15 kVA Ncej Mounted Transformer-24.94/0.12*0.24 kV|Canada 2024
Peev xwm: 15kVA
Qhov hluav taws xob: 24.94 / 0.24kV
Feature: nrog OCTC

Qhov chaw ua haujlwm siab tshaj plaws ua tau raws li kev ua tau zoo ntawm kev txhim khu kev qha -ib zaug -theem ncej- mounted transformers.
01 General
1.1 Project Background
Lub 15 KVA ib theem ncej mounted transformer tau xa mus rau Canada nyob rau hauv 2024. Lub zog ntawm tus ncej mounted transformer yog 15 KVA nrog ONAN txias, thawj voltage yog 24.94 KV, theem nrab voltage yog 0.12 / 0.24 KV. Tsim raws li tus qauv CSA C2.2-06.
Hauv cov teb chaws tsim kho sab hnub poob thiab cov teb chaws Esxias sab hnub tuaj, North thiab South America, ntau tus -theem transformers tau siv los ua cov khoom xa tawm. Hauv kev faib hluav taws xob faib hluav taws xob, ib qho -theem transformer raws li kev faib hluav taws xob muaj qhov zoo, nws tuaj yeem txo qhov ntev ntawm qhov tsawg-voltage tis kab, txo cov kab poob, txhim kho cov khoom siv hluav taws xob zoo. Kev ua haujlwm siab thiab txuag hluav taws xob txuag coil core qauv tsim tau txais yuav, qhov hloov pauv yog tus cwj pwm los ntawm kev siv cov kem mounted ncua kev kawm ntawv, me me, me me peev txheej, txo qis -voltage fais fab mov vojvoog, tuaj yeem txo cov kab poob ntau dua 60%. Lub transformer txais tag nrho cov qauv kaw, muaj zog tshaj lub peev xwm, muaj kev ntseeg siab hauv kev ua haujlwm tas mus li thiab kev saib xyuas yooj yim. Nws yog qhov tsim nyog rau cov phiaj xwm hluav taws xob nyob deb nroog, thaj chaw thaj tsam roob, cov zos tawg, kev ua liaj ua teb, teeb pom kev zoo thiab kev siv hluav taws xob, thiab tseem tuaj yeem siv rau lub zog-txuag kev hloov pauv ntawm cov ncej faib kab hauv kev tsheb ciav hlau thiab hauv nroog fais fab.
Peb xyuas kom meej tias txhua qhov ntawm peb cov khoom xa tuaj tau dhau los ua qhov kev lees paub tag nrho. Peb muab ib qho -cov kev pab cuam pob los ntawm kev sab laj, hais, tsim khoom, teeb tsa, commissioning, kev cob qhia rau cov kev pab cuam tom qab muag, peb cov khoom tam sim no ua haujlwm hauv ntau tshaj 50 lub nroog hauv ntiaj teb. Peb lub hom phiaj los ua koj tus neeg muag khoom ntseeg siab tshaj plaws nrog rau koj tus khub zoo tshaj plaws hauv kev lag luam!
1.2 Technical Specification
15 KVA ib theem ncej mounted transformer specification thiab cov ntaub ntawv ntawv
|
Xa rau
Canada
|
|
Xyoo
2024
|
|
Hom
Ncej Mounted Transformer
|
|
Txuj
CSA C2.2-06
|
|
Rated zog
15 KVA
|
|
Ntau zaus
60 tzs
|
|
Theem
1
|
|
Polarity
Ntxiv
|
|
Hom cua txias
ONAN
|
|
Ua kua insulating
Mineral Roj
|
|
Thawj Voltage
24.94 kV
|
|
Secondary Voltage
0.12 / 0.24 KV
|
|
Cov khoom siv winding
Aluminium
|
|
Impedance
1.5%
|
|
Coj mus rhaub Changer
OLTC
|
|
Tapping Range
±2*2.5%
|
|
Khoom siv
Standard Configuration
|
|
Lus hais
N/A
|
1.3 Cov duab kos
15 KVA ncej mounted transformer daim duab kos duab thiab loj.
|
|
|
02 Kev tsim khoom
2.1 Core
Cov tub ntxhais hlau txais yuav cov txheej txheem ca qhib dabtsi yog khoov coil txheej txheem, uas muaj kev ua haujlwm zoo tshaj plaws ntawm electromagnetic, me me excitation tam sim no, tsis muaj -load poob, tsis tshua muaj suab nrov, me me, lub teeb yuag, kev tiv thaiv ib puag ncig thiab txuag hluav taws xob, cov tub ntxhais ua tau zoo, kev ntseeg siab zoo, qhov loj me thiab lwm yam zoo, tuaj yeem ua tau raws li cov neeg siv khoom txhua qhov loj me.

2.2 Cua txias

Cov ntawv ci winding transformer yog ib hom tshiab ntawm qhuav transformer piv nrog cov tsoos transformer, thiab nws qis -voltage winding tsis raug mob los ntawm lem ntawm cov hlau tooj liab, tab sis yog qhwv los ntawm ib tug dav ntawm aluminium ntawv ci ntawv nyob ze rau qhov siab ntawm lub sab sauv thiab sab yoke. Cov ntawv ci winding transformer muaj ntau yam zoo, xws li lub teeb yuag, cov khoom siv tsawg, muaj zog luv luv -circuit resistance thiab siab ntau lawm efficiency.
2.3 Tank
Peb lub tuam txhab siv cov- zoo stainless hlau ua raw khoom rau zus tau tej cov roj tso tsheb hlau luam, thiab siv hydraulic machinery los yog lwm yam khoom siv los khoov, txiav thiab nias lub phaj steel rau hauv lub siab xav tau ntawm cov roj tank. Butt lub Cheebtsam thiab ua cov roj shielded vuam los yog lwm yam vuam txheej txheem los xyuas kom meej lub nruj thiab structural zog ntawm lub tank. Tag nrho cov ntsaws ruaj ruaj yog kaw rau ntawm qhov kawg txwv; Cov khoom hlau sab hauv thiab sab nraum lub thawv yog sib npaug kom tshem tawm cov plaub hau, thiab cov hlua khi thiab cov hlua khi raug kuaj peb zaug (fluorescence, zoo siab, tsis zoo siab toughness test); Cov xim yog ua raws li tus qauv tiv thaiv - xeb yuav tsum.

2.4 Kev sib dhos zaum kawg

Kev sib dhos txoj kev ntawm ib zaug -theem ncej mounted transformer
1. Txhim kho cov tub ntxhais hlau ntawm lub rooj zaum hlau. Nws yuav tsum tau muab sau tseg tias yuav tsum tsis muaj qhov ntse ntse ntawm lub rooj zaum kom tsis txhob txiav cov khoom siv rwb thaiv tsev.
2. Txhim kho cov khoom siv rwb thaiv tsev ntawm cov tub ntxhais hlau. Lub luag haujlwm ntawm cov khoom siv rwb thaiv tsev yog cais cov input coil los ntawm cov zis coil thiab tiv thaiv kev luv luv ntawm cov windings.
3. qhwv lub kauj nyob ib ncig ntawm cov khoom siv rwb thaiv tsev. Them mloog mus rau lub winding ib ntus, uas yuav tsum tau nqa tawm raws li tus tsim yuav tsum tau. Nyob rau tib lub sijhawm, nws tseem yuav tsum tau saib xyuas seb qhov winding ntawm lub kauj yog qhov tseeb, txwv tsis pub nws yuav cuam tshuam rau kev ua haujlwm ntawm lub tshuab hloov pauv.
4. Sib sau ua ke lub davhlau ya nyob twg. Terminal board tuaj yeem yog xaim xaim lossis davhlau ya nyob twg. Xaiv lub davhlau ya nyob twg raws li qhov xwm txheej tiag tiag. Tsis tas li ntawd, nws yuav tsum tau them sai sai rau qhov loj ntawm cov xaim xaim lossis lub davhlau ya nyob twg, kom phim lub kauj.
5. Txuas lub coil mus rau lub davhlau ya nyob twg board. Thaum txuas cov coils thiab cov boards, siv cov ntaub ntawv rwb thaiv tsev kom zoo kom ntseeg tau tias kev sib txuas ruaj khov thiab ruaj khov.
6. Sib dhos lub plhaub. Lub luag haujlwm tseem ceeb ntawm lub tsev yog los tiv thaiv lub kauj thiab kev nyab xeeb ntawm kev tawm tswv yim thiab tawm. Thaum sib sau ua ke, nws yog ib qho tsim nyog yuav tsum tau them sai sai rau qhov loj thiab cov khoom ntawm lub plhaub, thiab tseem yuav tsum xav txog qhov yuav tsum tau ua kom sov dissipation thiab kev tiv thaiv.
03 Kev Xeem
Ib leeg-phase kem transformers feem ntau yuav tsum tau ua raws li cov kev xeem hauv qab no:
Kev ntsuas rwb thaiv tsev: suav nrog kev ntsuas kev tiv thaiv hluav taws xob, kev ntsuas hluav taws xob tsis zoo thiab kev ntsuas ib nrab kom ntseeg tau qhov kev ntseeg siab ntawm cov rwb thaiv tsev.
Kev ntsuas hluav taws xob: Siv qee qhov hluav taws xob nruab nrab ntawm cov hluav taws xob hluav taws xob siab thiab cov hluav taws xob tsawg los kuaj seb qhov rwb thaiv tsev ntawm lub tshuab hluav taws xob puas tuaj yeem tiv taus qhov hluav taws xob siab.
Kev ntsuas kev tiv thaiv: Ntsuas qhov kev tiv thaiv ntawm lub tshuab winding thiab grounding kom ntseeg tau tias nws ua tau raws li cov qauv tsim.
Tsis muaj-load test: Ntsuas qhov hluav taws xob kev ua tau zoo ntawm transformer nyob rau hauv tsis muaj - load tej yam kev mob, nrog rau tsis muaj -load poob thiab tsis muaj -load tam sim no.
Load test: kuaj qhov kev ua tau zoo ntawm lub transformer nyob rau hauv rated load kom ntseeg tau tias nws tuaj yeem ua haujlwm ruaj khov thiab ntseeg tau.
Kev ntsuas kub nce: nyob rau hauv cov kev ntsuas load, sim ntsuas qhov kub ntawm qhov hloov pauv kom ntseeg tau tias nws yuav tsis raug puas los ntawm overheating.
Overload test: Ntsuas lub peev xwm dhau ntawm lub tshuab hluav taws xob kom ntseeg tau tias nws yuav tsis raug puas tsuaj thaum lub sijhawm thauj khoom ntau dhau.
Kev sim luv luv Circuit Court: Ntsuas lub peev xwm luv luv ntawm lub tshuab hluav taws xob kom paub meej tias nws yuav tsis raug puas tsuaj thaum lub caij luv luv.


04 Packing thiab Shipping


05 Site thiab Summary
Ua tsaug rau koj qhov kev txaus siab rau peb ib zaug -theem ncej-mounted transformer! Nrog nws qhov zoo ntawm kev ua haujlwm siab, kev ntseeg siab, thiab kev txuag hluav taws xob, cov khoom siv no tau siv dav hauv cov tshuab hluav taws xob, ua kom tau raws li qhov xav tau ntawm lub zog thoob plaws ntau yam xwm txheej. Peb tau cog lus tias yuav muab cov khoom zoo thiab cov kev pabcuam siab - kom ntseeg tau tias muaj kev nyab xeeb thiab ruaj khov ntawm koj lub tshuab fais fab. Peb tos ntsoov yuav ua haujlwm nrog koj txhawm rau txhim kho kev lag luam hluav taws xob ua ke!

Cim npe nrov: 15 kva ncej mounted transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
50 kVA Ncej Mounted Transformers-34.5/0.48 kV|Canada...
75 kVA Transformer Ntawm Cov Hluav Taws Xob-12.4 * 2...
167 kVA Fais fab Pole Transformer-13.8/0.347 kV|Cana...
50 kVA transformer utility ncej-13.8/0.24*0.12 kV|Gu...
50 kVA Transformer Ntawm Fais Fab Ncej-7.97/0.12/0.2...
167 kVA Ncej Mounted Distribution Transformer-24.94/...
Xa kev nug