630 kVA Qhuav Hom Fais Fab Transformer-11/0.55 kV|South Africa 2024

630 kVA Qhuav Hom Fais Fab Transformer-11/0.55 kV|South Africa 2024

Lub teb chaws: America 2024
Peev xwm: 630 kVA
Lub hwj chim: 11/0.55 kV
Feature: nrog kub tswj
Xa kev nug

 

 

630 kVA dry type power transformer

Mus Ntsuab, nyob nyab xeeb: Peb qhib Winding qhuav hom Transformers Muab Eco- cov phooj ywg thiab ruaj ntseg zog daws!

 

01 General

1.1 Project Background

Lub 630 kVA qhib winding qhuav hom transformer tau xa mus rau South Africa hauv 2024; Lub zog ntsuas ntawm lub transformer yog 630 kVA. Thawj qhov voltage ntawm lub transformer yog 11 kV thiab theem nrab voltage yog 0.55 kV. SCOTECH's open winding dry type transformers muaj cov yam ntxwv ntawm lub zog luv luv - Circuit Court tsis kam, kev ua haujlwm me me, kev ua haujlwm siab, me me, tsis tshua muaj suab nrov, thiab feem ntau siv rau hauv qhov chaw uas muaj kev ua haujlwm siab xws li kev tiv thaiv hluav taws thiab tiv thaiv tawg. Kev nyab xeeb, fireproof, tsis muaj kuab paug, tuaj yeem ua haujlwm ncaj qha rau hauv siab load zog. Cov khoom yog H chav kawm, cov khoom siv rwb thaiv tsev yog C chav kawm, luv luv - Circuit Court kuj muaj zog, thiab kev nyab xeeb kev ua haujlwm siab. Kev ua tau zoo thaum tshav kub kub dissipation, muaj zog tshaj qhov muaj peev xwm, luv -lub sij hawm super- muaj peev xwm ua haujlwm nyob rau hauv yuam cua txias. Zoo thiab siab permeability silicon steel, ntau- cov txheej txheem, bass nrov txo, tsis muaj -load poob. SCOTECH tsim qhib winding qhuav hom transformers uas muaj zog huab cua hloov tau, noo noo, ntsev tsuag thiab corrosion kuj, muaj zog huab cua tsis kam thiab kev pab lub neej ntev. Siv ntau yam thev naus laus zis, ua kom muaj kev sib haum xeeb zoo, lim kev sib haum xeeb, thiab ua kom lub cev muaj zog ntev.

Peb 630 kVA qhib winding qhuav hom transformer tau tsim los nrog cov thev naus laus zis siab heev thiab siv cov khoom zoo thiab cov khoom siv, uas ua rau muaj kev ntseeg tau zoo thiab lub sijhawm ua haujlwm ntev.

Peb xyuas kom meej tias txhua qhov ntawm peb cov khoom xa tuaj tau dhau los ua qhov kev lees paub tag nrho. Peb muab ib qho - kev pab cuam pob los ntawm kev sab laj, hais tawm, tsim khoom, teeb tsa, commissioning, kev cob qhia rau tom qab - kev muag khoom. Peb cov khoom tam sim no ua haujlwm hauv ntau tshaj 50 lub teb chaws hauv ntiaj teb. Peb lub hom phiaj los ua koj tus neeg muag khoom ntseeg siab tshaj plaws nrog rau koj tus khub zoo tshaj plaws hauv kev lag luam!

 

1.2 Technical Specification

630 kVA qhib winding qhuav hom transformer specification thiab cov ntaub ntawv ntawv

Xa rau
South Africa
Xyoo
2024
Qauv
630kVA - 11/0.55kV
Hom
Qhib winding qhuav hom transformer
Txuj
IEC60076
Rated zog
630kVA ua
Ntau zaus
50 tzs
Theem
3
Hom cua txias
UA/AF
Thawj Voltage
11kv ua
Secondary Voltage
0,55kv :ua
Cov khoom siv winding
Aluminium
Impedance
6%
Coj mus rhaub Changer
NLTC
Tapping Range
± 2 * 2.5% @ thawj sab
Tsis Load Loss
1.1 KW TSI
Ntawm Load Loss
8.3 kWv
Khoom siv
Standard Configuration
Rwb thaiv tsev theem
H
Basic impulse teeb pom kev zoo tiv taus voltage- sab xub ntiag (BIL)
75kv ua
Lub zog zaus tiv taus qhov voltage- sab xub ntiag
35kv ua
Basic impulse teeb pom kev zoo tiv taus voltage-secondary side (BIL)
/
Fais fab zaus tiv taus qhov voltage-secondary side
3kv ua
Winding kub nce @ ntsuas kev pabcuam
100K

 

1.3 Cov duab kos

630 kVA qhib winding qhuav hom transformer daim duab kos duab thiab loj.

630 kVA opening winding dry type transformer drawing

 

 

02 Kev tsim khoom

2.1 Core

Lub luag hauj lwm ntawm qhuav transformer core yog tsim ib tug sib nqus Circuit Court. Yuav kom txo tau qhov poob tam sim no, cov tub ntxhais yog ua los ntawm nyias silicon steel ntawv staggered. Qhov saum npoo ntawm silicon steel ntawv yog coated nrog insulating xim thiab oxidized los tsim ib txheej insulating. Cov tub ntxhais yog tsim los ntawm cov tub ntxhais hlau lub cev, fasteners thiab insulating qhov chaw. Cov tub ntxhais kawm siv ntau- cov txheej txheem los ntawm cov txheej txheem tso rau hauv qhov tseem ceeb. Nyob rau hauv ntau yam kev ua haujlwm, cov tub ntxhais tsis muaj kev hloov pauv mus rau qhov ntev thiab ntev.

630 kVA dry type power transformer iron core

 

2.2 Cua txias

630 kVA dry type power transformer winding

Lub winding ntawm lub transformer yog ua los ntawm fireproof chav H enamelled hlau, uas muaj kev ua tau zoo heev thiab kub dissipation, thiab yog teem kom nruj thiab sib npaug. Thaum winding, cylindrical winding yog siv, thiab qis -voltage winding yog nyob ze rau lub hauv paus txhawm rau tiv thaiv nws los ntawm cov tub ntxhais. Lub high voltage winding yog centrally kaw sab nraum lub low voltage winding. Cov windings feem ntau yog cascading los yog helical tsim los txo cov hlau nplaum to thiab txhim kho qhov ua tau zoo ntawm lub transformer. Lub winding ntawm qhib winding qhuav hom transformer tsis txwv los ntawm lub plhaub kaw thiab muaj peev xwm dissipate tshav kub nyob rau hauv cov huab cua, yog li nws cov cua kub dissipation kev ua tau zoo kuj zoo. Qhov kev tsim no tsim nyog siv rau hauv qhov chaw uas muaj qhov kub thiab txias dua los yog qhov cua zoo dua.

 

2.3 Lub Rooj Sib Tham Kawg

Kev kho rwb thaiv tsev: Siv cov ntaub ntawv rwb thaiv tsev thiab xyuas qhov tseeb ntawm cov rwb thaiv tsev.

Kev xaim: Nruab cov terminals thiab txuas cov xov hlau kom raug.

Lub Tsev Sib Tham: Txhim kho lub tsev thiab xyuas kom muaj kev sib khi zoo.

630 kVA dry type power transformer assembly

 

 

03 Kev Xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Kev txais txiaj ntsig

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntawm winding kuj

/

Maximum kuj unbalance tus nqi

Kab tsis kam: Tsawg dua lossis sib npaug li 2%

HV (kab)

LV (kab)

Hla

0.26%

0.65%

2

Kev ntsuas qhov sib piv ntawm qhov voltage thiab xyuas cov theem hloov chaw

/

Kev kam rau siab ntawm qhov sib piv ntawm tus thawj tapping: ± 1/10

Cov cim kev sib txuas: Dyn11

-0.05% ~ 0.14%

Dyn 11

Hla

3

Kev ntsuas luv- Circuit Court Impedance thiab Load Poob

/

kW

kW

t: 120 degree

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

6.14%

5.59

7.243

Hla

4

Kev ntsuas tsis muaj -load poob thiab tam sim no ntawm 90% thiab 110% ntawm qhov ntsuas hluav taws xob

/

kW

I0:: muab ntsuas tus nqi

P0: muab ntsuas tus nqi

90% ua

110% Yog

Hla

0.342%

0.418%

0.951

1.162

5

Applied Voltage Test

/

HV: 35kV 60s

lwv: 3kv60

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

6

Induced Voltage Withstand Test

/

Kev siv hluav taws xob (kV):

2 ua

Induced voltage (kV): 1.1

Duration(s): 40

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Kev kuaj qhov tso tawm ib nrab

pC ua

Qhov siab tshaj plaws ntawm kev tso tawm ib nrab yuav tsum yog 10 pC

<10

Hla

 

630 kVA dry type power transformer testing
630 kVA dry type power transformer test

 

 

04 Packing thiab Shipping

630 kVA dry type power transformer packing
630 kVA dry type power transformer shipping

 

05 Site thiab Summary

Hauv thaj chaw tseem ceeb ntawm kev xa hluav taws xob thiab kev faib tawm, qhov qhib winding qhuav hom transformer tau dhau los ua ib qho tseem ceeb ntawm cov tshuab hluav taws xob niaj hnub vim nws qhov kev ua tau zoo thiab kev ntseeg tau. Peb tau cog lus los muab peb cov neeg siv khoom nrog siab - zoo qhuav hom transformers, kom ntseeg tau tias kev siv hluav taws xob zoo thiab kev ua haujlwm nyab xeeb. Txawm hais tias nyob rau hauv kev lag luam, kev lag luam, lossis kev siv hauv tsev, peb qhib winding qhuav hom transformers yuav muab koj cov kev daws teeb meem ruaj khov thiab txhim khu kev qha. Xaiv peb cov khoom txhais tau tias xaiv qhov zoo tshaj plaws thiab kev pabcuam zoo tshaj. Ua tsaug rau koj txoj kev ntseeg thiab kev txhawb nqa; peb tos ntsoov yuav ua haujlwm ua ke los tsim lub neej yav tom ntej.

630 kVA opening winding dry type power transformer

 

Cim npe nrov: qhuav hom fais fab transformer, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug