2000 kVA Pad Mounted Transformer-24/0.48 kV|USA 2024

2000 kVA Pad Mounted Transformer-24/0.48 kV|USA 2024

Lub Tebchaws xa tuaj: Tebchaws USA 2024
Peev xwm: 2000kVA
Voltage: 24000-480GrdY / 277 V
Feature: DOE 2016 efficiency
Xa kev nug

 

 

2000 kva pad mounted transformer

Ua tau zoo, nyab xeeb, thiab kab sib chaws-npaj - Scotech's 2000 kVA ncoo-mounted transformer powers niaj hnub infrastructure nrog kev ntseeg siab.

 

 

01 General

1.1 Project Description

Qhov no yog 2000 kVAncoo -mounted transformerua tau raws li US cov qauv tshiab, suav nrog IEEE C57.12.34-2022 thiab DOE 2016 kev ua haujlwm zoo. Nws nqis nqis thawj qhov hluav taws xob hluav taws xob los ntawm 24 kV mus rau qhov tso tawm thib ob ntawm 480GrdY / 277 V.

Featuring tooj liab windings thiab ib pawg Dyn1 vector, nws KNAN txias ua kom muaj kev ua haujlwm zoo. Kev txhim kho ib puag ncig thiab kev nyab xeeb tseem ceeb los ntawm kev siv cov kua dej FR3 - txhim kho cov ntaub ntawv pov thawj lub tsev ntsuab thaum txo kev pheej hmoo hluav taws, ua rau nws zoo tagnrho rau kev tsim kho vaj tse thiab cov chaw hauv nroog loj.

Nrog lub voj pub ua haujlwm, lub tshuab hloov pauv tau yooj yim rau hauv lub nplhaib- hom kev faib khoom, txhim kho kev ntseeg tau thiab tso cai rau kev saib xyuas niaj hnub yam tsis muaj kev cuam tshuam. Cov tuag-pem hauv ntej tsim txhim kho tus neeg teb xov tooj kev nyab xeeb.

Feem ntau siv rau hauv hluav taws xob faib hluav taws xob, qhov hloov pauv no nce qib siab -voltage input rau kev koom ua ke nrog kev tswj hwm hluav taws xob thiab cov khoom siv hluav taws xob hauv av.

 

 

 

1.2 Technical Specification

2000kVA peb theem ncoo mounted transformerspecification thiab cov ntaub ntawv

Xa rau
Teb chaws USA
Xyoo
2024
Hom
Peb theem pad mount transformer
Txuj
IEEE Std C57.12.34-2022
Rated zog
2000 kVA ua
Ntau zaus
60 tzs
Pub
Loop
Pem hauv ntej
Tuag
Theem
Peb
Hom cua txias
KNAN
Ua kua insulating
FR3 yog '
Thawj Voltage
24kv ua
Secondary Voltage
0 ,48kv
Vector Group
Dyn 1
Cov khoom siv winding
Tooj
Impedance
5.75%
Efficiency thiab Losses Standard
TSI 2016
Coj mus rhaub Changer
NLTC
Tapping Range
±2*2.5%
Tsis Load Loss
1.420 kW tsi
Ntawm Load Loss
PEB 15.600 kW
Khoom siv
Standard Configuration

 

 

1.3 Cov duab kos

2000kVA peb theem ncoo mounted transformer kos duab thiab nameplate

2000 kva pad mounted transformer drawing 2000 kva pad mounted transformer nameplate

 

 

02 Kev tsim khoom

2.1 Core

Ua nrog ntau- txheej silicon steel laminations insulated los ntawm cov kua roj vanish los yog cob, SCOTECH cores zoo suppress eddy tam sim no thiab txo circulating losses. Qhov kev tsim laminated no kuj txo qis hysteresis poob, tshwj xeeb tshaj yog thaum rov ua cov hlau nplaum. Nws ua kom muaj kev ua haujlwm siab dua thiab txuas ntxiv lub tshuab hluav taws xob lub neej kev pab cuam.

2000 kva pad mounted transformer iron core

 

2.2 Cua txias

2000 kva pad mounted transformer copper winding

Qhov no 2000 kVA Dyn1 transformer nta tooj liab windings nrog cov ntawv ci ntawm LV sab thiab ntau - txheej cylindrical winding ntawm HV sab. Tus qauv tsim ua kom muaj zog luv luv -circuit resistance, tsis tshua muaj paug tawm, thiab thermal ua haujlwm zoo rau kev ua haujlwm ruaj khov hauv qab 24 kV cov khoom siv hluav taws xob.

 

2.3 Tank

Nruab nrog cov khoom siv xws li lub siab nyem li qub, ntsuas roj qib, thiab ntsuas lub tshuab nqus tsev, lub tank tso cai rau lub sijhawm tiag tiag - saib xyuas cov xwm txheej sab hauv. Cov yam ntxwv no txhawb kev tiv thaiv kev ua txhaum thiab txhim kho kev nyab xeeb thoob plaws hauv kev ua haujlwm ntawm lub tshuab hluav taws xob.

2000 kva pad mounted transformer oil tank

 

2.4 Kev sib dhos zaum kawg

2000 kva pad mounted transformer-inside-view

Scotech xyuas kom meej tias tag nrho cov transformers xa tawm tau qhia meej meej thiab sau npe raws li Division 26 "Electrical Identification" cov qauv. Thaum lub sij hawm kev teeb tsa, peb pom zoo kom txhua qhov kev sib txuas hluav taws xob thiab cov khoom siv hluav taws xob nruj nruj raws li UL 486A thiab UL 486B kom ntseeg tau ntev -lub sijhawm.

 

 

03 Kev Xeem

Routine Test thiab Test Standard

1. Kev ntsuas ntsuas raws li IEEE C57.12.90-2021 Clause 5

2. Theem-Kev xeem txheeb raws li IEEE C57.12.90-2021 Clause 6

3. Kev Ntsuas Qhov Ntsuas raws li IEEE C57.12.90-2021 Clause 7

4. Tsis muaj Load Losses thiab Tsis Muaj Load Tam Sim No raws li IEEE C57.12.90-2021 Clause 8

5. Load Losses, Impedance Voltage thiab Efficiency raws li IEEE C57.12.90-2021 Clause 9

6. Induced Voltage Withstand Test raws li IEEE C57.12.90-2021 Clause 10.5.1

7. Applied Voltage Test raws li IEEE C57.12.90-2021 Clause 10.6

8. Kev Xeem Leak nrog Lub Siab rau Cov Kua Immersed Transformers - qhov kev ntsuam xyuas tawm ntawm 15 kPa yuav tsum tau ua rau 12 teev yam tsis muaj qhov to. Tsis tas li deformation.

9. Kev ntsuas kev tiv thaiv rwb thaiv tsev

10. Roj Dielectric Test

 

2000 kva pad mounted transformer testing
2000 kva pad mounted transformer factory test

 

Kev Xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Kev txais txiaj ntsig

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

Maximum kuj unbalance tus nqi

0.356

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Dyn1

-0.02%

Hla

3

theem- kev xeem sib txheeb

/

Dyn 1

Dyn 1

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

%

kW

I0:: muab ntsuas tus nqi

P0: muab ntsuas tus nqi

Qhov kam rau ua tsis muaj load poob yog +0%

0.18%

0.985

Hla

5

Load poob impedance voltage thiab efficiency

%

kW

kW

t:85 ua

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

Kev kam rau siab impedance yog ± 7.5%

Kev kam rau tag nrho cov load poob yog +0%

Kev ua haujlwm tsis tsawg dua 99.43%

5.61%

7.740

8.725

99.46%

Hla

6

Applied Voltage Test

kV ua

HV: 40kV 60s

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

kV ua

Kev siv hluav taws xob (KV):

0.960

Duration(s): 40

Zaus (HZ): 180

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

8

Kev Xeem Leakage

kPa ua

Kev siv siab: 15kPA

Duration: 12h

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

9

Rwb thaiv tsev Resistance Measurement

HV-LV to Av:

LV-HV to Av:

HV & LV rau hauv av:

2.51

2.60

3.88

/

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 40

52.0

Hla

 

 

04 Packing thiab Shipping

2000 kva pad mounted transformer packaging
2000 kva pad mounted transformer shipping

05 Site thiab Summary

Scotech's 2000 kVA ncoo-mounted transformer yog tsim los ua kom tau raws li cov qauv hauv Teb Chaws Asmeskas, suav nrog IEEE C57.12.34-2022 thiab DOE 2016 kev ua haujlwm zoo. Nws nqis qis dua 24 kV thawj qhov hluav taws xob mus rau 480GrdY / 277 V cov zis thib ob, uas muaj cov kab hluav taws xob tooj liab thiab Dyn1 vector pawg nrog KNAN txias kom ntseeg tau tias kev ua haujlwm ruaj khov. Kev siv cov kua dej ib puag ncig FR3 txo qis kev pheej hmoo hluav taws thiab txhawb nqa cov qauv vaj tsev ntsuab, ua rau nws zoo tagnrho rau kev tsim kho vaj tse thiab thaj chaw hauv nroog.

Lub tank steel muaj zog muaj xws li lub siab nyem li qub, ntsuas qib roj, thiab ntsuas lub tshuab nqus tsev kom paub tseeb- lub sijhawm saib xyuas thiab ua kom muaj kev nyab xeeb ntxiv. Scotech ua raws cov ntawv sau nruj thiab cov qauv kev teeb tsa kom ntseeg tau tias muaj kev ntseeg siab, siab - xa khoom zoo thiab kev ua haujlwm ntev -.

Raws li cov chaw tsim khoom ntseeg siab ntawm nruab nrab- cov khoom siv hluav taws xob faib tawm, Scotech tau cog lus los muab cov txiaj ntsig zoo, nyab xeeb, thiab lub luag haujlwm ntawm ib puag ncig lub ncoo- mounted transformers los txhawb cov phiaj xwm niaj hnub thiab cov ntawv thov kev lag luam.

2000 kva pad mounted transformer-left-view

 

Cim npe nrov: 2000 kva ncoo mounted transformer, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug