50 kVA Transformer Ntawm Fais Fab Kab-7.97 / 0.277 kV|Canada 2024

50 kVA Transformer Ntawm Fais Fab Kab-7.97 / 0.277 kV|Canada 2024

Lub Tebchaws: Canada 2024
Peev xwm: 50kVA
Qhov hluav taws xob: 7.97 / 13.8Y-0.277kV
Feature: Amorphous core
Xa kev nug

 

 

50 kva transformer on power line-front-view

Ua tau zoo, txhim khu kev qha, thiab eco-tus phooj ywg-powering koj lub network faib nrog Scotech's 50 kVA ncej-mounted transformer

 

01 General

1.1 Project Description

Qhov no 50 kVA ib qho -theem transformer ntawm lub hwj chim kab yogtsim los ntawm Scotechthiab exported rau Canada. Lub transformer ua tau raws li IEEE C57.12.20 cov qauv, ua kom ntseeg tau kev ua tau zoo rau cov chaw nyob thiab lub teeb ua lag luam.

Qhov kev txiav txim no suav nrog 20 units ntawm ib qho -theem ncej-mounted transformers, ntawm cov 5 units yog ntawm no 50 kVA qauv. Txhua lub tshuab hloov pauv yog tsim los rau thawj qhov hluav taws xob ntawm 7.97 / 13.8Y kV thiab qhov hluav taws xob thib ob ntawm 277 V, muaj ob lub siab -voltage bushings thiab ob qhov qis{10}}voltage bushings. Lub transformer yog nruab nrog tsis muaj -load tap changer (NLTC) nrog ± 2 × 2.5%.

Lub 50 kVA transformer ntawm lub hwj chim kab siv lub amorphous alloy core, txo tsis muaj -load poob rau 0.043 kW thiab load poob rau 0.5 kW. Nws yog lub zog-txuag thiab tus phooj ywg ib puag ncig, txo cov nqi hluav taws xob.

Lub transformer hnyav 327 kg, nrog rau 81 kg ntawm insulating roj. Cov roj pab ua kom txias thiab rwb thaiv tsev. Nws loj yog 645 × 715 × 1115 mm. Tus qauv me me thiab sib npaug sib haum zoo rau ntawm tus ncej- txuas fais fab. Tus thawj coj surge arrester tso cai yooj yim kev koom ua ke ntawm cov cuab yeej tiv thaiv, txhim kho kev ntseeg tau thiab kev nyab xeeb.

Tsim nrog aluminium windings, additive polarity, thiab ONAN ntuj cua txias, qhov transformer ntawm lub hwj chim kab yog compact, npaum, thiab txhim khu kev qha. Aluminium kev tsim kho thiab kev tsim qauv ntse muab cov kev daws teeb meem hloov pauv rau niaj hnub siv hluav taws xob faib hluav taws xob, ua kom lub zog ua haujlwm tau zoo thiab ua haujlwm tau zoo.

 

 

 

1.2 Technical Specification

50kVA transformer ntawm lub hwj chim kab specification thiab cov ntaub ntawv ntawv

Xa rau
Canada
Xyoo
2024
Hom
Ib theem ncej mounted transformer
Txuj
IEEE C57.12.20
Rated zog
50 kVA
Ntau zaus
60 tzs
Polarity
Ntxiv
Vector pawg
Ib 6
Thawj Voltage
7.97/13.8Y kV
Secondary Voltage
277 V
Cov khoom siv winding
Aluminium
Impedance
2.1%
Txoj kev txias
ONAN
Coj mus rhaub Changer
NLTC
Tapping Range
±2X2.5%
Tsis Load Loss
0.043 kWm
Ntawm Load Loss
0.5 kW tsi
Khoom siv
Surge arrester tus thawj coj

 

 

1.3 Cov duab kos

50kVA transformer ntawm lub hwj chim kab qhov ntev thiab cov ntsiab lus hnyav

50 kva transformer on power line-engineering-drawing 50 kva transformer on power line-nameplate

 

 

02 Kev tsim khoom

2.1 Core

Lub 50kVA transformer ntawm lub hwj chim kab siv lub amorphous hlau core, ib qho isotropic mos magnetic khoom nrog siab resistivity, zoo heev txo eddy tam sim no poob. Piv nrog rau txias- dov silicon steel, nws txo cov tub ntxhais poob los ntawm 70-80%, ua tiav qhov tsis muaj-load poob ntawm 0.043 kW thiab load poob ntawm 0.5 kW. Nws nyias 0.03 hli ribbons yooj yim tsim, txhim kho kev ua haujlwm, thiab muab lub zog -txuag, eco- cov tshuaj zoo.

50 kva transformer on power line-amorphous-core

 

2.2 Cua txias

50 kVA transformer on power line-foil-wound low-voltage coils

Optimized coil design nta ntawv ci-mob tsawg-voltage coils thiab xaim-mob siab-voltage coils. Cov neeg siv khoom tuaj yeem xaiv aluminium rau LV coil, txo tus nqi thiab qhov hnyav thaum tswj kev ntseeg tau thiab kev ua neej zoo ib yam li tooj liab. Polarity yog additive thiab transformer ua raws li vector pawg Ii6, muab kev sib raug zoo theem thiab txhim khu kev qha.

 

2.3 Tank

Tsim los rau ncej mounting, lub tank transformer no tiav nyob rau hauv lub teeb grey thiab tsim los ntawm siab -zoo low- carbon steel siv cov txheej txheem kos duab los tsim ib lub cylindrical qauv. Lub tank lub cev siv cov cuab yeej sib khi, nrog lub hau thiab hauv qab tsim los ntawm cov ntawv hlau stamping, txo qhov hnyav thaum ua kom muaj zog ntawm cov qauv.

50 kVA transformer on power line cylindrical structure tank

 

2.4 Kev sib dhos zaum kawg

50 kVA transformer on power line active part fastening

Active Part Cleaning & Fastening

1. Kev ntxuav

Tshem tawm tag nrho cov hlau thiab pom tsis yog- cov khib nyiab hlau.

2. Ceev ceev

Tighten yoke thiab base bolts.

Kev ruaj ntseg khi-band, xauv txiv ntseej, hlau clamps, kev txhawb nqa, brackets, thiab sab nrauv bolts; xyuas kom rwb thaiv tsev qhov chaw ua kom zoo.

Siv axial siab symmetrically ntawm HV / LV sab, tsawg kawg 2 lub voj voog.

Tighten cov xov hlau thiab muaj peev xwm txuas bolts nrog torque wrench.

3. Kev tshuaj xyuas

Tshawb xyuas cov rwb thaiv tsev thiab ua rau kev puas tsuaj lossis av.

Xyuas kom tsis muaj qhov ploj lawm.

Suav tag nrho cov cuab yeej siv.

 

 

03 Kev Xeem

Routine Test

1. Kev ntsuas ntsuas

2. Kev ntsuas qhov sib piv

3. Theem -kev sib txheeb xeem

4. Tsis muaj Load Losses thiab Tsis Muaj Load Tam Sim No

5. Load Losses, Impedance Voltage thiab Efficiency

6. Applied Voltage Test

7. Induced Voltage Withstand Test

8. Kev ntsuas dej nrog lub siab rau cov kua Immersed Transformers

9. Kev ntsuas kev tiv thaiv rwb thaiv tsev

10. Roj Dielectric Test

11. Kev Ntsuas Hluav Taws Xob

 

50 kva transformer on power line-routine-test
50 kva transformer on power line-factory-test

 

Cov qhabnias xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Kev txais txiaj ntsig

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

/

/

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Ii6

-0.17

Hla

3

theem- kev xeem sib txheeb

/

Ntxiv

Ntxiv

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

%

kW

t:85 ua

I0 :: muab ntsuas tus nqi

P0: muab ntsuas tus nqi

qhov kam rau tsis muaj load poob yog +10%

1.20(100%)

2.35(105%)

0.043(100%)

0.056(105%)

Hla

5

Load poob impedance voltage thiab efficiency

%

kW

kW

t:85 ua

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

Qhov kam rau ua impedance yog ± 10%

qhov kam rau tag nrho load poob yog +6%

2.28

0.481

0.526

99.39

Hla

6

Applied Voltage Test

kV ua

HV: 34kV 60s

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

kV ua

Kev siv hluav taws xob (KV):

15.94

Duration(s): 40

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

8

Kev Xeem Leakage

kPa ua

Kev siv siab: 20kPA

Duration: 12h

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

9

Rwb thaiv tsev Resistance Measurement

HV & LV rau hauv av:

51.7

/

HV-LV to Av

24.5

LV-HV to Av

31.5

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 45

52.05

Hla

11

xob laim impulse test

kV ua

puv nthwv dej, Ib nrab nthwv dej

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

 

 

04 Packing thiab Shipping

50 kVA transformer on power line-wooden crate packaging
50 kva transformer on power line-export-packing

 

05 Site thiab Summary

50 kVA uaib leeg-theem ncej-mounted transformer xa mus rau Canada hauv 2024 qhia Scotech tsom mus rau qhov zoo, kev ua tau zoo, thiab kev tsim kho tshiab. Nws muaj amorphous hlau core, aluminium windings, thiab ONAN ntuj txias. Qhov kev tsim no txo ​​qis kev poob, ua haujlwm ruaj khov, thiab txuag hluav taws xob rau cov chaw nyob thiab lub teeb lag luam. Nws cov compact, ncej-mounted tsim, robust tank, thiab integrated surge arrester tus thawj saib xyuas kev nyab xeeb, durability, thiab yooj yim ntawm installation.

Scotech ua rau siab -kev ua tau zoo, eco- hloov pauv tus phooj ywg rau cov tshuab hluav taws xob niaj hnub. Qhov project no qhia peb cov txuj ci hauv engineering, kev tsim khoom, thiab kev tswj kom zoo. Peb muab cov khoom txhim khu kev qha uas txuag hluav taws xob thiab txhim kho kev ua haujlwm ntawm daim phiaj.

50 kva transformer on power line-left-45-degree-view

 

 

Cim npe nrov: transformer ntawm fais fab kab, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug