250 KVA Me Pad Mounted Transformer-13.8/0.22 KV|Guyane xyoo 2025

250 KVA Me Pad Mounted Transformer-13.8/0.22 KV|Guyane xyoo 2025

Lub teb chaws: Guyana 2024
Muaj peev xwm: 250 kVA
Lub hwj chim: 13.8-0.22y / 0.127 kV
Feature: nrog OCTC
Xa kev nug

 

image001

Pad Mounted Transformer: Fais fab kev nce qib, nyab xeeb thiab ntsiag to.

 

 

01 General

1.1 Project Description

250 kVA peb theem ncoo mounted transformer tau xa mus rau Guyana xyoo 2024. Lub zog ntsuas ntawm lub transformer yog 250 kVA nrog ONAN txias. Qhov siab voltage yog 13.8 kV nrog ± 2 * 2.5% tapping ntau (NLTC), qhov tsawg voltage yog 0.22y / 0.127 kV, lawv tsim ib pawg vector ntawm Dyn11.

CovPad-Mounted Transformeryog lub hauv paus ntawm niaj hnub, muaj kev nyab xeeb, thiab txhim khu kev qha hluav taws xob hauv av. Tsim los rau kev ua tau zoo thiab kev nyab xeeb rau pej xeem, qhov compact, hauv av- theem chav tsev yog tsim los nqis siab - hluav taws xob hluav taws xob mus rau qib uas siv tau los ntawm cov neeg nyob ib puag ncig, cov chaw lag luam, thiab cov chaw tsim khoom. Tsis zoo li ib txwm ncej-mounted transformers, nws tag nrho cov nyob rau hauv, tamper-resistant steel vaj tse ruaj ntseg muaj tag nrho cov nyob Cheebtsam, ua rau nws yog ib qho kev xaiv zoo tagnrho rau tej thaj chaw uas pej xeem muaj kev txhawj xeeb. Cov qauv tsim muaj zog tiv thaiv ib puag ncig cov ntsiab lus, kev ua phem, thiab kev sib cuag tsis sib haum, ua kom cov kev pabcuam tsis cuam tshuam thiab txhim kho kev nyab xeeb rau zej zog.

Ib qho txiaj ntsig tseem ceeb ntawm Pad-Mounted Transformer yog nws cov hneev taw me me thiab zoo nkauj yooj yim. Nws yog discreetly ntsia rau ntawm lub pob zeb hauv av theem, yooj yim sib xyaw rau hauv nws ib puag ncig lossis raug tshuaj xyuas nrog kev tsim kho kom zoo nkauj. Qhov kev tsim no tsis tsuas yog khaws cia qhov pom kev pom ntawm thaj chaw tab sis kuj tso cai rau cov neeg siv hluav taws xob muaj kev nyab xeeb thiab yooj yim rau kev saib xyuas thiab tswj kev thauj khoom.

Los ntawm lub zog ntawm lub nroog ntse mus rau kev sib koom ua ke cov khoom siv hluav taws xob tauj dua tshiab, Pad-Mounted Transformer sawv ua tus ntsiag to, txhim khu kev qha, thiab muaj txiaj ntsig tus neeg saib xyuas ntawm daim phiaj hluav taws xob, xa hluav taws xob rau qhov xav tau- nyab xeeb thiab seamlessly.

 

 

 

1.2 Technical Specification

250 kVA ncoo mounted transformer specifications hom thiab cov ntaub ntawv ntawv

Xa rau
Guyane
Xyoo
2024
Hom
Pad mounted transformer
Txuj
IEEE Std C57.12.34
Rated zog
250 kVA ua
Ntau zaus
60 tzs
Theem
3
Pub
Loop
Pem hauv ntej
Tuag
Hom cua txias
ONAN
Thawj Voltage
13.8 kV 2
Secondary Voltage
0.22y / 0.127 kV
Cov khoom siv winding
Tooj
Vector Group
Dyn 11
Impedance
4%
Kev ua tau zoo
98.94%
Coj mus rhaub Changer
NLTC
Tapping Range
±2*2.5%
Tsis Load Loss
0.535 kWm
Ntawm Load Loss
3.56 kWm

 

1.3 Cov duab kos

250 kVA ncoo mounted transformer daim duab kos duab thiab loj.

image003 image005

 

 

02 Kev tsim khoom

2.1 Core

image007

Lub ncoo no -mounted transformer nta lub compact peb-theem, peb-limb core ua los ntawm laminated silicon steel. Tus qauv tsim muab txoj hauv kev zoo sib nqus rau lub ntsiab flux thaum tso cai xoom-flux rov qab los ntawm huab cua, ua rau muaj qhov muaj zog thiab qhov chaw- txuag chav.

 

2.2 Cua txias

Cov windings siv tooj liab rau ob qhov qis-voltage thiab siab-voltage seem. Qhov qis-voltage winding yog ntawm cov ntawv ci tsim, muab cov axial luv luv- lub zog hluav taws xob thiab ua kom muaj cua sov zoo. Conversely, lub siab -voltage winding ntiav ib txheej- qhov txhab tsim nrog puag ncig los yog duab plaub hlau nplaum, muab qhov tsim nyog voltage endurance thiab yooj nyob rau hauv lem kev npaj. Qhov kev sib xyaw ua ke ntawm cov ntawv ci thiab txheej - cov txheej txheem kev kho mob ua rau muaj kev sib koom ua ke, kev cog lus, thiab txhim khu kev qha coil.

image009

 

2.3 Tank

image011

Lub tank transformer yog tsim los ntawm cov hlau me me, muab lub zog thiab tus nqi -cov ntaub ntawv zoo. Nws yog hermetically kaw kom ntseeg tau tias cov roj insulating sab hauv tseem cais tawm ntawm cov dej noo thiab cov kab mob. Cov txheej txheej sab nrauv uas siv tau los tiv thaiv ib puag ncig hnyav, ua rau nws haum rau ntev - kev pabcuam sab nraum zoov.

 

2.4 Lub Rooj Sib Tham Kawg

Kev sib dhos zaum kawg ua ke nrog cov tub ntxhais - thiab - coil unit rau hauv lub tank me me, uas tom qab ntawd tau ntim cov roj purified dielectric. Tag nrho cov kev sib txuas sab hauv tau ruaj ntseg, thiab cov khoom siv sab nraud xws li cov khoom sib txuas hauv nruab nrab, kev txiav tawm thawj zaug (xws li lub luj tshib lossis bushings), cov cuab yeej siv siab, thiab cov hlua hauv av tau teeb tsa. Lub tank yog hermetically kaw, thiab tag nrho lub tsev yuav raug kuaj nruj kom ntseeg tau tias kev ua haujlwm zoo, kev nyab xeeb, thiab kev ntseeg tau ua ntej tau txais kev pom zoo rau kev pabcuam.

image013

 

 

03 Kev Xeem

Cov kev ntsuam xyuas suav nrog cov khoom siv niaj hnub: ntsuas qhov ntsuas qhov ntsuas qhov ntsuas (max tsis sib npaug li 1.57%), qhov ntsuas qhov sib piv (kev sib txawv -0.07% rau -0.05%), kev ntsuas theem (paub Dyn11), tsis muaj kev poob qis thiab ntsuas tam sim no (0.450kW, 0.76%), load thiab voltage 0.54kW (3. poob, 3.93% impedance, 99.04% efficiency), thov voltage test (34kV rau HV, 10kV rau LV, 60s txhua yam uas tsis muaj voltage vau), induced voltage withstand test (27.6kV, 150Hz, 48s, tsis muaj voltage vau), to test (20kPa rau 12h), rwb thaiv tsev roj thiab hluav taws xob ntsuas. (55.13 kV). Txhua qhov ntsuas ntsuas tau raws li qhov yuav tsum tau ua, ua rau "Pass" xaus. Daim ntawv tshaj tawm tsuas yog siv tau nrog kos npe ntawm tus neeg kuaj, tus neeg pov thawj, thiab tus neeg pom zoo; Kev tawm tsam yuav tsum xa tuaj hauv 7 hnub tom qab tau txais, thiab tsis pub luam tawm yam tsis muaj Scotech daim ntawv tso cai.

Tsis muaj.

Cov khoom kuaj

Chav tsev

Txais

Tus nqi

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

Kev tiv thaiv siab tshaj plaws tsis sib npaug tsawg dua lossis sib npaug li 5%

1.57

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

Cov cim kev sib txuas: Dyn11

-0.07%-0.05%

Hla

3

theem- kev xeem sib txheeb

/

Dyn 1

Dyn 1

Hla

4

Tsis muaj -load poob thiab excitation tam sim no

/

I0 :: muab ntsuas tus nqi

0.76%

Hla

P0: muab ntsuas tus nqi (t: 20 degree)

0.450 kWm

qhov kam rau tsis muaj load poob yog +10%

/

5

Load poob impedance voltage thiab efficiency

/

t:85 ua

Qhov kam rau ua impedance yog ± 7.5%

qhov kam rau tag nrho load poob yog +6%

/

Hla

Z%: ntsuas tus nqi

3.93%

Pk: ntsuas tus nqi

3, 354 kWm

Pt: ntsuas tus nqi

3, 804 kWm

Kev ua haujlwm tsis tsawg dua 98.94%

99.04%

6

Applied Voltage Test

kV ua

HV: 34kV 60s

LV: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

kV ua

Kev siv hluav taws xob (KV): 2Ur

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

Induced voltage (KV): 27.6

Duration(s): 48

Zaus (HZ): 150

8

Kev Xeem Leakage

kPa ua

Kev siv siab: 20kPA

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

Duration: 12h

9

Rwb thaiv tsev Resistance Measurement

GΩ

HV-LV to Av:

46.0

/

LV-HV to Av:

109.6

HV & LV rau hauv av:

42.6

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 45

55.13

Hla

 

image015
image017

 

 

04 Packing thiab Shipping

4.1 Ntim

image019

Muab ib lub hnab ntawv ci rau ntawm nws lub tais kom npog lub tshuab hloov pauv, ntxiv cov desiccant, tawm qhov qhib rau lub tshuab nqus tsev, ces muab lub hnab ntim. Tom ntej no, haum lub kaum tiv thaiv (ua npuas ncauj, yas los yog nias cardboard) nyob ib ncig ntawm nws thiab qhwv nrog zaj duab xis tiv thaiv. Thaum kawg, ntim nws rau hauv lub thawv ntoo, uas yog txau nrog lub forklift thiab nruab nrab - ntawm - cov cim nqus.

 

4.2 Shipping

Kev sib sau ua ke thiab sim transformer yog npaj rau kev xa khoom mus rau qhov chaw nres nkoj ntawm qhov chaw, Georgetown, Guyana. Tag nrho cov sab nraud protrusions raug tiv thaiv, thiab chav tsev yog nrog los ntawm cov ntaub ntawv tsim nyog shipping, nrog rau cov ncauj lus kom ntxaws packing lists thiab technical manuals, los pab txhawb kev lis kev cai clearance thiab xa zaum kawg.

image021

 

 

05 Site thiab Summary

Hauv cov ntsiab lus, lub ncoo no -mounted transformer muab cov khoom siv hluav taws xob muaj zog thiab txhim khu kev qha, tsim kom muaj lub neej ntev thiab kev nyab xeeb. Nws txoj kev tsim kho kom zoo, sib txuas cov tub ntxhais sib nqus zoo, cov khoom siv tooj liab ruaj khov, thiab lub tank hlau kaw, ua kom muaj kev ua tau zoo ib yam hauv kev xav tau sab nraum zoov. Peb cia siab tias chav tsev no yuav muab cov teeb meem ntau xyoo - kev pabcuam pub dawb, ua rau nws muaj kev ntseeg siab thiab muaj txiaj ntsig zoo rau koj cov khoom siv hluav taws xob.

image023

 

Cim npe nrov: me me ncoo mounted transformer, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug