Qhov tseeb li dlaus thiab ruaj ntseg nrawm nrawm rau sab saud thiab qis dua clamping Cheebtsam rau tus qauv coj muaj peev xwm ntawm lub zog ntawm lub transformer.

4. Cov Khoom Siv Txhawb Zog:Nruab ntau cov khoom siv xws li cov tswj kom sov, kiv cua kom ntseeg tau tias cov khoom siv kom zoo ntawm cov khoom siv.

630 kVA vpi type transformer assembly

 

 

03 kuaj

Tsis yog.

Ntsuas Yam

Ib yam

Txais qhov tseem ceeb

Kev ntsuas qhov tseem ceeb

Tag

1

Kev Ntsuas Ntawm Winding Kuj

/

Qhov Ntau Tshaj Plaws Tsis Tau

Kab tsis kam: tsawg dua los yog sib npaug rau 2%

HV (kab)

LV (kab)

Daim pib

0.21%

0.11%

2

Kev ntsuas ntawm voltage piv thiab tshawb xyuas theem kev sib tsoo

/

Kev thev siab ntawm voltage piv rau tus thawj xibfwb tapping: ± 1/10

Kev Txuas Txuas: Dyn11

-0.03% ~ 0.10%

Dyn11

Daim pib

3

Kev ntsuas ntawm luv - Circuit Court Impedance thiab Thauj Khoom Poob

/

kw

kw

T: 120 Qib

Z%: Ntsuas cov nqi

PK: ntsuas tus nqi

PT: ntsuas tus nqi

6.16%

4.529

6.048

Daim pib

4

Kev ntsuas ntawm tsis muaj {{0} butlock poob thiab tam sim no ntawm 90% thiab 110% ntawm ntsuas hluav taws xob

/

kw

I0 :: muab tus nqi ntsuas

P0: Muab tus nqi ntsuas

90% koj

0.468

1.006

Daim pib

100% ur

0.52

1.118

110% ur

0.572

1.229

5

Siv cov ntawv ntsuas voltage

/

HV: 35KV 60s

LV: 3KV 60

Tsis muaj kev sib tsoo ntawm kev xeem voltage tshwm sim

Daim pib

6

Inducts voltage wallstand kuaj

/

Siv Voltage (KV):

2 ur

Tis Voltage (KV): 1.1

Duration (s): 40

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm kev xeem voltage tshwm sim

Daim pib

7

Kev Ntsuas Ib Cheeb Tsam

PC

Theem siab tshaj plaws ntawm ib nrab tso tawm yuav tsum yog 10 lub PC

<10

Daim pib

 

630 kVA vpi type transformer test
630 kVA vpi type transformer fat

 

 

04 ntim thiab xa khoom

4.1 packing

VPI qhuav -}} hom transformer yog ntim rau hauv ib qho chaw ua pov thawj nrog anti- corrosion aluminium ncej qhwv. Mekas Shock -}} nqus nkhaus thiab cov ntaub ntawv Cushioning tau thov los tiv thaiv cov khoom tseem ceeb. Cov ntim tau raws IEC 60076-11 tus qauv, haum rau dej hiav txwv thauj khoom thiab kev thauj mus los.

VPI dry-type transformer is packed in a wooden crate

 

4.2 shipping

Vacuum Pressure Impregnated dry transformer shipping

VPI (nqus plua plav impregnated) qhuav hom transformer tau thauj hauv Cif (nqi, thiab thauj khoom) cov xwm txheej rau Durban. Nws yuav tau ntim khoom nrog cov ntaub ntawv tiv thaiv kom tiv thaiv kev puas tsuaj, thauj khoom mus rau lub nkoj thauj khoom, thiab pov hwm thaum lub sijhawm hla. Thaum tuaj txog, tus transformer yuav yauv ua kev lis kev cai kom raws li cov cai hauv nroog, tom qab nws yuav tau txais kev ua tib zoo thauj mus rau qhov chaw xa khoom zaum kawg rau kev teeb tsa. Txhua qhov kev ceev faj tsim nyog yuav raug coj los xyuas kom muaj kev nyab xeeb thiab ncav sijhawm.

 

 

05 lub vev xaib thiab cov ntsiab lus

Hauv kev xaus, lub VPI (lub tshuab nqus hluav taws xob impregnated) qhuav hom transformer sawv cev rau lub ncov siab niaj hnub, kev nyab xeeb, thiab ib puag ncig kev nyab xeeb. Nws cov tsim kev tsim txiaj thiab siab - cov ntaub ntawv zoo ua kom tau kev ua tau zoo nyob rau ntau daim ntawv thov, los ntawm kev lag luam cov vaj tse. Nrog qis ua ke thiab ua tau zoo heev rau cov kev cuam tshuam hluav taws xob, VPI transformer tsis yog ntsib tab sis ntau tshaj li kev lag luam qauv. Xaiv lub VPI cov hom hloov pauv hloov pauv mus ua haujlwm nyob rau yav tom ntej uas ua tau zoo thiab kev nyab xeeb mus rau sab tes, toj roob hauv pes kom muaj zog ntxiv.

630 kVA VPI Type Transformer South Africa

 