50 Kva Transformer Ncej Mount-13.8/0.12*0.24 KV|USA 2025

50 Kva Transformer Ncej Mount-13.8/0.12*0.24 KV|USA 2025

Lub Tebchaws xa tuaj: Tebchaws USA 2025
Muaj peev xwm: 50kVA
Lub hwj chim: 13.8-0.12 / 0.24kV
Feature: HV winding: tooj liab, LV winding: Aluminium
Xa kev nug

 

50 kva transformer pole mount

Kev ntseeg tau thiab ua tau zoo 50 kVA ncej-mounted transformer, engineered rau North American tis network nrog kev ua tau zoo tshaj

 

 

01 General

1.1 Project Description

Lub 50 kVA ib qho -theem ncej- mounted transformer muaj 13.8 kV thawj thiab 120/240 V theem nrab. Tsim los rau IEEE C57.12.20 rau overhead faib transformers. Nws haum rau 13.8 kV peb-theem, peb- xaim xaim xaim hauv North America. Cov50kva ncej mount transformernta ONAN ntuj roj txias nrog cov ntxhia roj rwb thaiv tsev. Nrog rau kev tsom mus rau kev ua tau zoo thiab qhov chaw optimization, Scotech siv ob qho tib si txhuas thiab tooj liab winding. Lub polarity yog rho tawm, thiab pawg vector yog Ii0, kom ntseeg tau tias cov theem ua tiav hauv lub network faib. Kev ua haujlwm tseem ceeb suav nrog tsis muaj-load poob ntawm 0.14 kW, load poob ntawm 0.527 kW, tag nrho poob ntawm 0.667 kW, thiab tag nrho -load efficiency ntawm 98.97%. Impedance yog 2.86%, nyob rau hauv ib txwm faib transformer ntau yam. Tsis tas li ntawd, lub tshuab hloov pauv tau nruab nrog tsis muaj -load kais hloov pauv (NLTC) uas tso cai rau siab - qhov hloov pauv hloov hluav taws xob los ntawm 14, 400 V txog 12, 540 V kom haum rau qhov hloov pauv voltage hauv lub network.

 

1.2 Technical Specification

50kVA ib theem ncej mounted transformerspecification thiab cov ntaub ntawv

Xa rau
Teb chaws USA
Xyoo
2025
Hom
Ncej Mounted Transformer
Txuj
IEEE C57.12.20
Rated zog
50 kVA
Ntau zaus
60 tzs
Theem
Ib leeg
Hom cua txias
ONAN
Ua kua insulating
Mineral Roj
Thawj Voltage
13.8 kV 2
Secondary Voltage
0.12 / 0.24 kV
Vector Group
Ib 0
Polarity
Kev rho tawm
Cov khoom siv winding
HV: Tooj, LV: Aluminium
Kev ua tau zoo
98.97 %
Impedance
2.86%
Coj mus rhaub Changer
NLTC
Tapping Range
14400,13800,13200,12870,12540
Tsis Load Loss
0.14 kWm
Ntawm Load Loss
0.527 kWm
Khoom siv
Standard Configuration

 

1.3 Cov duab kos

50kVA ib theem ncoo mounted transformer daim duab kos duab thiab loj.

50 kva transformer pole mount drawing 50 kva transformer pole mount nameplate

 

 

02 Kev tsim khoom

2.1 Core

Siv cov nplej- taw qhia silicon steel, lub qhov txhab lub qhov txhab muab kev ua haujlwm zoo sib nqus los ntawm kev txo qis kev cuam tshuam hauv txoj kev flux. Tus tsim zam kev sib nqus saturation, ua kom ruaj khov ua haujlwm raws li kev hloov pauv ntawm kev thauj khoom. Piv nrog rau cov txheej txheem txheej txheem ib txwm muaj, cov qauv qhov txhab txo qis tsis muaj-load poob thiab tsis muaj-load tam sim no, thaum tseem txo qis kev vibration thiab suab nrov. Cov txiaj ntsig zoo no ua rau lub qhov txhab muaj zog heev - ua haujlwm tau zoo thiab txhim khu kev qha hauv kev faib khoom.

 

2.2 Cua txias

Lub high voltage winding txais concentric tsim nrog electrolytic tooj liab hlau ntawm 99.9% purity, enamel insulated, kom ntseeg tau conductivity tsis tsawg tshaj li 100% IACS. Thermal rwb thaiv tsev withstands mus txog 105 degree. LV winding siv aluminium ntawv ci, uas txo qis eddy tam sim no poob, ua kom muaj zog txhua yam kev ncaj ncees, thiab ua tau raws li cov khoom siv hluav taws xob.

50 kva transformer pole mount winding

 

2.3 Tank

50 kva transformer pole mount oil tank

Lub tank transformer yog lub kaw lus cylindrical qauv ua los ntawm cov hlau me me nrog txheej txheej hauv RAL7035 xim. Nws yog tsim los tsis muaj kev soj ntsuam los yog tu lub qhov kom ntseeg tau tias muaj kev ncaj ncees. Ib lub hau domed tshem tau yog siv rau kev nkag. Mounting brackets yog ua los ntawm cov hlau nrog qhov tsawg kawg nkaus thickness ntawm 3.4 hli. Qhov kawg yog khoov thiab welded rau lub tank lub cev. Qhov no ua rau cov qauv muaj zog thiab ruaj khov.

 

2.4 Kev sib dhos zaum kawg

1. Winding Assembly:Xaub lub HV / LV windings mus rau hauv cov tub ntxhais laminated, kom ntseeg tau tias kev sib raug zoo thiab kev ruaj ntseg ntawm rwb thaiv tsev.
2. Kev sib txuas hluav taws xob:Txuas winding coj mus rau kais hloov pauv, bushings, thiab lwm yam khoom, ces ruaj ntseg thiab insulate cov pob qij txha.
3. Core-Coil ziab:Muab cov khoom sib dhos ua ke (core + windings) rau hauv qhov cub kom qhuav rau lub tshuab nqus tsev kom tshem tawm cov dej noo.
4. Tank Installation:Nqa cov khoom ua haujlwm qhuav rau hauv lub tank, tso nws kom ruaj ntseg, thiab xyuas kom muaj kev rwb thaiv tsev los ntawm cov phab ntsa tank.
5. Accessory Mounting:Txhim kho bushings, siab nyem valve thiab lwm yam khoom siv, tom qab ntawd xyuas seb cov dej xau.
6. Roj Sau & Teeb:Lub tshuab nqus tsev- sau nrog cov roj insulating, degas, thiab tso cai rau kev daws teeb meem ua ntej kuaj cov roj qib thiab lub zog dielectric.

50 kva transformer pole mount active part

 

 

03 Kev Xeem

Test Standard thiab Routine Test

IEEE C57.12.20-2017: IEEE Standard for Overhead-Type Distribution Transformers 500 kVA thiab Me; High Voltage, 34500 V thiab hauv qab; Tsawg Voltage,7970/13 800YV thiab hauv qab
IEEE C57.12.90-2021: IEEE Standard Test Code rau Liquid-Immersed Distribution, Fais Fab, thiab regulating Transformers
CSA C802.1-13 (R2022): Yam tsawg kawg nkaus efficiency qhov tseem ceeb rau cov kua-filled tis transformers
 

1. Kev ntsuas ntsuas
2. Kev ntsuas qhov sib piv
3. Polarity Test
4. Tsis muaj Load Losses thiab Tsis Muaj Load Tam Sim No
5. Load Losses thiab impedance Voltage
6. Applied Voltage Test
7. Induced Voltage Withstand Test
8. Rwb thaiv tsev ntsuas ntsuas
9. Kev kuaj cov dej ntws nrog lub siab rau cov kua Immersed Transformers
10. Roj Dielectric Test
 

Cov qhabnias xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Txais

Tus nqi

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

/

/

/

Hla

2

Kev ntsuas ntsuas

/

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Ii0

-0.02

Hla

3

Kev ntsuam xyuas polarity

/

Kev rho tawm

Kev rho tawm

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

%

kW

I0 :: muab ntsuas tus nqi

P0: muab ntsuas tus nqi

qhov kam rau tsis muaj load poob yog +10%

0.22

0.107

Hla

5

Load poob, impedance voltage, tag nrho poob thiab efficiency

/

kW

kW

t:85 ua

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

Qhov kam rau ua impedance yog ± 10%

qhov kam rau tag nrho load poob yog +6%

2.93

0.557

0.664

99.07

Hla

6

Applied Voltage Test

/

HV: 30 KV 60s

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

/

Kev siv hluav taws xob (KV):

2 ua

Duration(s): 48

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

8

Rwb thaiv tsev Resistance Measurement

GΩ

HV-LV to Av

LV-HV to Av

HV&LV to Av

96.9

49.1

55.8

Hla

9

Kev Xeem Leakage

/

Kev siv siab: 20kPA

Duration: 12h

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 45

59.1

Hla

 

 

04 Packing thiab Shipping

50 kVA single-phase pole-mounted transformer packing

 
 

05 Site thiab Summary

Lub 50 kVA ib qho -theem ncej- mounted transformer ua haujlwm rau North American overhead distribution networks. Nws siv ONAN roj txias thiab khiav tau zoo. Cov tub ntxhais yog ua los ntawm qhov txhab silicon steel. Cov windings siv zoo tooj liab thiab txhuas. Qhov no muab kev ruaj ntseg voltage, tsawg poob, thiab ua haujlwm ntsiag to. Nws tsis muaj -load kais hloov pauv rau kev hloov pauv voltage. Lub tank muaj zog thiab kaw. Nws ua haujlwm zoo rau tsev thiab kev lag luam. Scotech ua rau txhua qhov hloov pauv kom zoo. Txhua chav ua tau raws li cov qauv thoob ntiaj teb.

50 kva transformer pole mount-back-view

 