1000 kVA Tuag Pem Hauv Ntej Transformer-24/0.48 kV|USA 2024
Peev xwm: 1000kVA
Lub hwj chim: 24000 D-480Y / 277 V
Feature: nrog feedthru insert

1000 kVA tuag- pem hauv ntej ncoo-mounted transformer - muaj kev nyab xeeb, ua haujlwm tau zoo, thiab tsim kom muaj kev faib hluav taws xob zoo hauv txhua qhov chaw.
01 General
1.1 Project Description
Xa mus rau Tebchaws Meskas hauv xyoo 2024, qhov no 1000 kVApeb-phase ncoo-mounted transformerua raws li IEEE Std C57.12.34-2022 thiab ua tau raws li DOE 2016 cov qauv kev siv hluav taws xob. Nws ua haujlwm ntawm 60 Hz nrog thawj qhov hluav taws xob ntawm 24 kV thiab qhov nruab nrab ntawm 480GrdY / 277 V, featuring Dyn1 vector pawg. Lub transformer siv tooj liab windings thiab KNAN txias, thiab tau sau nrog FR3 natural ester roj los txhim kho hluav taws kev nyab xeeb thiab ib puag ncig sustainability. Nruab nrog lub voj pub ua haujlwm, tuag- nkag rau pem hauv ntej, thiab tsis muaj -load kais hloov pauv muab ± 2 × 2.5% kev tswj hwm qhov hluav taws xob, chav tsev muaj 5.75% impedance, tsis muaj -load poob ntawm 1.020 kW, thiab ib qho ntawm {{20} . 10 W, 0.000000 nbsp; poob ntawm 7 kW. vam khom nruab nrab-voltage fais fab tuag.
Lub 1000 kVA tuag pem hauv ntej transformer txo qhov kev pheej hmoo ntawm arc flash thaum ua haujlwm lossis kho. Nws tuag pem hauv ntej kev tsim kho suav nrog tag nrho cov roj hmab bushings, nrog rau kev txiav tawm ntawm lub luj tshib loadbreak, ua kom muaj kev ruaj ntseg thiab yooj yim ntawm kev sib txuas.
1000 kVA tuag pem hauv ntej ncoo mount transformer pab raws li ib tug compact thiab npaum lub zog tov rau kev siv hluav taws xob, kev lag luam, thiab kev lag luam kev siv. Engineered rau durability, nws tuaj yeem ntsia tau rau hauv tsev thiab sab nraum zoov, muab lub zog ruaj khov thiab muaj kev nyab xeeb thoob plaws ntau qhov chaw.
1.2 Technical Specification
1000kVA peb theem tuag pem hauv ntej transformer specification thiab cov ntaub ntawv ntawv
|
Xa rau
Teb chaws USA
|
|
Xyoo
2024
|
|
Hom
Peb theem pad mount transformer
|
|
Txuj
IEEE Std C57.12.34-2022
|
|
Rated zog
1000 kVA ua
|
|
Ntau zaus
60 tzs
|
|
Pub
Loop
|
|
Pem hauv ntej
Tuag
|
|
Theem
Peb
|
|
Hom cua txias
KNAN
|
|
Ua kua insulating
FR3 yog '
|
|
Thawj Voltage
24kv ua
|
|
Secondary Voltage
0 ,48kv
|
|
Vector Group
Dyn 1
|
|
Cov khoom siv winding
Tooj
|
|
Impedance
5.75%
|
|
Efficiency thiab Losses Standard
TSI 2016
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
±2*2.5%
|
|
Tsis Load Loss
1.020 kW tsi
|
|
Ntawm Load Loss
8.170 kWm
|
|
Khoom siv
Standard Configuration
|
1.3 Cov duab kos
1000kVA peb theem tuag pem hauv ntej transformer teeb duab thiab nameplate
![]() |
![]() |
02 Kev tsim khoom
2.1 Core
SCOTECH cores yog tsim nyob rau hauv kev tswj hwm nruj, kom ntseeg tau cov txheej txheem sib dhos, cov txheej txheem lamination siab, thiab sib nqus sib nqus. Cov txheej txheem no ua tau zoo txo qhov sib txawv ntawm huab cua thiab kev siv tshuab ua haujlwm nyob rau hauv cov tub ntxhais, txhim kho cov qauv kev ntseeg siab thiab txo qhov kev pheej hmoo ntawm qhov kub thiab txias.

2.2 Cua txias

Ua rau kev lag luam thiab kev lag luam siv, qhov no 1000 kVA Dyn1 transformer txais cov ntawv ci -mob LV coils thiab ntawv- insulated tooj liab hlau HV coils. Cov qauv kev ua kom zoo ua kom muaj kev ruaj ntseg rwb thaiv tsev, tsis tshua muaj suab nrov, thiab txhim khu kev ruaj ntseg nyob rau hauv 24 kV cov tswv yim thiab cov khoom sib txawv.
2.3 Tank
Transformer tank tiv thaiv cov khoom siv sab hauv los ntawm kev sib tsoo, kev vibration, thiab lwm yam quab yuam. Nws cov qauv steel reinforced ua kom ntseeg tau tias thaum thauj thiab teeb tsa, cov khoom tseem ceeb tseem muaj kev tiv thaiv zoo thiab nyob ruaj ntseg.

2.4 Kev sib dhos zaum kawg

Scotech equips txhua transformer nrog sab hauv Bay -O-Net fuses nyob rau hauv series nrog tam sim no - txwv fuses, loj npaum li cas rau kev tiv thaiv zoo. Peb muab MOV lub luj tshib- hom surge arresters uas ua tau raws li IEEE 386, ua kom muaj kev nyab xeeb ua haujlwm nyob rau hauv cov xwm txheej surge.
03 Kev Xeem
Routine Test thiab Test Standard
1. Kev ntsuas ntsuas raws li IEEE C57.12.90-2021 Clause 5
2. Theem-Kev xeem txheeb raws li IEEE C57.12.90-2021 Clause 6
3. Kev Ntsuas Qhov Ntsuas raws li IEEE C57.12.90-2021 Clause 7
4. Tsis muaj Load Losses thiab Tsis Muaj Load Tam Sim No raws li IEEE C57.12.90-2021 Clause 8
5. Load Losses, Impedance Voltage thiab Efficiency raws li IEEE C57.12.90-2021 Clause 9
6. Induced Voltage Withstand Test raws li IEEE C57.12.90-2021 Clause 10.5.1
7. Applied Voltage Test raws li IEEE C57.12.90-2021 Clause 10.6
8. Kev Xeem Leak nrog Lub Siab rau Cov Kua Immersed Transformers - qhov kev ntsuam xyuas tawm ntawm 15 kPa yuav tsum tau ua rau 12 teev yam tsis muaj qhov to. Tsis tas li deformation.
9. Kev ntsuas kev tiv thaiv rwb thaiv tsev
10. Roj Dielectric Test


Cov qhabnias xeem
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Kev txais txiaj ntsig |
Ntsuas Tus Nqi |
Xaus |
|
1 |
Kev ntsuas ntsuas |
% |
Maximum kuj unbalance tus nqi |
0.356 |
Hla |
|
2 |
Kev ntsuas ntsuas |
% |
Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5% Cov cim kev sib txuas: Dyn1 |
-0.02% |
Hla |
|
3 |
theem- kev xeem sib txheeb |
/ |
Dyn 1 |
Dyn 1 |
Hla |
|
4 |
Tsis muaj -load poob thiab excitation tam sim no |
% kW |
I0 :: muab ntsuas tus nqi P0: muab ntsuas tus nqi qhov kam rau tsis muaj load poob yog +0% |
0.18% 0.985 |
Hla |
|
5 |
Load poob impedance voltage thiab efficiency |
% kW kW |
t:85 ua Z%: ntsuas tus nqi Pk: ntsuas tus nqi Pt: ntsuas tus nqi Qhov kam rau ua impedance yog ± 7.5% qhov kam rau tag nrho load poob yog +0% Kev ua haujlwm tsis tsawg dua 99.43% |
5.61% 7.740 8.725 99.46% |
Hla |
|
6 |
Applied Voltage Test |
kV ua |
HV: 40kV 60s LV: 10kV 60s |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
7 |
Induced Voltage Withstand Test |
kV ua |
Kev siv hluav taws xob (KV): 0.960 Duration(s): 40 Zaus (HZ): 180 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
8 |
Kev Xeem Leakage |
kPa ua |
Kev siv siab: 15kPA Duration: 12h |
Tsis muaj leakage thiab tsis muaj Kev puas tsuaj |
Hla |
|
9 |
Rwb thaiv tsev Resistance Measurement |
GΩ |
HV-LV to Av: LV-HV to Av: HV & LV rau hauv av: |
2.51 2.60 3.88 |
/ |
|
10 |
Roj Dielectric Test |
kV ua |
Ntau dua lossis sib npaug li 40 |
52.0 |
Hla |
04 Packing thiab Shipping
![]() |
![]() |
05 Site thiab Summary
Scotech's 1000 kVA tuag pem hauv ntej transformeryog tsim los rau kev txhim khu kev qha thiab muaj txiaj ntsig nruab nrab-voltage fais fab kev faib tawm hauv kev siv hluav taws xob, kev lag luam, thiab chaw tsim khoom. Tsim los ua kom tau raws li IEEE Std C57.12.34-2022 thiab DOE 2016 cov qauv hluav taws xob, lub tshuab hluav taws xob no nta tooj liab windings, KNAN txias, thiab FR3 ntuj ester roj rau kev txhim kho kev nyab xeeb thiab kev saib xyuas ib puag ncig. Nws tuag pem hauv ntej tsim nrog tag nrho insulated bushings thiab loadbreak luj tshib ho txo arc flash kev pheej hmoo thaum lub sij hawm ua hauj lwm thiab txij nkawm.
Ua nrog precision-stacked cores thiab optimized foil-mob LV thiab ntawv-insulated HV coils, nws ua kom cov rwb thaiv tsev ruaj khov thiab tsis tshua muaj suab nrov nyob rau hauv ntau qhov sib txawv. Lub tank steel muaj zog tiv thaiv cov khoom tseem ceeb los ntawm kev poob siab thiab kev vibrations thoob plaws hauv kev thauj mus los thiab kev teeb tsa. Nruab nrog Bay-O-Net thiab tam sim no- txwv fuses ntxiv rau IEEE 386-raws li MOV surge arresters, qhov tuag pem hauv ntej transformer muaj kev tiv thaiv thiab kev ua tau zoo.
Ntawm Scotech, peb tsom mus rau kev xa cov khoom siv tau, muaj kev nyab xeeb, thiab ruaj khov rau pem hauv ntej transformers uas haum rau ntau qhov chaw sib txawv - sab hauv tsev lossis sab nraum zoov - txhawb nqa koj txoj haujlwm nrog kev ntseeg siab thiab kev thaj yeeb ntawm lub siab.

Cim npe nrov: tuag pem hauv ntej transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
225 kVA Pad Mount Transformer-34.5/0.208 kV|USA 2024
300 kVA Pad Mount Transformer-12.47/0.48 kV|USA 2024
1000 kVA Residential Pad Mounted Transformer-22.86/0...
500 kVA Tuag Pem Hauv Ntej Pad Mounted Transformer-2...
1500 kVA Mount Transformer-22.86/0.208 kV|USA 2024
1500 kVA Pad Mounted Transformer-34.5/0.48 kV|USA 2024
Xa kev nug