50 kVA Tib Ncej Mounted Transformer-13.8/0.347 kV|Canada 2025

50 kVA Tib Ncej Mounted Transformer-13.8/0.347 kV|Canada 2025

Lub teb chaws: Canada 2025
Muaj peev xwm: 50kVA
Qhov hluav taws xob: 13.8 / 0.347kV
Feature: nrog ntes
Xa kev nug

 

 

single pole mounted transformer

Tsis Txhob ntshai xob laim, Tsis muaj hluav taws xob tawm-24/7 Kev tiv thaiv nrog peb tus ncej Mounted Transformer!

 

 

01 General

1.1 Project Description

Xyoo 2025, 50 kVA ib zaug -theem ncej- mounted transformer tau raug xa mus rau Canada rau kev siv nyob rau hauv cov neeg nyob deb nroog thiab ib nrab- hauv nroog faib network. Lub tsev kawm ntawv ua haujlwm pab pawg me me thiab thaj chaw hauv zos lossis kev lag luam thauj khoom siv los ntawm 13.8 kV nyiaj siv ua haujlwm. Tsim los tswj cov kev xav tau ntawm lub caij nyoog siab tshaj plaws thiab nquag cua daj cua dub, lub tshuab hloov ua kom ruaj khov, muaj zog txaus txawm tias nyob hauv ib puag ncig hnyav.

Ua rau CSA C2.2-06 tus qauv, chav tsev nta ONAN txias, 13.8 kV / 0.347 kV ratings, Ii6 vector pawg, thiab Additive polarity. Nws suav nrog NLTC kais hloov pauv nrog ± 2 × 2.5% ntau yam rau kev hloov pauv qhov tseeb. Nrog aluminium windings, 2.3% impedance, thiab 98.35% kev ua haujlwm, nws muaj kev ua tau zoo nrog kev poob qis thiab kev saib xyuas yooj yim.

Mounted ntawm tus qauv faib ncej nrog lub fused thawj txiav tawm, surge arrester, thiab grounding system, no transformer muab ib tug muaj kev ruaj ntseg thiab saj zawg zog faib kev daws teeb meem. Qhov zoo tshaj plaws rau kev siv hluav taws xob nyob deb nroog, kev sib tham hauv xov tooj, thiab cov khoom siv me me, nws ua ke ua haujlwm ntev, kev ntseeg tau, thiab kev tswj hluav taws xob zoo heev hauv ib qho kev tsim sab nraum zoov.

 

 

 

1.2 Technical Specification

50 kVA ncej mounted transformer specifications hom thiab cov ntaub ntawv ntawv

Xa rau
Canada
Xyoo
2025
Hom
Ncej mounted transformer
Txuj
CSA C2.2-06
Rated zog
50 kVA
Ntau zaus
60 tzs
Theem
1
Polarity
Ntxiv
Hom cua txias
ONAN
Thawj Voltage
13.8 kV 2
Secondary Voltage
0, 347 kv
Cov khoom siv winding
Aluminium
Angular tshem tawm
Ib 6
Impedance
2.3%
Coj mus rhaub Changer
NLTC
Tapping Range
±2*2.5%
Tsis Load Loss
0.135 kWm
Ntawm Load Loss
0.705 kWm

 

 

1.3 Cov duab kos

50 kVA ncej mounted transformer daim duab kos duab thiab loj.

single pole mounted transformer diagram single pole mounted transformer nameplate

 

 

02 Kev tsim khoom

2.1 Core

Qhov no transformer nta ib tug siab heev lub qhov txhab tsim, qhov twg cov tub ntxhais yog tsis tu ncua raug mob los ntawm siab -permeability txias- dov silicon steel strips los ua ib tug seamless kaw magnetic Circuit Court. Piv rau cov pa laminated cores, lub qhov txhab qhov txhab muaj qis dua tsis muaj -load poob, txo suab nrov, tsis sib xws flux tis, thiab txhim khu kev tiv thaiv luv luv.

advanced wound core design

 

2.2 Cua txias

current losses

Lub tshuab hluav taws xob no siv thev naus laus zis thev naus laus zis: qhov qis -voltage (LV) sab siv cov ntawv ci winding rau superior tam sim no - nqa peev xwm thiab cua sov dissipation, zoo txo ​​eddy tam sim no poob; thaum lub siab -voltage (HV) sab txais precision txheej hlau winding los xyuas kom meej rwb thaiv tsev lub zog thiab voltage stability. Qhov no "foil-mob LV + xaim-mob HV" ua ke tsim ua tiav kev ua haujlwm zoo, compactness thiab luv luv -circuit resistance, ua rau nws zoo tagnrho rau kev thov sab nraum zoov ncej- mounted daim ntaub ntawv.

 

2.3 Tank

Qhov no transformer siv lub hermetically kaw cylindrical tank tsim los ntawm precision roller dabtsi yog khoov txheej txheem. Ua los ntawm premium txias-rolled steel, lub tank yog zoo li tus CNC dov tshuab nrog tsuas yog ib tug precision laser -welded longitudinal seam, nruj me ntsis soj ntsuam los ntawm X- rays thiab xau kuaj. Lub cylindrical tsim tsis tsuas yog compact aesthetics tab sis kuj tshwj xeeb mechanical zog thiab tshav kub dissipation, featuring lub sab hauv roj guiding raws rau npaum ntuj txias. Nrog triple - txheej tiv thaiv - txheej txheej corrosion (primer + epoxy intermediate + polyurethane topcoat), nws tiv taus qhov chaw hnyav xws li ntsev tsuag thiab kua qaub los nag.

sealed cylindrical tank

 

2.4 Lub Rooj Sib Tham Kawg

single pole mounted transformer final assembled

1. Winding Assembly:Xaub lub HV / LV windings mus rau lub laminated core, kom ntseeg tau tias kev sib raug zoo thiab rwb thaiv tsev clearance.
2. Kev sib txuas hluav taws xob:Txuas winding ua rau kais hloov pauv, bushings, thiab lwm yam khoom, ua raws li kev kho kom nruj thiab rwb thaiv tsev.
3. Core-Coil ziab:Muab cov khoom sib dhos ua ke rau hauv qhov cub kom qhuav kom tshem tawm cov dej noo thiab txhim kho kev ua haujlwm ntawm rwb thaiv tsev.
4. Tank Installation:Nqa cov khoom ua haujlwm qhuav rau hauv lub tank, ruaj ntseg rau hauv txoj hauj lwm, thiab kaw lub tank npog.
5. Accessory Mounting:Nruab bushings, ntes, siab nyem valve.
6. Roj Sau & Sealing:Lub tshuab nqus tsev- sau nrog cov roj insulating, xyuas cov roj qib thiab sealing tom qab kev daws teeb meem, thiab ua qhov kev ntsuam xyuas zaum kawg kom tiav.

 

 

03 Kev Xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Kev txais txiaj ntsig

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

/

/

/

Hla

2

Kev ntsuas ntsuas

/

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Ii6

0.06~0.10

Hla

3

Kev ntsuam xyuas polarity

/

Ntxiv

Ntxiv

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

%

I0 :: muab ntsuas tus nqi (100%)

0.24

Hla

kW

P0: muab ntsuas tus nqi (100%)

0.1065

%

I0 :: muab ntsuas tus nqi (105%)

0.24

kW

P0: muab ntsuas tus nqi (105%)

0.1172

/

qhov kam rau tsis muaj load poob yog +10%

/

5

Load poob, impedance voltage, tag nrho poob thiab efficiency

/

t:85 ua

Qhov kam rau ua impedance yog ± 15%

qhov kam rau tag nrho load poob yog +6%

/

Hla

%

Z%: ntsuas tus nqi

2.28

kW

Pk: ntsuas tus nqi

0.634

kW

Pt: ntsuas tus nqi

0.7405

%

Kev ua haujlwm tsis tsawg dua 98.84%

99.01

6

Applied Voltage Test

/

LV: 10kV 60s

HV: 34kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

/

Kev siv hluav taws xob (KV): 2 Ur

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

Duration(s): 40

Zaus (HZ): 180

8

Rwb thaiv tsev Resistance Measurement

HV-LV·to·Ground

451

Hla

LV-HV to Av

489

HV&LV to Av

113

9

Kev Xeem Leakage

/

Kev siv siab: 20kPA

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

Duration: 12h

10

Roj Xeem

kV ua

Dielectric zog

61.3

Hla

mg/kg

Cov ntsiab lus noo noo

10.6

%

Dissipation Factor

0.091

mg/kg

Furan Analysis

Tsawg dua los yog sib npaug li 0.1

/

Gas Chromatography Analysis

/

 

single pole mounted transformer test
single pole mounted transformer routine test

 

 

04 Packing thiab Shipping

4.1 Ntim

Lub tshuab hloov pauv tau ntim rau hauv ib lub thawv ntim ntoo uas tsim los nrog cov dej noo- cov ntaub ntawv pov thawj plywood, featuring kev cai- molded foam inserts thiab anti- vibration brackets kom immobilize chav tsev thaum lub sij hawm thauj mus los. Sab nrauv yog coated nrog cov kua roj vanish tsis muaj dej thiab ntxiv dag zog nrog cov hlua hlau, nruab nrog hnyav- lub luag haujlwm nqa nqa ntawm txhua lub ces kaum. Ua ntej packing, lub transformer undergoes lub nqus tsev vacuum qhuav thiab puv nrog 0.02MPa nitrogen. Cov cim thoob ntiaj teb tseem ceeb rau qhov nruab nrab ntawm lub ntiajteb txawj nqus, "Keep Dry" thiab "Side Up" yog tso tawm. Muaj ntawv pov thawj rau ISTA 3A cov qauv, lub ntim nrog 2000km kev thauj mus los thiab thoob ntiaj teb hiav txwv freight tej yam kev mob.

enclosed wooden crate

 

4.2 Shipping

CIF terms

Cov transformers yuav raug xa mus raws li CIF (Cov Nqi, Kev Pov Hwm, thiab Freight) cov nqe lus, tawm ntawm Ningbo chaw nres nkoj mus rau Chaw nres nkoj ntawm Montreal. Cov khoom xa tuaj yuav raug thauj los ntawm cov thawv ntim khoom hauv hiav txwv, nrog rau kev nyab xeeb thiab kev tiv thaiv kev tiv thaiv (tiv thaiv- poob siab, ya raws- pov thawj, thiab tiv thaiv- xeb) kom muaj kev nyab xeeb ntev - kev thauj mus los hauv hiav txwv. Tus neeg muag khoom yuav npaj kev thauj mus los hauv hiav txwv thiab muab kev tuav pov hwm marine (Tag nrho cov kev pheej hmoo), suav nrog kev puas tsuaj vim muaj xwm txheej lossis kev puas tsuaj ntuj tsim thaum caij tsheb npav. Thaum tuaj txog ntawm Montreal, tus neeg yuav khoom yog lub luag haujlwm rau kev lis kev cai thiab kev thauj mus los hauv av ntxiv.

 

 

05 Kev saib xyuas ntawm ncej-mounted transformers

Kev tuav tus ncej-mounted transformers tsis yog hais txog ticking tawm ntawm daim ntawv teev npe. Nws yog hais txog kev ua kom txhua chav ua haujlwm txuas ntxiv kom nyab xeeb, ua tau zoo, thiab ntev li ntev tau. Kev nyab xeeb, kev cia siab, thiab sib xws - lawv txhua tus nyob ntawm cov ntsiab lus me me. Qee zaum, cov ntsiab lus uas lwm tus saib dhau.
(1) Kev Tshawb Fawb Txog Kev Pom Zoo tsis tu ncua
Thawj kauj ruam yog qhov yooj yim tshaj plaws - tsuas yog saib. Kev soj ntsuam ceev feem ntau qhia ntau dua li daim ntawv tshaj tawm. Tshawb xyuas cov roj xau, corrosion, lossis dents. Roj stains tej zaum yuav qhia ib tug phem foob; xeb tuaj yeem txhais tau tias lub tank maj mam poob nws lub zog. Txhim kho cov no thaum ntxov- ua ntej lawv loj hlob mus rau cov teeb meem loj dua - txuag lub sijhawm thiab khoom siv.
(2) Roj Qib thiab Kev Ntsuas Zoo
Transformer roj yog nws cov ntshav. Nws txias, insulates, tiv thaiv. Cov roj tsawg? Qhov ntawd yog tus chij liab. Tsaus lossis huab roj? Kuj teeb meem. Scotech qhov kev paub qhia tau hais tias kev kuaj roj tsis tu ncua, txawm tias ceev ceev, tiv thaiv feem ntau ntawm cov cua sov ua ntej lawv pib.
(3) Roj Purification
Tam sim no, qee zaum kev tshuaj xyuas tsis txaus. Cov roj yuav zoo li zoo tab sis poob nws cov khoom nyob rau lub sijhawm - ya raws, roj av, cov khoom me me nkag mus rau hauv. Qhov ntawd yog thaum purification los rau hauv. Lub tshuab nqus dej, pom, degassing… me ntsis kev, yog, tab sis tsim nyog. Txhua lub voj voog rov ua kom cov roj lub zog, txuas ntxiv lub neej ntawm transformer.
(4) Kev sib txuas ceev ceev
Loose bolts tsis ua suab nrov, tab sis lawv ua rau muaj teeb meem tiag tiag - arcing, tshav kub kub, tsis ua hauj lwm. Txhua qhov kev sib txuas tseem ceeb: bushings, kais dej, cov ntsiab lus hauv av. Scotech cov pab pawg tu xyuas nruj, rov xyuas dua, thiab nruj dua yog tias xav tau. Nws yog tedious ua hauj lwm, tab sis qhov ntawd yog dab tsi ua rau transformers ciaj sia rau xyoo.
(5) Ntxuav
Plua plav, noog poob, txawm tawm - tej yam me me uas thaiv cov cua ntws thiab cua kub. Thaum lub sij hawm, lub radiator ua tsis taus pa. Yog li, kev ntxuav tsis yog tshuaj pleev ib ce; nws yog ib feem ntawm lub tshuab cua txias. Ib tug huv transformer khiav txias, kav ntev. Yooj yim, tab sis

transformer with surge arrester

 

Cim npe nrov: Tib Ncej Mounted Transformer, chaw tsim khoom, chaw muag khoom, nqe, nqi