1500 KVA Hluav Taws Xob Substations-5/0.48 KV|USA 2025

1500 KVA Hluav Taws Xob Substations-5/0.48 KV|USA 2025

Lub teb chaws: USA 2025
Muaj peev xwm: 1500 kVA
Qhov hluav taws xob: 5D-0.48Y / 0.277 kV
Feature: FR3 roj
Xa kev nug

Jiangshan Scotech Hluav Taws Xob Co., Ltd yog ib qho ntawm feem txhim khu kev qha manufacturers thiab lwm tus neeg ntawm 1500 kva hluav taws xob substations-5/0.48 kv|USA 2025 in China. Thov koj xav tias dawb mus yuav cov khoom lag luam zoo rau kev muag ntawm no thiab tau txais cov duab kos los ntawm peb lub hoobkas. Tiv tauj peb kom paub meej ntxiv.

 

electrical substations

Unit Substation Transformer - Kev sib xyaw ua ke, ua haujlwm tau zoo, thiab lub plawv ntawm kev faib hluav taws xob txhim khu kev qha.

 

 

01 General

1.1 Project Description

1500 kVA chav tsev substation transformer raug xa mus rau Tebchaws Meskas hauv xyoo 2025. Lub zog ntsuas ntawm lub transformer yog 1500 kVA nrog KNAN txias. Qhov siab voltage yog 5D kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov tsawg voltage yog 0.48Y / 0.277 kV, lawv tsim ib pawg vector ntawm Dyn1.

Cov chaw nres tsheb hluav taws xob yog cov khoom siv hluav taws xob sib txuas sib txuas uas sib txuas ua ke thawj qhov hloov pauv, peb lub -theem fais fab transformer, thiab cov khoom siv hluav taws xob thib ob rau hauv ib qho, kaw- sib txuas ua ke. Nws yog tsim los txo cov nqi hluav taws xob faib hluav taws xob mus rau qib uas haum rau hauv - cog lossis kev lag luam hauv tsev faib khoom, thiab tsim nyog rau kev teeb tsa sab hauv tsev thiab sab nraum zoov. Nrog rau nws nyob ze-coupled tsim, lub transformer tuaj yeem muab tso rau ze ntawm qhov chaw thauj khoom, txo qhov ntev ntawm cable thiab tsheb npav, uas ua rau txo qis kab poob thiab raug cuam tshuam thaum txhim kho kev tswj hluav taws xob thiab kev pabcuam txuas ntxiv. Piv nrog rau cov qauv substation ua ke, nws cov hneev taw me me txuag tau ntau qhov chaw teeb tsa, txo rau ntawm - qhov chaw tsim kho thiab cov nqi tsheb thauj mus los, thiab txo qis ntev - cov nqi kho mob los ntawm cov khoom siv yooj yim. Chav tsev substation transformer ua raws li ANSI, IEEE, thiab NEMA cov qauv, ua kom tiav kev sib koom ua ke ntawm hluav taws xob thiab tshuab. Raws li ib qho kev xaiv, lub transformer tuaj yeem sau nrog FR3 ™ natural ester kua- tauj dua tshiab, zaub- roj-raws li dielectric nrog rau qhov hluav taws kub siab thiab ib puag ncig zoo heev -thaum cov roj ntxhia roj tseem muaj rau cov ntawv thov nrog cov qauv yuav tsum tau ua. Nrog nws cov kev ntseeg siab, efficiency, thiab hloov tau yooj yim configuration, lubchav tsev substation transformeryog siv dav hauv cov chaw tsim khoom, cov tsev lag luam, cov chaw siv hluav taws xob, thiab cov kev sib txuas lus tseem ceeb uas qhov chaw, kev nyab xeeb, thiab kev ua haujlwm tseem ceeb.

 

 

 

1.2 Technical Specification

1500 kV hluav taws xob substations specifications hom thiab cov ntaub ntawv ntawv

Xa rau
Teb chaws USA
Xyoo
2025
Hom
chav tsev substation transformer
Txuj
IEEE
Rated zog
1500 kVA ua
Ntau zaus
60 tzs
Theem
3
Hom cua txias
KNAN
Thawj Voltage
5d kwv
Secondary Voltage
0.48 Y / 0.277 kV
Cov khoom siv winding
Tooj
Vector Group
yNyj 0
Impedance
5.75%±7.5%
Coj mus rhaub Changer
NLTC
Tapping Range
±2*2.5%
Tsis Load Loss
1, 545 kWm
Ntawm Load Loss
PEB 10.54 kW

 

1.3 Cov duab kos

1500 kVA hluav taws xob substations daim duab kos duab thiab qhov loj me.

electrical substations diagram electrical substations nameplate

 

 

02 Kev tsim khoom

2.1 Core

electrical substations core

Core uses CRGO silicon steel, perfectly matched to 1500kVA, 5.0/0.48kV, Dyn1, 60Hz (no‑load loss 1.545kW, load loss 10.540kW). Design & manufacturing comply with IEEE C57.12.34-2022, C57.12.00-2021 & C57.12.90-2021. Tests confirm: max turns ratio deviation +0.16% (well below 0.5%), losses and impedance meet guaranteed values. Quality: five‑step step‑lap process reduces eddy losses and noise; core clamped and coated against moisture/rust. Highlights: step‑lap cuts no‑load current ~12% and transverse leakage >50% yog '; 45℃mitered pob qij txha du flux steering.

 

2.2 Cua txias

HV winding nrog 2 × 2.5% on-load kais dej (5 kais), LV Y txuas 480V / 277V + nruab nrab. Cov txiaj ntsig kev xeem (saib cov lus hauv qab no) qhia LV tsis sib npaug 1.11%, HV max unbalance 0.80%; rwb thaiv tsev tsis kam & sib nqus sib npaug tag nrho dhau. Zoo: high-purity tooj liab, Class F (155 degree) rwb thaiv tsev, nqus vapor-theem ziab. Highlights: nruam / interleaved HV tsim, ntawv ci / helical LV windings, txhawb qhov kawg clamping rau luv-circuit withstand.

Cov khoom kuaj

Ntsuas tus nqi / Qhov tshwm sim

Txuj Kev Cai

HV winding kuj (kais 5)

0.0699Ω (3 theem avg.)

Max unbalance Tsawg dua lossis sib npaug li 1%

LV winding tsis kam

0.714/0.706/0.713 mΩ

Tsis sib npaug 1.11%

LV nruab nrab point kuj

0.388/0.380/0.376 mΩ

Tsis sib npaug 3.07%

Rwb thaiv tsev tsis kam (HV-GND, thiab lwm yam)

Hla

Saib daim ntawv qhia

Magnetic balance test

Balanced voltages ib kauj ruam

Tsis muaj qhov txawv txav

electrical substations copper winding

 

2.3 Tank

Tank tsim nrog stiffeners; kuaj ntawm +50kPa thiab -67kPa. Cov txiaj ntsig (saib cov lus): tom qab tso tawm, ruaj khov deflection Tsawg dua lossis sib npaug ntawm 0.03mm ntawm tag nrho 10 cov ntsiab lus, tsis muaj kev puas tsuaj - ob qho tib si kev xeem dhau. Zoo: qib high-qib steel, 100% kev soj ntsuam vuam, cais kev ntsuas ua ntej sib dhos. Cov ntsiab lus tseem ceeb: optimized rib layout, tswj vuam cua sov input, gasket tsim tawm tsam roj to & ya raws ingress.

Kev ntsuas siab zoo (50kPa):

Taw tes

1

2

3

4

5

6

7

8

9

10

Pib (mm)

1.50

1.50

1.50

1.50

1.30

1.50

1.50

1.50

1.20

1.50

Tom qab siv siab (mm)

2.19

+3.00

+3.00

2.72

2.10

1.72

2.07

1.94

2.15

1.98

Tom qab tso siab (mm)

1.51

1.52

1.52

1.51

1.51

1.51

1.51

1.52

1.52

1.50

Permanent deflection (mm)

0.01

0.02

0.02

0.01

0.01

0.01

0.01

0.02

0.02

0.02

 

Lub tshuab nqus tsev vacuum (-67kPa):

Taw tes

1

2

3

4

5

6

7

8

9

10

Pib (mm)

1.51

1.52

1.52

1.51

1.51

1.51

1.51

1.52

1.52

1.52

Tom qab nqus tsev vacuum (mm)

0.71

-0.00

-0.00

-0.00

0.78

1.12

0.89

1.01

0.85

0.92

Tom qab lub tshuab nqus tsev tso tawm (mm)

1.49

1.49

1.50

1.48

1.49

1.49

1.49

1.49

1.49

1.50

Permanent deflection (mm)

0.02

0.03

0.02

0.03

0.02

0.02

0.02

0.03

0.03

0.01

 

electrical substations tank past pressure test

 

2.4 Kev sib dhos zaum kawg

electrical substations active part

Kev sib dhos: core-coil txo qis, kev kho cov roj nqus, bushing / accessory installation, Dyn1 lead configuration. Cov kev xeem ib nrab tiav (tom qab ziab, ua ntej tanking) tag nrho dhau: rwb thaiv tsev tsis kam, lem ratio (max dev. 0.16%), theem kev sib raug zoo (Dyn1), winding resistance, impedance (5.75%), sib nqus sib nqus. Zoo: txhua kauj ruam kaw, roj nqus-filtered, kais-changer ua haujlwm tau lees paub. Cov ntsiab lus tseem ceeb: lub tshuab nqus tsev ziab & impregnation, precision jigs rau core-tank clearance, torque-caj dab nruj ntawm txhua qhov kev sib txuas.

 

 

03 Kev Xeem

Cov kev ntsuam xyuas npog hluav taws xob, khoom siv hluav taws xob & rwb thaiv tsev ua haujlwm raws li IEEE C57.12.00-2021 & C57.12.90-2021.

Cov khoom kuaj

Kev Xeem

Xaus

Rwb thaiv tsev tsis kam (HV-GND, LV-GND, HV-LV, core-frame)

Hla

Hla

Hloov pauv qhov sib txawv

<0.2% per tap

Hla

Theem kev sib raug zoo

Dyn 1

Yog lawm

Winding kuj tsis sib npaug

LV 1.11%, HV 0.80%

Zoo heev

Luv-circuit impedance

5.75%

Ua tau raws li tus nqi lav

Magnetic balance test

3-theem voltage balanced

Hla

Kev ntsuas siab zoo (50kPa)

Permanent deflection Tsawg dua lossis sib npaug ntawm 0.02mm

Hla

Lub tshuab nqus tsev vacuum (-67kPa)

Permanent deflection Tsawg dua lossis sib npaug ntawm 0.03mm

Hla

Tank pom kev soj ntsuam

Tsis muaj kev puas tsuaj

Hla

electrical substations short-circuit impedance
electrical substations routine test

 

 

04 Packing thiab Shipping

4.1 Ntim

Kev cai ntoo crates, ISPM15 kub-kho ntoo rau kev lis kev cai clearance tsis muaj fumigation. Kev ntseeg tau txheeb xyuas los ntawm kev tshuaj xyuas ua ntej xa khoom & kev co simulation. Zoo: 6-txoj kev strapping + anti-slip pads (kev txav<2mm), cushioning material, moisture/rust protection. Highlights: centre of gravity & lifting points marked, 100% pre‑pack inspection, spare parts in same crate.

electrical substations packed with custom wooden crates

 

4.2 Shipping

electrical substations shipping under CIF term

Hiav txwv / av thauj mus rau qhov chaw; traceable ntawm daim ntawv cog lus & serial tooj. Ua raws li Incoterms & export cov cai; kev tshuaj xyuas ua ntej ua zaub mov txaus siab rau kev lis kev cai. Kev ntseeg tau lees paub los ntawm kev co simulation. Zoo: huab cua-pov thawj "tsis txhob ntxeev / poob" cov ntawv, kev tshuaj ntsuam xyuas, tag nrho cov ntaub ntawv xa khoom & COO. Cov ntsiab lus tseem ceeb: eco-friendly cov ntaub ntawv, cov cim qhia txog kev poob siab ntawm cov chav loj, cov ntawv ntim khoom / cov npe hnyav / qhov loj me tau muab.

 

05 Cov ntsiab lus

Nyob rau hauv cov ntsiab lus, qhov 1500kVA hluav taws xob substations muab tshwj xeeb hluav taws xob kev ua tau zoo, muaj pov thawj mechanical robustness, thiab tag nrho ua raws li IEEE C57.12.34-2022. Nrog cov tub ntxhais thiab winding poob lub rooj sib tham tau lees paub qhov tseem ceeb, qhov sib txawv ntawm qhov sib txawv hauv qab 0.2%, winding kuj tsis sib npaug qis li 1.11%, thiab lub tank ruaj khov deformation nyob rau hauv siab / lub tshuab nqus tsev kuaj txwv tsawg dua lossis sib npaug li 0.03mm, nws muaj kev txhim khu kev qha, tsis tshua muaj nqi ntawm lub neej. Kev sim ua tiav ib nrab tiav thiab zaum kawg - los ntawm kev tiv thaiv kev tiv thaiv rau kev sib nqus sib nqus thiab lub tank deformation - xyuas kom txhua chav tawm hauv lub Hoobkas npaj rau kev thov kev siv hluav taws xob.Xaiv SCOTECHraws li koj tus khub ntseeg siab los tsim kom muaj kev txawj ntse, muaj zog dua hluav taws xob infrastructure.

electrical substations supplier

 

 

Cim npe nrov: hluav taws xob substations, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug