167 KVA Ib Theem Ncej Mounted Transformer-2.4/0.347 KV|Canada 2025
Peev xwm: 167 kVA
Qhov hluav taws xob: 2.4 / 0.347 kV
Feature: nrog IFD thiab tiv thaiv - taug qab

Ua rau Cov Ntsiab Lus, Tso Siab rau Kev Ua Tau Zoo: Tib Theem Ncej Mounted Transformer.
01 General
1.1 Project Description
167 kVA ib theem ncej mounted transformer tau xa mus rau Canada nyob rau hauv 2025. Lub zog ntsuas ntawm lub transformer yog 167 kVA nrog ONAN txias. Qhov siab voltage yog 2.4 kV, qhov tsawg voltage yog 0.347 kV, lawv tsim ib pawg vector ntawm Ii6.
Niaj hnub no ib leeg -theem ncej- mounted transformer, integrating Internal Fault Detector (IFD) thiab Anti- Tracking rwb thaiv tsev, yog engineered rau superior kev ntseeg siab nyob rau hauv cov ntaub ntawv tseem ceeb xws li nyob rau hauv lub zog faib, hluav taws xob nyob deb nroog, thiab industrial feeder kab. Lub IFD ua haujlwm saib xyuas kev ua txhaum sab hauv kom muaj kev saib xyuas zoo thiab tiv thaiv kev ua tsis tiav, thaum Anti-Tag nrho cov kab ke tiv thaiv kev taug qab los ntawm ntug hiav txwv ntsev pos huab, muaj kuab paug, lossis ib puag ncig ntub. Qhov kev sib koom ua ke ntawm kev kuaj mob thiab kav ntev ua kom muaj kev nyab xeeb zoo dua thiab txo qis kev cuam tshuam rau cov neeg siv khoom siv hluav taws xob.
1.2 Technical Specification
167 kVA ncej mounted transformer specifications hom thiab cov ntaub ntawv ntawv
|
Xa rau
Canada
|
|
Xyoo
2025
|
|
Hom
Ncej mounted transformer
|
|
Txuj
CSA C2.2-06
|
|
Rated zog
167 kVA ua
|
|
Ntau zaus
60 tzs
|
|
Theem
1
|
|
Polarity
Ntxiv
|
|
Hom cua txias
ONAN
|
|
Thawj Voltage
2,4kv wb
|
|
Secondary Voltage
0, 347 kv
|
|
Cov khoom siv winding
aluminium
|
|
Vector Group
Ib 6
|
|
Impedance
2.3%(±10%)
|
|
Coj mus rhaub Changer
N/A
|
|
Tsis Load Loss
0, 096 kWm
|
|
Ntawm Load Loss
1.85 kWm
|
1.3 Cov duab kos
167 kVA ncej mounted transformer daim duab kos duab thiab loj.
![]() |
![]() |
02 Kev tsim khoom
2.1 Core

Nws cov tub ntxhais yog tsim los ntawm kev tsim lub qhov txhab txuas ntxiv los ntawm qib siab - silicon steel. Cov qauv tshiab no tsim txoj hauv kev zoo sib nqus nrog qhov sib txawv me me, ua rau lub zog ua haujlwm zoo dua qub thiab ua haujlwm ntsiag to, txhim khu kev qha ntau dua.
2.2 Cua txias
Nws ntiav cov ntawv txhuas txhuas-mob tsim rau qhov qis-voltage sab kom muab lub zog luv luv-circuit zog thiab txheej txheej aluminium xaim-mob tsim rau qhov siab-voltage sab rau qhov zoo tshaj plaws voltage tis. Qhov no hybrid winding mus kom ze, siv txhuas, ua tiav qhov zoo tshaj qhov sib npaug ntawm kev ntseeg tau, tus nqi -efficiency, thiab thermal ua haujlwm.

2.3 Tank

Lub tank yog tsim los ntawm qib siab - qib stainless hlau, muab tshwj xeeb corrosion kuj thiab tshem tawm qhov xav tau rau tha xim. Nws cov qauv tsim los ntawm hermetically kaw, ua ke nrog cov corrugated fins, ua kom muaj kev tiv thaiv zoo tiv thaiv ib puag ncig hnyav thiab ua haujlwm tau zoo, txij nkawm- tsis muaj cua sov dissipation thoob plaws lub neej ua haujlwm ntev.
2.4 Kev sib dhos zaum kawg
Kev sib dhos zaum kawg sawv cev rau kev sib koom ua ke ntawm txhua yam khoom loj. Cov tub ntxhais -winding sib dhos yog kaw nyob rau hauv lub corrosion-resistant stainless steel tank, uas yog nqus tsev vacuum- puv nrog dielectric kua los lav superior dielectric zog thiab txias. Kev sib txuas ntawm siab -voltage bushings, accessories, thiab kev sim zaum kawg nruj ua kom tiav kev ua tau zoo, ua rau muaj kev ruaj khov thiab kev txij nkawm-pab transformer optimized rau overhead faib.

03 Kev Xeem
Tus tib-theem ncej-mounted transformer (model: 167kVA-2.4/0.347kV) los ntawm SCOTECH ua raws li CSA C2.2-06(R2022) thiab CSA C802.1-20. Cov kev ntsuam xyuas niaj hnub suav nrog kev ntsuas kev ntsuas cua (HV: 0.09067Ω, LV: 1.919mΩ ntawm 32℃thiab 60% txheeb ze av noo), piv piv (dev: 0.04% Tsawg dua lossis sib npaug rau 0.5%, pawg vector: Ii6), polarity test (Additive, ntsib cov kev xav tau ntawm 9%) kam rau ua, tam sim no: 0.36%), load test (poob ntawm 85 degree: 1165W, tag nrho poob: 1261W, short-circuit impedance: 2.17% nyob rau hauv ± 10% kam rau ua, efficiency: 99.57% Ntau tshaj los yog sib npaug zos rau 98.63%), thov voltage 10 kV voltage (LV) withstand test (0.694kV, 150Hz rau 48s, tsis muaj hluav taws xob vau), rwb thaiv tsev ntsuas ntsuas (LV-HV rau hauv av: 29.1GΩ), 20kPa siab xau kuaj (24h, tsis muaj dej xau lossis puas), thiab ntsuas roj (dielectric zog: 58.4kV, noo noo cov ntsiab lus: 9.5mg / kg, thiab lwm yam.
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Txais Tus nqi |
Ntsuas Tus Nqi |
Xaus |
|
1 |
Kev ntsuas ntsuas |
/ |
/ |
/ |
Hla |
|
2 |
Kev ntsuas ntsuas |
/ |
Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5% Cov cim kev sib txuas: Ii6 |
0.04 |
Hla |
|
3 |
Kev ntsuam xyuas polarity |
/ |
Ntxiv |
Ntxiv |
Hla |
|
4 |
Tsis muaj -load poob thiab excitation tam sim no |
% |
I0 :: muab ntsuas tus nqi |
0.36 |
Hla |
|
kW |
P0: muab ntsuas tus nqi |
0.095 |
|||
|
/ |
qhov kam rau tsis muaj load poob yog +15% |
/ |
|||
|
5 |
Load poob, impedance voltage, tag nrho poob thiab efficiency |
/ |
t:85 ua Qhov kam rau ua impedance yog ± 10% lub kam rau tag nrho load poob yog +8% |
/ |
Hla |
|
% |
Z%: ntsuas tus nqi |
2.17 |
|||
|
kW |
Pk: ntsuas tus nqi |
1.165 |
|||
|
kW |
Pt: ntsuas tus nqi |
1.261 |
|||
|
% |
Kev ua tau zoo tsis tsawg dua 98.63% |
99.57 |
|||
|
6 |
Applied Voltage Test |
/ |
LV: 10kV 60s |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
7 |
Induced Voltage Withstand Test |
/ |
Kev siv hluav taws xob (KV): 0.694 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
Duration(s):48 |
|||||
|
Zaus (HZ): 150 |
|||||
|
8 |
Rwb thaiv tsev Resistance Measurement |
GΩ |
LV-HV to Av |
29.1 |
Hla |
|
9 |
Kev Xeem Leakage |
/ |
Kev siv siab: 20kPA |
Tsis muaj leakage thiab tsis muaj Kev puas tsuaj |
Hla |
|
Duration: 12h |
|||||
|
10 |
Roj Xeem |
kV ua |
Dielectric zog |
58.4 |
Hla |
|
mg/kg |
Cov ntsiab lus noo noo |
9.5 |
|||
|
% |
Dissipation Factor |
0.00194 |
|||
|
mg/kg |
Furan Analysis |
0.03 |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Packing thiab Shipping
4.1 Ntim

Rau kev ntim khoom, ib zaug - theem ncej - mounted transformer yog ruaj ntseg nyob rau hauv ib lub thawv ntoo plywood ruaj khov. Ua ntej muab tso rau hauv lub thawv, lub transformer yog npog nrog ib txheej ntawm yas zaj duab xis los tiv thaiv cov av noo thiab cov kab mob. Lub thawv ntoo yog nruab nrog cov hlau ntug reinforcements kom zoo dua durability, thiab tseem ceeb tuav cov lus qhia thiab ceeb toom cov paib kom meej meej luam tawm ntawm nws nto. Tsis tas li ntawd, nws tau teem rau ntawm lub pallet, ua kom yooj yim rau kev khiav lag luam zoo thiab ua kom lub tshuab hloov pauv nyob rau hauv qhov zoo thaum lub sij hawm xa khoom thiab khaws cia.
4.2 Shipping
Raws li CIF Montreal cov ntsiab lus, tib - theem ncej - mounted transformers yog thauj los ntawm hiav txwv freight. Tus neeg muag khoom npaj thiab them tus nqi ntawm kev thauj mus los hauv hiav txwv mus rau Chaw nres nkoj ntawm Montreal, muab kev tuav pov hwm kev thauj mus los hauv hiav txwv los tiv thaiv kev pheej hmoo ntawm kev thauj mus los, thiab xyuas kom cov transformers raug tswj kom raug thiab thauj mus rau hauv lub nkoj kom muaj kev nyab xeeb ntawm kev xa mus rau qhov chaw nres nkoj.

05 Site thiab Summary
Los ntawm nws txoj kev tsim kho steel hlau tsis muaj zog mus rau nws lub qhov txhab ua haujlwm zoo heev thiab cov cua ntsawj ntshab, txhua qhov ntawm qhov no ib zaug -theem ncej- mounted transformer yog tsim los rau ib lub hom phiaj: unmatched kev ntseeg nyob rau hauv lub teb. Nws yog qhov kev xaiv ntse, ruaj khov rau kev siv hluav taws xob nrhiav kev txhim kho kab sib chaws, txo cov nqi ua haujlwm, thiab muab kev pabcuam tshwj xeeb rau lawv cov neeg siv khoom. Npaj kom muaj zog rau yav tom ntej nrog kev ntseeg siab? Tiv tauj peb hnub no kom pom tias qhov transformer no tuaj yeem ua ke rau hauv koj lub network li cas.

Cim npe nrov: ib theem ncej mounted transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
37.5 kVA Transformers Ntawm Xov Tooj Ncej-34.5/0.12*...
167 kVA Fais fab Pole Transformer-13.8/0.347 kV|Cana...
75 kVA utility transformer-24.94/0.24*0.12 kV|Canada...
50 kVA Transformer Fais Fab Kab-13.8/0.12*0.24 kV|Gu...
75 kVA Ncej Mounted Transformer-7.97/0.12/0.24 kV|Ca...
25 kVA Transformer Ncej Mounted-14.4/0.12 kV|Canada ...
Xa kev nug