25 KVA Ib Phase Ncej Transformer-25/0.347 KV|Canada 2024

25 KVA Ib Phase Ncej Transformer-25/0.347 KV|Canada 2024

Lub Tebchaws: Canada 2024
Muaj peev xwm: 25 kVA
Qhov hluav taws xob: 25/0.347kV
Feature: High-voltage ob chav bushings
Xa kev nug

 

25 kVA single phase pole transformer

25 kVA ib theem ncej transformer - txhim khu kev qha, muaj txiaj ntsig, thiab xob laim - tiv thaiv hluav taws xob sab nraum zoov

 

 

01 General

1.1 Project Description

Peb 25 kVA ib qho -theem ncej- mounted transformers tau muab rau Canadian tus neeg siv khoom los ntawm Scotech hauv 2024 raws li ib feem ntawm cuaj-unit order. Ua tiav raws li CSA C2.2-06 tus qauv. Rated rau thawj qhov hluav taws xob ntawm 25 kV thiab qhov hluav taws xob thib ob ntawm 0.347 kV, muab tag nrho lub peev xwm ntawm 25 kVA nyob rau hauv qhov nruam load. Nws siv ONAN natural oil cooling, ntxhia roj raws li qhov nruab nrab insulating, additive polarity, thiab vector pawg Ii6.

Qhov no transformer nta aluminium windings, txo qhov hnyav thiab nqi, ua rau kev teeb tsa thiab kev thauj mus los yooj yim dua. Nws 2.8% impedance pab sib npaug luv luv - Circuit Court tam sim no thiab kev tswj hluav taws xob hauv cov tshuab xa khoom, ua kom yooj yim rau kev tiv thaiv kev teeb tsa. Nws tau nruab nrog NLTC (Tsis yog-Load Tap Changer) nrog 2.5% kauj ruam, tso cai rau cov zis hluav taws xob hloov pauv thaum lub sijhawm ua haujlwm kom ruaj khov. Nws kuj muaj 33 kV polymer xob laim ntes thiab dual siab -voltage bushings kom zoo xob laim thiab tiv thaiv overvoltage.

Qhov kev teeb tsa hluav taws xob no muaj nyob hauv North American thiab Canadian tis systems. Cov qauv no ua haujlwm rau cov zej zog nyob deb nroog, thaj chaw nyob, thiab cov lag luam me uas ruaj khov ib leeg -theem fais fab yog qhov tseem ceeb. 25 kV thawj qhov kev sib txuas ua rau nws muaj kev xaiv zoo rau feeder lossis voj tshuab nyob rau hauv ib puag ncig sab nraum zoov uas muaj kev ua haujlwm siab dua. Txawm hais tias siv nyob rau hauv cov kab tseem ceeb nyob deb nroog lossis qhov kawg ntawm lub nplhaib network, qhov hloov pauv no muab kev ua haujlwm ruaj khov thiab txhim khu kev qha.

 

1.2 Technical Specification

25 kVA ib theem ncej transformer specification thiab cov ntaub ntawv ntawv

Xa rau
Canada
Xyoo
2024
Hom
Ncej Mounted Transformer
Txuj
CSA C2.2-06
Rated zog
25kVA ua
Ntau zaus
60 tzs
Polarity
Ntxiv
Theem
1
Hom cua txias
ONAN
Ua kua insulating
Mineral Roj
Thawj Voltage
25 kv
Secondary Voltage
0, 347 kv
Vector Group
Ib 6
Cov khoom siv winding
Aluminium
Impedance
2.8%
Kev ua tau zoo
98.63%
Coj mus rhaub Changer
NLTC
Tapping Range
±2*2.5%
Tsis Load Loss
83kv ua
Ntawm Load Loss
4 04kv
Khoom siv
Tub ceev xwm

 

1.3 Cov duab kos

25 kVA ib theem ncej transformer kos duab thiab nameplate

25 kVA single phase pole transformer drawing 25 kVA single phase pole transformer nameplate

 

 

02 Kev tsim khoom

2.1 Core

Cov tub ntxhais transformer yog ib qho tseem ceeb ntawm kev tsim cov hlau nplaum hluav taws xob thiab ua kom lub zog hloov pauv ntawm thawj thiab theem nrab windings. Nws siv siab - zoo lis- taw qhia silicon steel laminations stacked thiab insulated kom txo qis eddy tam sim no poob. Cov tseem ceeb nta ib tug tub ntxhais- hom tsim nrog cov kab plaub hau, optimized rau siab tshaj plaws sib nqus flux thiab high efficiency nyob rau hauv kev lag luam tas mus li.

 

2.2 Cua txias

Aluminium windings yog tsim nyob rau hauv kev tswj nruj ntawm kev taw qhia, polarity, thiab nro. Lub LV kauj yog qhov txhab ua ntej, ua raws li HV kauj, nrog txheej rwb thaiv tsev compactly thov thiab tsis muaj wrinkles. Hloov qhov tseeb yog nyob rau hauv ± 0.3%. Radial roj ducts Ntau dua lossis sib npaug li 3 hli thiab ruaj khov ua kom txias txias thiab lub zog txhua yam, tiv thaiv deformation thaum lub sijhawm ua haujlwm.

25 kVA single phase pole transformer winding

 

2.3 Tank

25 kVA single phase pole transformer oil tank

Lub tank roj tau tsim kom ua tau raws li cov qauv nruj nreem kaw. Nws muaj cov flanges muaj zog thiab kev txhawb nqa, tuaj yeem nqa qhov hnyav thiab kev co, thiab nta ruaj ntseg mounting qhov. Cov khoom siv tank tiv taus qhov kub thiab txias. Gaskets kom tsis txhob muaj roj. Qhov saum npoo yog kho tiv thaiv corrosion. Sab saum toj muab qhov chaw txaus rau kev tshem tawm yooj yim thiab hloov cov neeg ntes yam tsis muaj kev cuam tshuam kev sib khi.

 

2.4 Kev sib dhos zaum kawg

Core thiab Winding Assembly
Nruab qhov siab -voltage thiab low-voltage windings mus rau hauv lub hauv paus, kom ntseeg tau tias rwb thaiv tsev thiab concentricity.
Lub cev Installation
Muab cov tub ntxhais thiab winding sib dhos rau hauv lub tank roj.
Txhim kho cov hlau lead thiab insulating bushings, xyuas kom zoo sealing.
Filling Transformer Roj
Txhaj cov roj hloov pauv hloov, kom nws huv si thiab tsis muaj impurities.
Nruab Cov Khoom Siv Sab Nraud
Txuas cov kev nyab xeeb li qub, roj qib ntsuas, thiab kev sib txuas ntawm lub davhlau ya nyob twg.

25 kVA single phase pole transformer active part

 

 

03 Kev Xeem

Test Standard thiab Routine Test

CSA C2.2-06(R2022) Ib leeg-theem thiab peb-theem kua-filled tis transformers
CSA C802.1-13(R2022) Yam tsawg kawg nkaus efficiency qhov tseem ceeb rau cov kua-filled tis transformers
 

1. Kev ntsuas ntsuas
2. Kev ntsuas qhov sib piv
3. Polarity Test
4. Tsis muaj Load Losses thiab Tsis Muaj Load Tam Sim No
5. Load Losses thiab impedance Voltage
6. Applied Voltage Test
7. Induced Voltage Withstand Test
8. Kev ntsuas kev tiv thaiv hluav taws xob
9. Kev ntsuas qhov dej nrog lub siab rau cov kua dej hloov pauv
10. Roj Test
 

Cov qhabnias xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Txais

Tus nqi

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

/

/

/

Hla

2

Kev ntsuas ntsuas

/

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Ii6

0.11~0.12

Hla

3

Kev ntsuam xyuas polarity

/

Ntxiv

Ntxiv

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

%

I0 :: muab ntsuas tus nqi (100%)

0.38

Hla

kW

P0: muab ntsuas tus nqi (100%)

0.0681

%

I0 :: muab ntsuas tus nqi (105%)

0.40

kW

P0: muab ntsuas tus nqi (105%)

0.0766

/

qhov kam rau tsis muaj load poob yog +10%

/

5

Load poob, impedance voltage, tag nrho poob thiab efficiency

/

t:85 ua

Qhov kam rau ua impedance yog ± 7.5%

lub kam rau tag nrho load poob yog +6%

/

Hla

%

Z%: ntsuas tus nqi

2.60

kW

Pk: ntsuas tus nqi

0.366

kW

Pt: ntsuas tus nqi

0.4341

%

Kev ua tau zoo tsis tsawg dua 98.63%

98.81

6

Applied Voltage Test

/

LV: 10kV 60s

HV: 40kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

/

Kev siv hluav taws xob (KV): 2Ur

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

Duration(s): 40

Zaus (HZ): 180

8

Rwb thaiv tsev Resistance Measurement

HV-LV·to·Ground

306

Hla

LV-HV to Av

422

HV&LV to Av

129

9

Kev Xeem Leakage

/

Kev siv siab: 20kPA

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

Duration: 12h

10

Roj Xeem

kV ua

Dielectric zog

61.0

 

mg/kg

Cov ntsiab lus noo noo

13.6

%

Dissipation Factor

0.158

mg/kg

Furan Analysis

Tsawg dua los yog sib npaug li 0.1

/

Gas Chromatography Analysis

/

image013
image015

 

 

04 Packing thiab Shipping

25 kVA single phase pole transformer packing
 
25 kVA single phase pole transformer shipping
 
 

05 Site thiab Summary

25 kVA single phase pole transformer

Kev ntseeg tau thiab ua tau zoo, qhov no 25 kVA transformer ua tau raws li CSA C2.2-06 tus qauv nrog 25 kV / 0.347 kV ntsuas, aluminium windings, thiab ONAN cua txias. Nruab nrog NLTC kais hloov pauv thiab 33 kV xob laim ntes, nws ua kom ruaj khov thiab tiv thaiv. Zoo tagnrho rau cov chaw nyob deb nroog, thaj chaw, thiab kev lag luam me, nws muab kev nyab xeeb, ruaj khov, thiab yooj yim -rau-nruab sab nraum zoov.

 

Cim npe nrov: ib theem ncej transformer, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug