300 kVA Pad Mount Transformer-12.47/0.48 kV|USA 2024
Peev xwm: 300kVA
Qhov hluav taws xob: 12.47 / 0.48kV
Feature: stainless hlau tank

Green innovation, zog-txuag pioneer-Peb-theem ncoo-mounted transformers, ua rau lub sijhawm ntawm lub zog ruaj khov!
01 General
1.1 Project Background
300 kVA ncoo mounted transformer tau xa mus rau Asmeskas hauv xyoo 2024. Lub zog ntsuas ntawm lub transformer yog 300 kVA nrog ONAN txias. Thawj qhov hluav taws xob yog 12.47GrdY / 7.2 kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov nruab nrab voltage yog 0.48 / 0.277 kV, lawv tsim ib pawg vector ntawm YNyn0, qhov zoo yog qhov zoo tshaj plaws voltage, nruab nrab taw tes tsis drift, lub thawv tsis kub, tsis muaj suab nrov, zoo teeb pom kev zoo. Nws yog ib lub voj feed thiab tuag pem hauv ntej transformer. pad mounted transformer tuaj yeem siv sab hauv tsev lossis sab nraum zoov, dav siv hauv cov chaw ua si, thaj chaw nyob, chaw ua lag luam thiab siab - nce vaj tsev thiab lwm qhov chaw.
Nws yog tsim nyog hais tias lub dielectric coolant nyob rau hauv lub transformer siv heev refined hom II inhibited tshiab ntxhia roj. Bayonet nrog kev txwv tam sim no fuses. Lub siab -voltage overcurrent tiv thaiv tswvyim muab nrog lub transformer yog ib tug sab nraud tshem tawm loadbreak expulsion Bay-O-Net fuse sib dhos nrog lub flapper valve kom txo cov roj nchuav. Lub bayonet fuses yog nyob rau hauv series nrog ELSP nyob rau hauv - roj ib nrab -ntau yam tam sim no txwv rov qab -up fuses nrog kev cuam tshuam kev ntsuam xyuas ntawm 50,000 RMS symmetrical amperes cuam tshuam nrog yam tsawg kawg nkaus melting tam sim no kwv yees li 200% ntawm transformer nameplate ntsuam xyuas.
1.2 Technical Specification
300 kVA transformer specifications hom thiab cov ntaub ntawv ntawv
|
Xa rau
Asmeskas
|
|
Xyoo
2024
|
|
Hom
Pad mounted transformer
|
|
Txuj
IEEE Std C57.12.34-2022
|
|
Rated zog
300 KVA ua
|
|
Ntau zaus
60 tzs
|
|
Theem
3
|
|
Pub
Loop
|
|
Pem hauv ntej
Tuag
|
|
Hom cua txias
ONAN
|
|
Thawj Voltage
12.47 GRDY/7.2 KV
|
|
Secondary Voltage
0.48/0.277 KV
|
|
Cov khoom siv winding
Aluminium
|
|
Angular tshem tawm
yNyj 0
|
|
Impedance
4%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
±2*2.5%
|
|
Tsis Load Loss
0.45 kWm
|
|
Ntawm Load Loss
2, 925 kWm
|
|
Khoom siv
Standard Configuration
|
1.3 Cov duab kos
300 kVA ncoo mounted transformer daim duab kos duab thiab loj.
![]() |
![]() |
02 Kev tsim khoom
2.1 Core
Qhov zoo ntawm Peb -Phase Tsib- Limb Core
High Sib nqus Circuit Court Symmetry:Txhim kho peb -phase tshuav nyiaj li cas.
Luv luv zoo heev -Circuit Performance:Muaj zog tiv thaiv luv luv Circuit Court nrog tsawg sib nqus saturation.
Robust Mechanical Structure:Kev sib xyaw ua ke ntawm cov hlua khi thiab cov cuab yeej clamping ua kom ntev - lub sijhawm ua haujlwm kev ntseeg siab.
Clamping Devices Function: Txhim kho cov tub ntxhais thiab tiv thaiv cov nplooj ntawv silicon steel los ntawm loosening; txhawb nqa qhov hnyav ntawm cov tub ntxhais thiab windings.
Tie Phaj Function: Fasten lub qaum thiab qis clamping li siv bolts, muab lateral siab, thiab tiv thaiv cov tub ntxhais los ntawm loosening.

2.2 Cua txias

Lub kauj yog insulated nrog B-theem, epoxy coated, pob zeb diamond qauv, insulating ntawv, uas yog thermally kho nyob rau hauv lub siab los xyuas kom meej kev sib raug zoo ntawm cov neeg xyuas pib thiab ntawv. Lub coil tau raug ua tiav los xyuas kom meej qhov siab tshaj plaws ntawm cov dej insulating rau hauv lub coil rwb thaiv tsev. Kev sib xyaw ua ke ntawm low-voltage foil winding thiab high-voltage wire winding ua tiav qhov tsis muaj load poob thiab luv luv-circuit impedance, ua tau raws li cov kev xav tau sib txawv. Xyuas kom muaj hluav taws xob sib cais ntawm high-voltage thiab low-voltage windings, txhim khu kev ruaj ntseg. Cov neeg kho tshuab ruaj khov ntawm cov ntawv ci winding thiab rwb thaiv tsev kev ntseeg tau ntawm cov hlau winding txhim kho lub transformer lub neej ua haujlwm. Muaj zog tiv thaiv luv luv thiab kev vibrations ua rau nws haum rau kev ua haujlwm hnyav.
2.3 Tank
Lub tank transformer yog ua los ntawm 304 stainless hlau, Lub tank puag yog tsim los tso cai rau skidding los yog dov nyob rau hauv txhua txoj kev. Lifting cov kev cai muaj plaub lub lifting lugs welded rau lub tank. Lub transformer txais kev kaw lub tank tsim muaj lub zog txaus los tiv thaiv lub siab ntawm 7 psig yam tsis muaj kev cuam tshuam mus tas li, thiab 15 psig yam tsis muaj kev puas tsuaj lossis cuam tshuam rau txee ruaj ntseg.
Lub tank muaj xws li cov cuab yeej siv lub siab ua kom txo tau qhov siab ntawm qhov siab dhau los ntawm kev ua haujlwm ib txwm muaj. Cov yam ntxwv venting thiab sealing yuav tsum yog raws li nram no:
a. Cracking siab: 10psig ± 2psig.
b. Resealing siab: 6psig yam tsawg kawg nkaus.
c. Zero to los ntawm reseal siab rau -8psig.
d. Flow ntawm 15 psig: 35 SCFM yam tsawg kawg nkaus.

2.4 Kev sib dhos zaum kawg

Core Component Installation:
Txhim kho cov tub ntxhais thiab windings rau hauv cov roj tank, txuas siab - thiab qis-voltage leads, thiab nruab rwb thaiv tsev thiab thaiv cov khoom kom ntseeg tau tias muaj kev sib txuas hluav taws xob.
Accessory Installation:
Txhim kho cov khoom siv xws li cov roj ntsuas ntsuas, ntsuas kub, thiab cov cua txias. Txuas lub thawv davhlau ya nyob twg thiab cov chaw tswj, ua kom tiav kev teeb tsa ntawm cov khoom siv tiv thaiv.
Enclosure thiab sealing:
Mount cov hlau thaiv kom kaw cov roj tank, xyuas thiab kaw cov pob qij txha kom ntseeg tau tias ya raws thiab tiv taus.
Kev Xeem thiab Roj Sau:
Ua cov kev ntsuam xyuas hluav taws xob thiab kev ua haujlwm, sau cov roj tank nrog cov roj insulating, tshem tawm cov npuas, thiab ua cov roj- ntsuas nruj.
03 Kev Xeem
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Txais Tus nqi |
Ntsuas Tus Nqi |
Xaus |
|
1 |
Kev ntsuas ntsuas |
% |
Maximum kuj unbalance tus nqi |
0.37 |
Hla |
|
2 |
Kev ntsuas ntsuas |
% |
Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5% |
-0.05 |
Hla |
|
3 |
Theem -kev xeem sib txheeb |
/ |
yNyj 0 |
yNyj 0 |
Hla |
|
4 |
Tsis muaj -load poob thiab excitation tam sim no |
% |
I0 :: muab ntsuas tus nqi |
0.28 |
Hla |
|
kW |
P0: muab ntsuas tus nqi (ntawm 20 degree) |
0.412 |
|||
|
/ |
Kev kam rau ua tsis muaj load poob yog ± 10% |
/ |
|||
|
5 |
Load poob, impedance voltage, tag nrho poob thiab efficiency |
/ |
t:85 ua Qhov kam rau ua impedance yog ± 7.5% kev kam rau tag nrho load poob yog ± 6% |
/ |
Hla |
|
% |
Z%: ntsuas tus nqi |
3.86 |
|||
|
kW |
Pk: ntsuas tus nqi |
2.822 |
|||
|
kW |
Pt: ntsuas tus nqi |
3.234 |
|||
|
% |
Kev ua haujlwm tsis tsawg dua 99.27% |
99.30 |
|||
|
6 |
Applied Voltage Test |
/ |
HV: 34kV 60s LV: 10kV 60s |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
7 |
Induced Voltage Withstand Test |
/ |
Kev siv hluav taws xob (KV): 0.96 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
Duration(s):48 |
|||||
|
Zaus (HZ): 150 |
|||||
|
8 |
Rwb thaiv tsev Resistance Measurement |
GΩ |
HV-LV to Av: |
85.3 |
/ |
|
LV-HV to Av: |
95.2 |
||||
|
HV & LV rau hauv av: |
90.1 |
||||
|
9 |
Kev Xeem Leakage |
/ |
Kev siv siab: 20kPA |
Tsis muaj leakage thiab tsis muaj Kev puas tsuaj |
Hla |
|
Duration: 12h |
|||||
|
10 |
Roj Xeem |
kV ua |
Dielectric zog |
56.9 |
Hla |
|
mg/kg |
Cov ntsiab lus noo noo |
9.9 |
|||
|
% |
Dissipation Factor |
0.0274 |
|||
|
mg/kg |
Furan Analysis |
/ |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Packing thiab Shipping


05 Site thiab Summary
Hauv kev lag luam tam sim no hloov pauv sai sai, peb theem pad mounted transformer tau dhau los ua ib qho tseem ceeb ntawm cov hluav taws xob faib hluav taws xob vim nws qhov ua tau zoo thiab kev ntseeg tau. Txawm hais tias nyob hauv thaj chaw, kev lag luam, lossis kev lag luam, nws cov qauv tsim, yooj yim ntawm kev saib xyuas, thiab kev ua haujlwm zoo ib puag ncig ua rau nws muaj peev xwm ua tau raws li ntau yam kev xav tau ntawm lub zog. Kev xaiv peb theem pad mounted transformer tsis yog tsuas yog ib qho kev xaiv rau kev siv hluav taws xob zoo xwb tab sis kuj yog kev cog lus rau kev nyab xeeb thiab kev ruaj ntseg. Peb mob siab rau muab peb cov neeg siv khoom nrog cov khoom tshwj xeeb thiab cov kev pabcuam, pab koj ua tiav cov txiaj ntsig siab tshaj plaws hauv cov tshuab hluav taws xob niaj hnub no.

Cim npe nrov: 300kva pad mount transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
300 kVA Green Box Transformer-12/0.12*0.24 kV|Jamaic...
2500 kVA Residential Electrical Transformers-34.5/0....
500 kVA Pad Mounted Transformer Nqe-22.86/0.208 kV|U...
750 kVA Pad Mounted Transformer-13.2/0.48 kV|USA 2024
1000 kVA Roj Filled Pad Mounted Transformer-13.8/0.4...
1000 kVA Pad Mount Transformer-13.8/0.46 kV|Guyane x...
Xa kev nug