500 kVA Pad Mount Transformer-24 * 13.8 * 12 / 0.416 * 0.24 kV|Jamaica 2025
Peev xwm: 500kVA
Qhov hluav taws xob: 24GrdY / 13.8 * 13.8D * 12GrdY / 6.9-0.416Y / 0.24 * 0.24 / 0.12kV
Feature: nrog dual voltage hloov

Los ntawm Subdivisions mus rau Lub Nroog Ntse - Pad-Mounted Transformers Ua kom muaj zog ntws.
01 General
1.1 Project Description
500 kVA ncoo mounted transformer tau xa mus rau Jamaica hauv 2025. Lub zog ntsuas ntawm lub transformer yog 500 kVA nrog ONAN txias. Thawj qhov hluav taws xob yog 24/13.8 * 13.8D * 12/6.9 kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov nruab nrab voltage yog 0.416 / 0.24 * 0.24D / 0.12 kV, lawv tsim vector pawg ntawm YNyn0 thiab YNd11.
Peb lub ncoo-mounted transformer yog ib qho compact, tag nrho cov khoom siv hluav taws xob xa hluav taws xob tsim los rau kev ntseeg siab, kev nyab xeeb, thiab kev ua haujlwm zoo hauv nroog thiab chaw lag luam. Engineered rau seamless kev koom ua ke rau hauv daim phiaj niaj hnub, nws muaj qhov tawm ntawm - Circuit Court changer thiab dual voltage hloov rau kev ua haujlwm hloov tau yooj yim, tso cai yooj yim hloov voltage yam tsis muaj kev cuam tshuam.
Txhawm rau txhim kho kev tiv thaiv, chav tsev suav nrog lub luj tshib ntes thiab thauj khoom - rhuav lub luj tshib txuas, ua kom muaj kev nyab xeeb kev sib txuas thiab kev tawm tsam. Kev pub-thru insert ua rau kev tswj xyuas cov kab hluav taws xob zoo, thaum saib xyuas qib siab yog muab los ntawm lub ntsuas kub ntawm cov roj, ntsuas qib ua kua, thiab ntsuas lub tshuab nqus tsev rau qhov tseeb- lub sijhawm kuaj mob.
Kev nyab xeeb yog qhov tseem ceeb nrog Bay -O-Net fuse thiab tam sim no- txwv fuses los tiv thaiv overloads, nrog rau kev hloov pauv rau kev sib cais kom ruaj ntseg thaum tu. Ua kom muaj kev tiv thaiv ib puag ncig hnyav, lub tshuab hloov pauv no muab kev cia siab rau kev ua haujlwm nrog kev saib xyuas tsawg kawg nkaus - zoo tagnrho rau kev siv hluav taws xob, kev lag luam, thiab kev siv hluav taws xob tauj dua tshiab.
1.2 Technical Specification
500 kVA substation transformer specifications hom thiab cov ntaub ntawv ntawv
|
Xa rau
Asmeskas
|
|
Xyoo
2025
|
|
Hom
Substation transformer
|
|
Txuj
IEEE Std C57.12.34-2022
|
|
Rated zog
500 kVA ua
|
|
Ntau zaus
50 HZ
|
|
Theem
3
|
|
Hom cua txias
ONAN
|
|
Thawj Voltage
24/13.8 * 13.8D * 12/6.9 kV
|
|
Secondary Voltage
0.416 / 0.24 * 0.24D / 0.12 kV
|
|
Cov khoom siv winding
Tooj
|
|
Angular tshem tawm
YN0, YNd11
|
|
Impedance
5%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
±2*2.5%
|
|
Tsis Load Loss
Tsawg dua lossis sib npaug li 0.767kW
|
|
Ntawm Load Loss
Tsawg dua lossis sib npaug li 7.2kW
|
1.3 Cov duab kos
500 kVA substation transformer daim duab kos duab thiab loj.
![]() |
![]() |
02 Kev tsim khoom
2.1 Core
Lub transformer nta ib tug siab -efficiency stacked hlau core tsim los ntawm premium grain-oriented silicon steel laminations. Txhua lub lamination yog qhov tseeb laser-txiav thiab txheej nrog cov kauj ruam sib txuas- ceg tawv pob qij txha kom txo tau qhov sib nqus flux to thiab txo tsis muaj - thauj khoom poob. Cov tub ntxhais yog coated nrog ib txheej insulating oxide los tiv thaiv eddy tam sim no, thaum nws compact stacked tsim txhim kho txhua yam kev ruaj ntseg thiab txo qis suab nrov - tseem ceeb rau kev teeb tsa hauv nroog. Rigorously annealed rau kev pom zoo sib nqus permeability, cov tub ntxhais no ua kom lub zog zoo hloov mus rau ob qhov kev teeb tsa hluav taws xob, tswj kev ua haujlwm txawm tias nyob hauv cov khoom hloov pauv.

2.2 Cua txias

Lub LV ntawv ci winding siv tooj liab sawb, kom ntseeg tau tias muaj kev faib tawm tam sim no, zoo dua luv luv -circuit resistance, thiab txhim kho cua sov dissipation. Meanwhile, HV txheej winding txais yuav insulated tooj liab conductors raug mob nyob rau hauv concentric discs, nrog interleaved kraft ntawv rau graded dielectric zog. Cov txheej txheem hloov pauv tau siv los txo qis qhov poob qis, thaum axial thiab radial txias ducts optimize thermal tswj.
2.3 Tank
Lub tank transformer yog ib qho muaj zog, corrosion{0}}resistant steel enclosure featuring 3D corrugated phab ntsa rau roj expansion thiab integrated cooling fins rau passive tshav kub dissipation. Nrog rau tag nrho welded, kuaj radiographically tsim, nws suav nrog ua ntej -drilled cable ports nrog grounding bosses, thiab ua tau - hauv lifting / forklift ntsiab lus. Sab hauv suav nrog baffle daim hlau kom pom cov roj ntws zoo, thaum UV- cov xim epoxy resistant kom ntev -lub sij hawm ua haujlwm nyob rau hauv ib puag ncig sab nraum zoov.

2.4 Kev sib dhos zaum kawg

Kev sib dhos zaum kawg ntawm lub ncoo no -mounted transformer integrates core-coil assembly, tank, thiab accessories rau hauv ib qho kev sib koom ua ke. Cov tub ntxhais qhuav qhuav- chav tsev winding tau ua tib zoo txo qis rau hauv qhov corrosion-cov hlau tsis muaj zog, ua raws li kev teeb tsa ntawm bushings, txias fins, thiab tswj cov khoom. Cov kauj ruam tseem ceeb muaj xws li:
• Roj filling nyob rau hauv lub tshuab nqus tsev vacuum kom tiav rwb thaiv tsev impregnation
• Mechanical alignment ntawm load break keyboards & cable connectors
• Kev sim ua haujlwm ntawm txhua yam khoom siv saib xyuas (gauges, tswb)
03 Kev Xeem
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Kev txais txiaj ntsig |
Ntsuas Tus Nqi |
Xaus |
|
1 |
Kev ntsuas ntsuas |
% |
Maximun kuj unbalance tus nqi |
0.76 |
Hla |
|
2 |
Kev ntsuas ntsuas |
% |
Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug rau ± 0.5% Cov cim kev sib txuas: YNyn0/YNd11 |
0.14% ~ 0.15% |
Hla |
|
3 |
Theem -kev xeem sib txheeb |
/ |
YN0/YNd11 |
YN0/YNd11 |
Hla |
|
4 |
Tsis muaj -load poob thiab excitation tam sim no |
% kW |
I0 :: muab ntsuas tus nqi P0: muab ntsuas tus nqi qhov kam rau tsis muaj load poob yog +0% |
0.59% 0.7535 |
Hla |
|
5 |
Load poob impedance voltage thiab efficiency |
% kW kW |
t:85 ua Qhov kam rau ua impedance yog ± 7.5% lub kam rau tag nrho load poob yog +0% |
/ |
Hla |
|
Z%: ntsuas tus nqi |
5.02% |
||||
|
Pk: ntsuas tus nqi |
6, 649 kWm |
||||
|
Pt: ntsuas tus nqi |
7.40 25 kWm |
||||
|
Kev ua haujlwm tsis tsawg dua 99.05% |
99.10% |
||||
|
6 |
Applied Voltage Test |
kV ua |
HV: 40kV 60s LV: 10kV 60s |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
7 |
Induced Voltage Withstand Test |
kV ua |
Kev siv hluav taws xob (KV): 2Ur |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
Duration(s): 40 |
|||||
|
Zaus (HZ): 150 |
|||||
|
8 |
Kev Xeem Leakage |
kPa ua |
Kev siv siab: 20kPA Duration: 12h |
Tsis muaj leakage thiab tsis muaj Kev puas tsuaj |
Hla |
|
9 |
Rwb thaiv tsev Resistance Measurement |
GΩ |
HV-LV to Av: |
11.0 |
/ |
|
LV-HV to Av: |
9.51 |
||||
|
HV & LV rau hauv av: |
20.1 |
||||
|
10 |
Roj Dielectric Test |
kV ua |
Ntau dua lossis sib npaug li 45 |
58.6 |
Hla |


04 Packing thiab Shipping
4.1 Ntim
Lub ncoo mounted transformer no yog ntim los ntawm thawj zaug nteg ib txheej ntawm tin foil hnab rau ntawm transformer tray thiab npog lub transformer nrog lub tin foil hnab. Thaum muab lub hnab ntim cov ntawv ci, qhov qhib yuav tsum sab laug, los ntawm kev siv lub tshuab nqus tsev nqus cov pa tawm, thiab tom qab ntawd qhov qhib yog kaw nrog lub tshuab sealing. Lub caij no, desiccant muab tso rau hauv lub pob kom tiv thaiv xeb. Tom qab lub tshuab nqus tsev, lub kaum tiv thaiv ua los ntawm cov npuas dej, yas, lossis cov duab los qhia (tshwj xeeb lub kaum tiv thaiv nias los ntawm cov duab los qhia) yog ntxiv nyob ib ncig ntawm lub transformer, uas yog ces qhwv nrog zaj duab xis tiv thaiv. Thaum kawg, nws tau ntim rau hauv ib lub thawv ntoo, uas cov cim forklift thiab qhov chaw ntawm lub ntiajteb txawj nqus yuav tsum tau txau.

4.2 Shipping

Lub ncoo no -mounted transformer yuav raug xa mus raws li FOB (Free On Board) cov nqe lus, nrog tus neeg muag khoom lub luag haujlwm xa cov khoom mus rau Yiwu Chaw nres nkoj thiab ua tiav cov khoom thauj mus rau lub nkoj. Cov tswv cuab thiab kev pheej hmoo hloov mus rau tus neeg yuav khoom thaum cov khoom dhau lub nkoj txoj kev tsheb ciav hlau ntawm Yiwu Port. Tom qab dej hiav txwv freight thiab zaum kawg xa mus rau Jamaica yuav npaj los ntawm tus neeg yuav khoom. Thaum lub sij hawm thauj mus los, cov cuab yeej yuav tsum tau muab khi kom ruaj ntseg kom tsis txhob muaj kev vibration thiab ya raws, nrog rau cov ntawv ntim tiav thiab cov ntaub ntawv xa tawm tau muab rau kev lis kev cai.
05 Site thiab Summary
Nrog rau kev ua haujlwm siab, kev tsim qauv tsim, thiab kev ua haujlwm ruaj khov, lub Pad no -Mounted Transformer yog qhov kev xaiv zoo tshaj plaws rau kev lag luam, kev lag luam, thiab kev siv hluav taws xob hauv pej xeem. Tsim nyob rau hauv nruj raws li thoob ntiaj teb cov qauv, txhua chav tsev guarantees superior kev ua tau zoo thiab kev nyab xeeb. Txawm hais tias koj xav tau kev faib hluav taws xob txhim khu kev qha lossis cov kev daws teeb meem rau cov chaw nyuaj, peb pab neeg tau npaj los muab cov kws tshaj lij kev txhawb nqa. Tiv tauj peb hnub no rau cov ncauj lus kom ntxaws los yog cov kev pab cuam kho kom haum-peb tau cog lus tias yuav xa cov kev daws teeb meem muaj zog thiab muaj txiaj ntsig zoo rau koj cov kev xav tau!

Cim npe nrov: 500kva pad mount transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
300 kVA Roj Filled Transformer-13.2/0.48 kV|Guyane x...
500 kVA Pad Mounted Transformer Nqe-22.86/0.208 kV|U...
1000 kVA Pad Mounted Transformer Nqe List-13.8/0.415...
1500 kVA Pad Mounted Transformer Nqe-23.9/0.416 Kv|J...
500 kVA Peb Theem Distribution Transformer-4.16/0.6 ...
1500 kVA Pad Mounted Transformer-34.5/0.48 kV|USA 2024
Xa kev nug