75 kVA Utility Ncej Transformer-34.5/0.12*0.24 kV|Canada 2024
Peev xwm: 75kVA
Qhov hluav taws xob: 34.5 / 0.24kV
Feature: nrog c/w tsiaj zov

"Crafting excellence, xa lub neej yav tom ntej-Ib zaug-theem ncej-mounted transformers, illuminating txhua watt ntawm lub ntiaj teb no."
01 General
1.1 Project Background
75 kVA ib theem ncej mounted transformer tau xa mus rau Canada nyob rau hauv 2024. Lub zog ntsuas ntawm lub transformer yog 75 kVA nrog ONAN txias. Thawj qhov hluav taws xob yog 34.5kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov nruab nrab voltage yog 0.12 / 0.24kV, lawv tsim ib pawg vector ntawm Ii6.
Ib tug ncej mounted transformer yog ib hom fais fab transformer mounted rau ib tug xov tooj ncej, feem ntau nyob rau hauv txoj kev, txoj kev loj, los yog nyob rau hauv cov cheeb tsam. Cov transformers no ua lub luag haujlwm tseem ceeb hauv kev faib hluav taws xob los ntawm cov kab xa mus rau cov neeg siv, thiab yog cov khoom siv nruab nrab uas tswj cov qib voltage thiab xyuas kom muaj kev nyab xeeb thiab siv hluav taws xob zoo. Ib qho -theem ncej mounted transformer yog ib qho khoom siv hluav taws xob siv los xa hluav taws xob hluav taws xob ntawm ob lossis ntau lub circuits los ntawm electromagnetic induction. Nws feem ntau muaj ob lub xaim coils (hu ua thawj thiab theem nrab winding) qhov txhab nyob ib ncig ntawm cov tub ntxhais sib nqus sib nqus. Thaum alternating tam sim no (AC) ntws los ntawm thawj winding, nws tsim ib tug hloov magnetic teb nyob rau hauv lub tub ntxhais, uas nyob rau hauv lem induces ib tug voltage nyob rau hauv lub thib ob winding. Qhov hluav taws xob no tuaj yeem siab dua lossis qis dua qhov tseem ceeb ntawm qhov hluav taws xob, nyob ntawm qhov sib piv ntawm qhov hloov pauv ntawm cov thawj thiab theem nrab windings.
1.2 Technical Specification
75kVA ib theem ncej mounted transformer specification thiab cov ntaub ntawv ntawv
|
Xa rau
Canada
|
|
Xyoo
2024
|
|
Hom
Ib theem ncej mounted transformer
|
|
Txuj
IEEE C57.12.00 Nws
|
|
Rated zog
75kVA ua
|
|
Ntau zaus
60 tzs
|
|
Theem
Ib leeg
|
|
Hom cua txias
ONAN
|
|
Thawj Voltage
3 4,5kv
|
|
Secondary Voltage
0.24 / 0.12 kV
|
|
Cov khoom siv winding
Aluminium
|
|
Polarity
Ntxiv
|
|
Impedance
1.5%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
±2*2.5%
|
|
Tsis Load Loss
0.205 kWm
|
|
Ntawm Load Loss
0.870 kWm
|
|
Khoom siv
Standard Configuration
|
|
Lus hais
N/A
|
1.3 Cov duab kos
75kVA ib theem ncej mounted transformer qhov ntev thiab hnyav cov ntsiab lus
![]() |
![]() |
02 Kev tsim khoom
2.1 Core
Cov tub ntxhais yog ua los ntawm cov khoom txias txias-rolled grain-cov ntawv qhia txog silicon steel, feem ntau txhim kho nrog cov kev kho mob tshwj xeeb kom txo cov tub ntxhais poob. Cov tub ntxhais yog tsim los siv cov txheej txheem nruam winding, tsim ib qho seamless, kaw sib nqus sib nqus. Qhov kev tsim no txo cov hlau nplaum tiv thaiv los ntawm cov pob qij txha. Lub qhov txhab ntawm lub qhov txhab ua kom lub cev tsis sib xws thiab tsis tu ncua kev sib nqus, txo hysteresis thiab eddy tam sim no poob, yog li txhim kho kev ua haujlwm. Lub qhov txhab lub qhov txhab feem ntau muaj cov duab tsis tu ncua, uas txo qhov ntim thiab qhov hnyav, ua tau raws li qhov kev thov rau lub teeb yuag thiab yooj yim installation.

2.2 Cua txias

Precisely tsim lem piv ua kom lub voltage thiab tam sim no kev sib raug zoo ntawm cov thawj thiab theem nrab windings raws li specifications. Txo txo qhov sib nqus sib nqus los ntawm kev ua kom zoo ntawm tus neeg xyuas pib hla- ntu thiab kev npaj, ua kom muaj zog hloov pauv tau zoo. High- lub zog clamping cov qauv txhim khu kev tiv thaiv luv luv - Circuit Court quab yuam, tiv thaiv txhua yam deformation los ntawm electromagnetic stress. Thaum tshav kub kub generated nyob rau hauv lub winding yog zoo dissipated los ntawm inter-txheej txheej cua txias raws los yog ncig ntawm insulating roj, tiv thaiv kub kub nce.
2.3 Tank
Lub tank feem ntau yog ua los ntawm siab- zoo stainless hlau, nrog rau cov neeg kho tshuab siab zog thiab corrosion kuj, kom ntseeg tau ntev - lub sij hawm ruaj khov ntawm lub tank nyob rau hauv ib puag ncig hnyav. Sab nrauv yog coated nrog anti- xeb thiab tiv thaiv- xim xim, feem ntau nyob rau hauv lub teeb grey lossis lwm yam kev ua kom zoo ib puag ncig, tiv thaiv xeb thiab txuas ntxiv lub tank lub neej kev pab cuam. Advanced sealing welding cov txheej txheem kom ntseeg tau tias muaj zog, xau-cov ntaub ntawv pov thawj, tuav ruaj ntseg cia ntawm cov roj transformer. Advanced sealing welding cov txheej txheem kom ntseeg tau tias muaj zog, xau-cov ntaub ntawv pov thawj, tswj kev ruaj ntseg ntawm cov roj hloov pauv.

2.4 Lub Rooj Sib Tham Kawg

(1) Coil Winding thiab sib dhos:
- Cua lub hauv paus thiab theem nrab coils siv cov khoom siv xws li tooj liab lossis txhuas hlau.
- Txhim kho lub qhov txhab coils rau hauv cov tub ntxhais, kom ntseeg tau tias qhov chaw raug thiab hluav taws xob sib txuas ntawm cov coils.
(2) Kev kho rwb thaiv tsev:
- Muab cov ntaub ntawv insulating ntawm cov coils thiab lwm qhov chaw nyob kom tsis txhob muaj hluav taws xob poob siab thiab luv luv Circuit Court.
(3) Tank Assembly:
- Muab cov tub ntxhais sib dhos thiab coils rau hauv lub tank transformer.
- Sau lub tank nrog cov roj transformer kom txias thiab rwb thaiv tsev lub hom phiaj.
(4) Txhim kho cov khoom siv sab nraud:
- Txhim kho cov khoom siv sab nraud xws li cov ntsuas roj ntsuas, ntsuas qhov ntsuas kub, thiab lub siab nyem li qub txhawm rau saib xyuas kev ua haujlwm ntawm lub tshuab hloov pauv.
- Nruab qhov txuas txuas thiab lwm yam khoom siv hluav taws xob sib txuas tsim nyog.
03 Kev Xeem
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Txais Tus nqi |
Ntsuas Tus Nqi |
Xaus |
|
1 |
Kev ntsuas ntsuas |
/ |
/ |
/ |
Hla |
|
2 |
Kev ntsuas ntsuas |
/ |
Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5% Cov cim kev sib txuas: Ii6 |
0.00 |
Hla |
|
3 |
Kev ntsuam xyuas polarity |
/ |
Ntxiv |
Ntxiv |
Hla |
|
4 |
Tsis muaj -load poob thiab excitation tam sim no |
% |
I0 : muab ntsuas tus nqi (100%) |
0.30 |
Hla |
|
kW |
P0: muab ntsuas tus nqi (100%) |
0.186 |
|||
|
% |
I0 : muab ntsuas tus nqi (105%) |
1.15 |
|||
|
kW |
P0: muab ntsuas tus nqi (105%) |
0.268 |
|||
|
/ |
Kev kam rau ua tsis muaj load poob yog ± 15% |
/ |
|||
|
5 |
Load poob, impedance voltage, tag nrho poob thiab efficiency |
/ |
t:85 ua Kev kam rau siab impedance yog ± 7.5% Kev kam rau tag nrho load poob yog ± 8% |
/ |
Hla |
|
% |
Z%: ntsuas tus nqi |
2.55 |
|||
|
kW |
Pk: ntsuas tus nqi |
0.841 |
|||
|
kW |
Pt: ntsuas tus nqi |
1.027 |
|||
|
% |
Kev ua haujlwm tsis tsawg dua 98.94% |
99.01 |
|||
|
6 |
Applied Voltage Test |
/ |
HV: 50 KV 60S LV: 10kV 60s |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
7 |
Induced Voltage Withstand Test |
/ |
Kev siv hluav taws xob (KV): 69 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
Duration(s): 60 |
|||||
|
Zaus (HZ): 120 |
|||||
|
8 |
Rwb thaiv tsev Resistance Measurement |
GΩ |
HV-LV to Av: LV-HV to Av: HV & LV rau hauv av: |
102.8 79.5 77.3 |
Hla |
|
9 |
Kev Xeem Leakage |
/ |
Kev siv siab: 20kPA |
Tsis muaj leakage thiab tsis muaj Kev puas tsuaj |
Hla |
|
Duration: 12h |
|||||
|
10 |
Roj Xeem |
kV ua |
Dielectric zog |
55.4 |
Hla |
|
mg/kg |
Cov ntsiab lus noo noo |
9.8 |
|||
|
% |
Dissipation Factor |
0.00257 |
|||
|
mg/kg |
Furan Analysis |
0.03 |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Packing thiab Shipping


05 Site thiab Summary
Tib -theem ncej mounted transformer yog ib yam ntawm cov khoom tseem ceeb dav siv nyob rau hauv lub hwj chim faib system. Nws yog haum rau nws cov qauv compact, yooj yim txij nkawm thiab tus nqi siab efficiency. Vim tias nws lub luag haujlwm tseem ceeb hauv lub zog hluav taws xob, nws yog ib qho tseem ceeb heev uas yuav tsum ua kom lub zog ib theem kem transformer nyob rau hauv kev ua haujlwm zoo kom ntseeg tau tias kev ruaj ntseg thiab kev ruaj ntseg ntawm cov khoom siv hluav taws xob. Peb cov kws tshaj lij ua kom ntseeg tau, muaj txiaj ntsig kev faib hluav taws xob daws teeb meem uas ua tau raws li qhov tshwj xeeb ntawm txhua qhov haujlwm.