862 kVA Unit Substation-13.8/0.48 kV|USA 2025
Peev xwm: 750 / 862 kVA
Qhov hluav taws xob: 13.8-0.48 / 0.277kV
Feature: nrog FR3 roj

Lub zog ntse, kev txuag nyiaj zoo tshaj. Peb Chav Substation Transformers.
01 General
1.1 Project Description
750/862 kVA unit substation transformer tau xa mus rau Canada hauv 2025. Lub zog ntsuas ntawm lub tshuab hloov pauv yog 750/862 kVA nrog KNAN / KNAF txias. Thawj qhov hluav taws xob yog 13.8 kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov nruab nrab voltage yog 0.48 / 0.277 kV, lawv tsim ib pawg vector ntawm Dyn1.
Engineered rau kev ua tau zoo dua thiab kev ntseeg tau, qhov no 750/862 kVA chav tsev substation transformer muab cov kev daws teeb meem ua tiav rau kev thov kev lag luam thiab kev lag luam. Nws nta FR3® ntuj ester kua rau kev txhim kho hluav taws xob kev nyab xeeb thiab txuas ntxiv lub neej rwb thaiv tsev, ua ke nrog kev ua haujlwm zoo thermal (Top Roj: 45K, Winding Avg: 50K, Hot Spot: 63K) kom ntseeg tau tias kev ua haujlwm zoo thiab ua haujlwm tau zoo nyob rau hauv qhov chaw siab tshaj. Lub tshuab hluav taws xob tiv thaiv- hauv av rau kev txhim kho kev tiv thaiv thiab tuaj yeem nruab nrog cov khoom siv sib xyaw ua ke- suav nrog CT txee rau kev ntsuas thiab kev tiv thaiv, detachable radiators nrog cov kiv cua txias, lub log kom yooj yim tso, lub siab ceev relay rau kev tiv thaiv kev ua txhaum, thiab xob laim ntes rau kev tiv thaiv surge tiv thaiv{1}{1}{1} npaj txhij, {1} Cov pob hluav taws xob zoo tsim los rau kev nyab xeeb, kev ntseeg tau, thiab kev saib xyuas yooj yim.
1.2 Technical Specification
750/862 kVA unit substation transformer specifications type and data sheet
|
Xa rau
Asmeskas
|
|
Xyoo
2025
|
|
Hom
Substation transformer
|
|
Txuj
ANSI C57.12.00 Nws
|
|
Rated zog
750/{1}} kVA
|
|
Ntau zaus
60 tzs
|
|
Theem
3
|
|
Hom cua txias
KNAN/KNAF
|
|
Thawj Voltage
13.8 kV 2
|
|
Secondary Voltage
0.48 / 0.277 kV
|
|
Cov khoom siv winding
Tooj
|
|
Angular tshem tawm
Dyn 1
|
|
Impedance
6%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
±2*2.5%
|
|
Tsis Load Loss
Tsawg dua lossis sib npaug li 1.16 kW
|
|
Ntawm Load Loss
Tsawg dua lossis sib npaug li 7.08kW
|
1.3 Cov duab kos
750/862 kVA unit substation transformer daim duab kos duab thiab qhov loj me.
![]() |
![]() |
02 Kev tsim khoom
2.1 Core
Cov tub ntxhais yog precision-ua nrog siab-qib, txias- dov nplej- taw qhia silicon steel. Cov khoom siv no, nrog rau kev tsim laminated qib siab, txo qis kev sib nqus thiab lub zog tam sim no. Nws txoj kev tsim kho ruaj khov ua kom muaj suab nrov tsawg thiab lub zog siv tshuab, muab txoj hauv kev ruaj khov thiab muaj txiaj ntsig zoo sib nqus uas yog qhov tseem ceeb rau kev hloov pauv kev ntseeg tau thiab kev ua haujlwm.
2.2 Cua txias
Cov windings yog optimally tsim rau kev ua tau zoo thiab kev ntseeg tau. Qhov qis-voltage winding siv cov ntawv ci- tsim qhov txhab, muab cov neeg kho tshuab zoo heev, ua kom muaj cua sov zoo dua, thiab luv luv - Circuit Court muaj peev xwm. Ua kom tiav nws, qhov siab -voltage winding ntiav cov txheej txheem precision- cov txheej txheem mob nrog kev sib cuam tshuam zoo -tig rwb thaiv tsev, kom ntseeg tau qhov hloov pauv qhov tseeb thiab lub zog dielectric zog. Qhov kev sib xyaw ua pov thawj no muab kev ua haujlwm tshwj xeeb, ruaj khov, thiab kav ntev.

2.3 Tank

Lub tank yog ib qho ruaj khov, welded steel qauv tsim los rau kev ua haujlwm ntev thiab kev ua haujlwm. Nws ua hauj lwm raws li ib tug tiv thaiv enclosure rau cov tub ntxhais thiab windings, muab ib tug kaw reservoir rau insulating kua, thiab nta radiators kom zoo cua sov dissipation. Engineered los tiv thaiv ib puag ncig thiab kev ua haujlwm kev ntxhov siab, lub tank ua kom lub tshuab hloov lub sijhawm ntev - kev ncaj ncees thiab kev ntseeg tau.
2.4 Lub Rooj Sib Tham Kawg
Kev sib dhos zaum kawg yog kev sib koom ua ke ntawm cov tub ntxhais, windings, tank, thiab cov khoom siv rau hauv kev sib koom ua ke thiab muaj zog. Lub sijhawm tseem ceeb no ua kom txhua qhov kev sib txuas hluav taws xob sab hauv tau ruaj ntseg, cov khoom siv tshuab muaj suab nrov, thiab lub kaw lus kaw zoo kawg nkaus. Qhov tshwm sim yog qhov ua tiav ntawm tus kheej -muaj, npaj tau- rau- lub zog ua haujlwm uas muab cov qauv tsim, ua haujlwm ntev, thiab kev ntseeg tau.

03 Kev Xeem
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Kev txais txiaj ntsig |
Ntsuas Tus Nqi |
Xaus |
|
1 |
Kev ntsuas ntsuas |
% |
Maximum kuj unbalance tus nqi |
3.19 |
Hla |
|
2 |
Kev ntsuas ntsuas |
% |
Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5% |
-0.05~0.01 |
Hla |
|
3 |
Theem -kev xeem sib txheeb |
/ |
Dyn 1 |
Dyn 1 |
Hla |
|
4 |
Tsis muaj -load poob thiab excitation tam sim no |
% |
I0 :: muab ntsuas tus nqi |
0.47 |
Hla |
|
kW |
P0: muab ntsuas tus nqi |
0.938 |
|||
|
/ |
qhov kam rau tsis muaj load poob yog +0% |
/ |
|||
|
5 |
Load poob, impedance voltage, tag nrho poob thiab efficiency |
/ |
t:85 ua qhov kam rau ua impedance yog +7.5% qhov kam rau tag nrho load poob yog +0% |
/ |
Hla |
|
% |
Z%: ntsuas tus nqi |
6.20 |
|||
|
kW |
Pk: ntsuas tus nqi |
6.903 |
|||
|
kW |
Pt: ntsuas tus nqi |
7.841 |
|||
|
% |
Kev ua haujlwm tsis tsawg dua 99.16% |
99.21 |
|||
|
6 |
Applied Voltage Test |
/ |
HV: 34kV 60s LV: 10kV 60s |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
7 |
Induced Voltage Withstand Test |
/ |
Kev siv hluav taws xob (KV): 0.96 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
Duration(s): 40 |
|||||
|
Zaus (HZ): 180 |
|||||
|
8 |
Rwb thaiv tsev Resistance Measurement |
GΩ |
HV-LV to Av: |
8.18 |
Hla |
|
LV-HV to Av: |
3.79 |
||||
|
HV & LV rau hauv av: |
8.98 |
||||
|
9 |
Kev Xeem Leakage |
/ |
Kev siv siab: 50kPA |
Tsis muaj leakage thiab tsis muaj Kev puas tsuaj |
Hla |
|
Duration: 12h |
|||||
|
10 |
xob laim impulse test |
kV ua |
puv nthwv dej |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
11 |
Roj Xeem |
kV ua |
Dielectric zog Ntsuas tus nqi Ntau dua lossis sib npaug rau 45 kV |
68.4 |
Hla |
|
mg/kg |
Cov ntsiab lus noo noo |
168.6 |
|||
|
% |
Dissipation Factor |
3.751 |
|||
|
mg/kg |
Furan Analysis |
/ |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Packing thiab Shipping
4.1 Ntim
Chav tsev substation transformer yog ntim nrog kev tsom mus rau kev tiv thaiv kev ruaj ntseg thiab tuav kev ua haujlwm zoo. Nws yog feem ntau crated rau ntawm ib tug robust, skidded puag rau structural kev ncaj ncees thiab forklift nkag. Cov khoom tseem ceeb yog braced, thiab tag nrho chav tsev yog huab cua - pov thawj kom muaj kev nyab xeeb kev thauj mus los thiab cia, tuaj txog ntawm - qhov chaw npaj rau kev teeb tsa.
4.2 Shipping
Chav tsev substation transformer yog npaj rau kev thauj dej hiav txwv mus rau Tebchaws Meskas nrog lub zog, huab cua - kaw crating ruaj ntseg rau lub thawv thauj khoom thoob ntiaj teb. Nws tau raug cim kom meej nrog cov ntsiab lus nqa, qhov chaw nruab nrab - ntawm - lub ntiajteb txawj nqus ntsuas, thiab cov ntaub ntawv kev lis kev cai kom muaj kev nyab xeeb, kev thauj mus los ruaj khov, thiab kev tshem tawm tau zoo thaum tuaj txog ntawm US chaw nres nkoj.
05 Site thiab Summary
Ntau tshaj li ib feem, qhov Unit Substation Transformer yog lub siab ntseeg siab ntawm koj cov khoom siv hluav taws xob. Nws embodies ib tug cog lus rau durability, kev nyab xeeb, thiab efficiency, engineered xa uninterrupted hwj chim rau koj cov hauj lwm tseem ceeb tshaj plaws. Xaiv nws ua lub hauv paus ntawm koj qhov project rau kev ua tau zoo uas ua kom ntev.
Tiv tauj peb hnub no los tsim kev daws teeb meem raws li koj qhov kev xav tau tshwj xeeb.

Cim npe nrov: Chav tsev Substation, chaw tsim khoom, chaw muag khoom, nqe, tus nqi
You Might Also Like
50 kVA Transformer Electric Ncej-13.8/0.347 kV|Canad...
2000 kVA Distribution Substation Transformer-44/0.48...
3000 kVA Hluav Taws Xob Substation-44/0.6 kV|Canada ...
3750/4250 kVA Substation Transformer-13.8/0.48 kV|US...
1000/1150 kVA Distribution Transformer Substation-13...
2000/2300kVA Hluav Taws Xob Substation Transformer-1...
Xa kev nug