50 kVA Transformer Ntawm Fais Fab Ncej-7.97/0.12/0.24 kV|Canada 2024

50 kVA Transformer Ntawm Fais Fab Ncej-7.97/0.12/0.24 kV|Canada 2024

Lub Tebchaws: Canada 2024
Peev xwm: 50kVA
Lub hwj chim: 7.97 / 13.8Y-0.12 (0.24) kV
Feature: Amorphous core
Xa kev nug

 

 

50 kva transformer on power pole-front-view

Ib qho kev txhim khu kev qha transformer ntawm lub hwj chim ncej xa lub zog zoo thiab ruaj khov rau cov zej zog niaj hnub

 

01 General

1.1 Project Description

Qhov no yog 50 kVAib leeg-theem ncej-mounted faib transformernruj me ntsis ua raws li IEEE C57.12.20 tus qauv. Nws yog dav siv nyob rau hauv North American tis networks, feem ntau ntsia rau hauv 13.8 kV grounded -wye systems, qhov twg lub transformer yog txuas nrog theem- rau - nruab nrab ntawm 7.97 kV thiab muab ib tug txhim khu kev qha 120/240 V phua- theem tso zis rau thaj chaw thiab lub teeb coj mus muag daim ntaub ntawv.

Lub 50 kVA transformer ntawm lub hwj chim ncej txais ib qho amorphous hlau core, uas zoo heev txo tsis muaj -load poob rau tsuas yog 0.043 kW. Nws muab lub zog zoo heev -txuag kev ua tau zoo txawm tias lub teeb load. Nrog rau qhov ntsuas impedance ntawm 2.1%, lub transformer muaj qhov zoo voltage tswj thiab, ua ke nrog nws ± 2 × 2.5% tsis muaj-load kais hloov pauv, ua kom ruaj khov theem nrab voltage hauv ± 5% ntawm nominal.

Nws cov qauv tsim muaj xws li ONAN ntuj txias, aluminium windings, thiab ntxiv polarity, nrog vector pawg Ii6. Cov yam ntxwv no ua rau lub transformer compact. Nws ua tau zoo thiab txhim khu kev qha rau ncej-mounted siv. Lub unit muaj ib tug surge arrester tus thawj coj. Qhov no ua rau nws yooj yim ntxiv cov khoom siv tiv thaiv.

Lub transformer muaj tsawg losses. Nws ua haujlwm nrog kev ua haujlwm siab. Nws kuj yoog tau zoo rau cov kev xav tau sib txawv. Qhov no ua rau nws yog qhov kev xaiv zoo rau cov tshuab hluav taws xob niaj hnub.

 

 

 

1.2 Technical Specification

50kVA transformer ntawm lub hwj chim ncej specification thiab cov ntaub ntawv ntawv

Xa rau
Canada
Xyoo
2024
Hom
Ib theem ncej mounted transformer
Txuj
IEEE C57.12.20
Rated zog
50 kVA
Ntau zaus
60 tzs
Polarity
Ntxiv
Vector pawg
Ib 6
Thawj Voltage
7.97/13.8Y kV
Secondary Voltage
120/240 V
Cov khoom siv winding
Aluminium
Impedance
2.1%
Txoj kev txias
ONAN
Coj mus rhaub Changer
NLTC
Tapping Range
±2X2.5%
Tsis Load Loss
0.043 kWm
Ntawm Load Loss
0.5 kW tsi
Khoom siv
Surge arrester tus thawj coj

 

 

1.3 Cov duab kos

50kVA transformer ntawm lub zog ncej kos duab thiab daim ntawv teev npe

50 kva transformer on power pole-technical-drawing 50 kva transformer on power pole-nameplate

 

 

02 Kev tsim khoom

2.1 Core

Cov ncej-mounted transformernta amorphous hlau core, ua los ntawm cov hlau, boron, silicon, nickel, thiab carbon. Piv nrog rau cov pa txias- dov silicon steel, cov tub ntxhais no yog isotropic, nyias nyias (0.03 hli), thiab muaj hluav taws xob tiv taus siab, txo qis kev poob tam sim no. Nws ua tau zoo heev uas tsis muaj-load poob (0.043 kW) thiab load poob (0.5 kW), muab kev ua haujlwm siab, kev tsim khoom yooj yim, thiab eco- ua haujlwm zoo.

50 kva transformer on power pole-amorphous-metal-iron-core

 

2.2 Cua txias

50 kva transformer on power pole-aluminum-winding

Peb ib leeg -theem ncej-mounted transformers feature low-voltage foil coils thiab high-voltage wire coils. Cov neeg siv khoom xaiv aluminium LV coils tau txais txiaj ntsig los ntawm kev txo qhov hnyav thiab tus nqi, thaum tswj kev sib piv kev ntseeg tau thiab lub neej ua haujlwm rau tooj liab. High-voltage wire coils xyuas kom muaj qhov sib npaug ntawm qhov hluav taws xob thiab qhov hluav taws xob.

 

2.3 Tank

Qhov no ib zaug -theem cylindrical roj tank yog tsim los ntawm cov hlau me me, nrog lub hau thiab hauv qab tsim los ntawm cov txheej txheem nyias - daim ntawv. Nruab nrog ob lub HV bushings ntawm lub hau thiab peb lub LV eyebolt bushings ntawm lub sidewall, nws tag nrho cov qauv tsim kom muaj kev ruaj ntseg zoo dua thiab kev ua haujlwm zoo.

50 kva transformer on power pole-oil-cylindrical-fuel-tank

 

2.4 Kev sib dhos zaum kawg

50 kva transformer on power pole-final-assembly

Yuav ua li cas rau nruab lub kauj thiab lub qhov txhab qhov txhab: Ua ntej, nteg thawj C-core ca (qhib lub ntsej muag zoo li "U"). Coj lub kauj thiab lub tes tsho tag nrho nws lub hauv paus qhov rau ntawm ib ceg ntawm cov tub ntxhais, thawb nws mus rau hauv qab. Siv qhov thib ob C-core, kho nws cov kev txiav kom meej nrog thawj tus tub ntxhais txiav. Maj mam kaw nws kom txog thaum ob qhov sib xyaw ua ke. Nruab rau saum thiab hauv qab clamping daim hlau, ntxig rau cov ntsia hlau ntev.

 

 

03 Kev Xeem

Routine Test

1. Kev ntsuas ntsuas

2. Kev ntsuas qhov sib piv

3. Theem -kev sib txheeb xeem

4. Tsis muaj Load Losses thiab Tsis Muaj Load Tam Sim No

5. Load Losses, Impedance Voltage thiab Efficiency

6. Applied Voltage Test

7. Induced Voltage Withstand Test

8. Kev ntsuas dej nrog lub siab rau cov kua Immersed Transformers

9. Kev ntsuas kev tiv thaiv rwb thaiv tsev

10. Roj Dielectric Test

11. Kev Ntsuas Hluav Taws Xob

 

50 kva transformer on power pole-routine-test-leakage-test
50 kva transformer on power pole-routine-test-applied-voltage-test

 

Cov qhabnias xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Kev txais txiaj ntsig

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

/

/

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Ii6

0.02

Hla

3

theem- kev xeem sib txheeb

/

Ntxiv

Ntxiv

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

 

%

kW

t:85 ua

I0 :: muab ntsuas tus nqi

P0: muab ntsuas tus nqi

qhov kam rau tsis muaj load poob yog +10%

1.11(100%)

2.16(105%)

0.045(100%)

0.061(105%)

Hla

5

Load poob impedance voltage thiab efficiency

%

kW

kW

t:85 ua

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

Qhov kam rau ua impedance yog ± 10%

qhov kam rau tag nrho load poob yog +6%

2.21

0.496

0.543

99.37

Hla

6

Applied Voltage Test

kV ua

HV: 34kV 60s

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

kV ua

Kev siv hluav taws xob (KV):

15.94

Duration(s): 40

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

8

Kev Xeem Leakage

kPa ua

Kev siv siab: 20kPA

Duration: 12h

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

9

Rwb thaiv tsev Resistance Measurement

HV & LV rau hauv av:

120.0

/

HV-LV to Av

51.8

LV-HV to Av

62.6

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 45

55.48

Hla

11

xob laim impulse test

kV ua

puv nthwv dej, Ib nrab nthwv dej

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

 

 

04 Packing thiab Shipping

50 kva transformer on power pole-export-packing
50 kva transformer on power pole-delivery

 

 
 

05 Site thiab Summary

Qhov no 50 kVA ib leeg -theem ncej-mounted transformer yog tsim rau Canada xyoo 2024. Nws ua raws IEEE C57.12.20. Nws ua haujlwm ntawm 13.8 kV hauv av-wye systems, muab 120/240 V rau cov tsev thiab cov lag luam me.

Lub transformer muaj ib tug amorphous hlau core. Nws khaws tsis tau -load poob ntawm 0.043 kW thiab load poob ntawm 0.5 kW. Nws txuag lub zog thiab khiav nrog kev ua haujlwm siab. Aluminium windings, ONAN txias, thiab ntxiv polarity ua rau lub tsev compact, nyab xeeb, thiab txhim khu kev qha. Tus thawj surge arrester tso cai hloov kho kev tiv thaiv yooj yim.

Qhov no transformer ntawm lub hwj chim ncej muab kev ua tau zoo, kev ntseeg tau, thiab eco-kev ua tau zoo, ua rau nws muaj kev xaiv zoo rau kev faib khoom niaj hnub.

Scotech ua cov transformers zoo rau cov neeg siv khoom thoob ntiaj teb. Peb cov khoom txuag lub zog, txiav kev poob, thiab muab lub zog ruaj khov. Peb xa cov kev daws teeb meem nyab xeeb thiab pov thawj uas pab cov phiaj xwm hluav taws xob ua haujlwm zoo dua txhua hnub.

Scotech - transformers txhim khu kev qha, muaj zog zog, zoo dua network.

50-kva-pole-mounted-transformer-left-45-degree-view

Cim npe nrov: Transformer On Power Ncej, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug