Cov lus qhia no suav nrog kev teeb tsa, kev ua haujlwm, thiab kev saib xyuas ntawm ib-theem roj-immersed ncej-mounted faib transformers. Nws yog raws li cov khoom siv kev qhia thiab cov qauv kev lag luam xws li IEEE C57.12.00. Kev txhim kho kom raug, kev ua haujlwm raug, thiab kev saib xyuas tsis tu ncua yog qhov tseem ceeb rau kev nyab xeeb thiab txhim khu kev qha transformer kev pabcuam. Cov lus qhia no suav nrog kev txais thiab tuav, txuas, txuas hluav taws xob, kev sib txuas hauv av, kev kuaj xyuas ua ntej thiab tom qab lub zog, kev ua haujlwm tiv thaiv, kev tshuaj xyuas niaj hnub, thiab kev tuav dej.
Cov khoom siv npog: Ib-theem roj-immersed overhead faib transformers (paub series)
Cov qauv siv tauIEEE C57.12.00, IEEE C57.12.90, NEMA TR1, NFPA 70E
1. Kev Nyab Xeeb Kev Nyab Xeeb
1.1 Hazard level txhais
|
Cov lus qhia |
Lub ntsiab lus |
|
DANGER |
Tam sim no muaj kev phom sij uas, yog tias tsis zam, yuav ua rau tuag, raug mob hnyav lossis khoom puas tsuaj. |
|
CEEB TOOM |
Tej zaum yuav muaj teeb meem uas, yog tias tsis zam, tuaj yeem ua rau tuag, raug mob hnyav lossis khoom puas tsuaj. |
|
CEEB TOOM |
Tej zaum yuav muaj teeb meem uas, yog tias tsis zam, tej zaum yuav ua rau me me / nruab nrab raug mob los yog khoom puas tsuaj. |
1.2 Cov kev cai dav dav txog kev nyab xeeb
Tsuas yogcov neeg ua haujlwm tsim nyog(kawm nyob rau hauv high-voltage khoom installation, txij nkawm, kev khiav hauj lwm, kev siv PPE zoo, thiab kev pab thawj zaug) tej zaum yuav ua hauj lwm rau cov cuab yeej no.
Ua ntej kev saib xyuas lossis tshuaj xyuas:
- De-energise lub transformer los ntawm aqhov chaw nyob deb.
- Siv lub ntsuas hluav taws xob tsim nyog los kuaj xyuasxoom voltage ntawm tag nrho cov high-voltage thiab low-voltage bushings.
- Ua tib zoo av tag nrho cov terminals(ob qho tib si thawj thiab theem nrab).
- Xav txog qhov ua tau backfeed (xws li standby generator).
Tsis txhob cia siab rau kev tshem tawm fuse lossis hloov chaw ua pov thawj ntawm de-energisation.
Hnav PPE tsim nyog (cov hnab looj tes insulating, lub ntsej muag tiv thaiv, arc-flash suit) raws li NFPA 70E xav tau.
Tsis txhob khiav cov kua dej-immersed switching li thaum lub insulating kua kub nyob rau hauv qab no:
- Cov roj ntxhia los yog cov kua dej silicone: -20 degree
- R-Temp kua: 0 degree
- FR3 ™ natural ester kua: -10 degree
2. Kev txais, tuav thiab khaws cia
2.1 Tau txais kev tshuaj xyuas (ua ntej unloading)
|
Yam khoom |
Kev ua |
|
Daim ntawv npe |
Txheeb xyuas tus lej xov tooj, kVA, HV / LV kev ntsuas, impedance, kua hom kev sib tw. |
|
Kev puas tsuaj sab nraud |
Tshawb xyuas cov dents, khawb, deformed radiators, xim puas. |
|
Leaks |
Tshawb xyuas welds, bushings, gauges, li qub rau cov roj stains. |
|
Khoom siv |
Paub meej tias lub siab / lub tshuab nqus tsev ntsuas, ntsuas roj qib, ntsuas qhov ntsuas kub, ntsuas lub valve, ntes, fuses, phau ntawv qhia, cov ntawv ceeb toom tam sim no. |
|
Lub tshuab nqus tsev vacuum |
Kev nyeem ntawv yuav tsum sib txawv nrog qhov kub thiab txias. Tsis tas li xoom yuav qhia tau tias muaj dej xau. |
Yog pom muaj kev puas tsuaj lossis tsis txaus,ceeb toom ntawm daim nqi ntawm lading, thaij duab, ua ntawv thov nrog tus neeg nqa khoom, thiab ceeb toom rau cov chaw tsim khoom.
2.2 Lifting thiab tuav
Crane / Hoist Lifting:
- Sivtsuas yog muab lifting lugs. Tsis txhob nqa los ntawm bushings, radiators los yog khi-down qhov.
- Cov cuab yeej nqa (hooks, slings, spreader bar) yuav tsum tau ntsuas rau tag nrho qhov hnyav (saib daim ntawv teev npe).
- Siv cov kab sib kis kom cov hlua khi ze li ntsug (lub kaum sab xis tsawg dua lossis sib npaug li 20℃ntawm ntsug).
- Maximum qaij thaum nqa:15℃los ntawm ntsug.
- Thaum ambient kub qis dua -20 degree, kho nrog kev saib xyuas ntxiv kom tsis txhob muaj kev puas tsuaj.
Forklift tuav:
- Tsuas yog rau cov transformers ruaj ntseg mounted ntawm shipping pallet.
- Forks yuav tsum txuas tag nrho hauv qab pallet.
- Tsis txhobnqa ib tug unpalletised transformer nrog ib tug forklift.
2.3 Cia khoom
Lub sij hawm luv luv: Khaws rau hauv cov ntim khoom qub hauv qhov chaw huv, qhuav, tsis muaj corrosive.
Long‑term (>3 lub hlis):
- Khaws rau ntawm qhov chaw ruaj khov, theem saum npoo. Siv cov racks cia.
- Tsis txhob stacktransformers - kev pheej hmoo ntawm lub tank thiab bushing puas.
- Tshawb xyuas txhua 3 lub hlis: ntsuas ntsuas, roj qib, xau, corrosion.
- Yog tias lub ntsuas ntsuas siab nyeem xoom lossis qib roj poob, tshawb xyuas thiab kho cov xau.
- Khaws lub siab me ntsis (3-4 PSIG) nrog cua qhuav lossis nitrogen yog tias ua tau.
3. Cov kauj ruam ntawm kev teeb tsa
3.1 Xaiv qhov chaw
Ua raws li IEEE C57.12.00 "Kev Pabcuam Ib Ntus":
- Qhov siab tsawg dua lossis sib npaug li 1000 m
- Ambient kub -25℃rau +40 degree
- Tsis muaj plua plav ntau dhau, corrosive gases, kev vibration, lossis dej nyab.
Nruab nyob rau hauv ib qho chaw nkag tau tsuas yog rau cov neeg ua haujlwm tau tso cai (xws li xauv lub qhov rooj lossis ncej).
Khaws cov radiators (yog tias muaj) tsis muaj kev cuam tshuam.
3.2 Ncej mounting
Siv cov hanger brackets muab rau ncaj ncej mounting.
Ncej lub zog yuav tsum txhawb nqa transformer tag nrho qhov hnyav (saib daim ntawv teev npe).
Tom qab mounting, qaij nyob rau hauv txhua txoj kevyuav tsum tsis pub tshaj 3 degree. Kev qaij ntau dhau tuaj yeem:
- Txo cov dej insulating ntawm cov khoom nyob.
- Impair cua txias ncig.
- Muab cov ntawv nyeem qib roj cuav.
3.3 Kev tsim kho av
Siv covtshwj xeeb grounding ncoo los yog txiv ntseejntawm lub tank.
Tus neeg xyuas pib hauv av (feem ntau yog tooj liab, Ntau dua lossis sib npaug li 16 mm²) yuav tsum ua raws li cov cai hauv zos.
Kev tiv thaiv hauv av yuav tsum qis raws li qhov yuav tsum tau ua los ntawm cov cai hauv zos (feem ntau Tsawg dua lossis sib npaug li 10 Ω).
Tsis txhobsiv hanger brackets, bushings los yog lwm yam uas tsis yog-grounding qhov chaw rau grounding.
Txuas tag nrho cov nruab nrab muaj nyob rau hauv qhov system nruab nrab.
3.4 HV thiab LV kev sib txuas
Ntxuav thiab du tag nrho cov mating connector nto ua ntej kev sib txuas.
Ua raws li daim duab txuas ntawm daim ntawv teev npe.
Tighten bolts rau cov nqi torque hauv Table 3 (saib Tshooj 8).
Tsis txhob muaj ntau lub cantilever loads ntawm bushings (tsis txhob rub cov conductors nruj heev) - txwv tsis pub bushing los yog gasket puas yuav tshwm sim.
Optional insulated terminal caps ntawm HV sab pab tiv thaiv cov tsiaj qus tiv tauj.
3.5 Reconfiguring Internal LV kev sib txuas (yog tias xav tau)
Qhov xwm txheej: Transformer nrog peb LV bushings, Hoobkas-set rau E/2E (xws li . 120/240 V), tab sis xav tau E voltage (xws li . 120 V).
Txheej txheem:
- De-energise, av, txo siab (ua haujlwm PRV).
- Tshem tawm lub hau npog los yog lub hau npog (saib Tshooj 8.7).
- Reconnect LV coj los ntawm koob mus rau qhov sib npaug raws li qhia ntawm daim duab kos npe.
- Xyuas kom tag nrho cov kev sib txuas yog nruj (siv lub rooj torque), cov hlau lead yog zoo insulated, thiab tsis txhob kov lub tank los yog ib leeg.
- Reinstall npog, refill rau qib kom tsim nyog, tso cai rau 24 teev, tom qab ntawd ua qhov ntsuas piv los txheeb xyuas.
Hu rau cov chaw tsim khoom yog tias tsis paub meej.


4. Kev soj ntsuam thiab kuaj ua ntej lub zog
Lub transformer yuav tsum tsis txhob energized kom txog rau thaum tag nrho cov nram qab no cov kev ntsuam xyuas thiab kev ntsuam xyuas tiav tiav.
|
Tsis muaj. |
Kuaj / Tshawb xyuas |
Paub meej |
Kev lees txais |
|
1 |
Ratio Test (TTR) |
Siv transformer lem ratio tester ntawm tag nrho cov kais dej |
Tsawg dua lossis sib npaug ± 0.5% |
|
2 |
Rwb thaiv tsev tsis kam |
1000V megger; winding-winding thiab winding-av |
Ntau dua lossis sib npaug rau 1.0 GΩ (huv / qhuav) |
|
3 |
Multi-voltage hloov txoj hauj lwm |
Teem raws li daim ntawv teev npe, locking ntsia hlau koom |
Txoj hauj lwm raug |
|
4 |
Coj mus rhaub hloov txoj hauj lwm |
Teem rau qhov ntsuas voltage (feem ntau yog nruab nrab kais) |
Txoj hauj lwm raug |
|
5 |
Hauv av |
Visual + av tiv thaiv ntsuas |
Ruaj ntseg, nyob rau hauv lub zos txwv |
|
6 |
Bolted kev sib txuas |
Torque check ib Tables 1-4 |
Nyob rau hauv lub torque range |
|
7 |
Dej theem |
Level gauge los yog pom plug |
Nruab nrab ntawm "High" thiab "Low" |
|
8 |
Dej kub |
Nyeem qhov ntsuas kub |
Tsis pub tsawg kawg nkaus (saib hauv qab) |
|
9 |
Internal Fault Detector (IFD) |
Tshem cov txiv kab ntxwv shipping xauv |
Xauv tshem tawm |
|
10 |
Tam sim no transformers (CTs) |
Yog tias tsis txuas nrog kev thauj khoom, cov hlau lead yuav tsum luv luv thiab hauv av |
Tsis qhib Circuit Court |
|
11 |
Accessory thaiv |
Tswj, tswb circuits - tsis muaj kev sib txuas xoob lossis puas rwb thaiv tsev |
Zoo mob |
|
12 |
Tank tiav |
Xim - tsis muaj kev puas tsuaj, xeb |
Txais tau |
Yam tsawg kawg nkaus tso cai dej kub ua ntej energis:
- Mineral roj / silicone: -20 degree
- R-Temp: 0 degree
- FR3: -10 degree
Yog tias cov kua dej txias dua, sov nws maj mam (xws li nrog cov pam cua sov) ua ntej muaj zog.


5. Kev Tshawb Fawb Tom Qab Hluav Taws Xob
Tom qab thawj lub zog (zoo dua los ntawm qhov chaw nyob deb), ua:
- Txheeb xyuas qhov voltage thib ob- Yuav tsum tsis pub dhau ± 5% ntawm daim ntawv teev npe tus nqi.
- Tshawb xyuas cov dej xau- Tshawb xyuas welds, bushings, li qub, gauges rau cov roj seepage.
- Saib xyuas kev ua haujlwm- Tsis muaj kev vibration txawv txav, pa taws, sparking, lossis suab nrov txawv txawv.
- Tshawb xyuas cov ntsuas- Cov roj qib yuav tsum nce siab (raws li qhov kub nce), tus pas ntsuas kub yuav tsum maj mam nce, lub ntsuas ntsuas lub tshuab nqus tsev yuav tsum pom qhov zoo.
- Suab nrov- Ib txwm yog qhov "hum" tsis tu ncua (magnetostriction).
Cracking / intermittent popping → ua tau nto tawm ntawm bushings.
Buzzing nrog arcing suab → internal xoob kev twb kev txuas los yog core teeb meem.
Suab nrov heev → over-excitation los yog overvoltage.
- Infrared Thermography (yeem)- Tshawb xyuas cov kev sib txuas ntawm lub davhlau ya nyob twg rau qhov chaw kub.
6. Kev ua haujlwm ntawm kev hloov pauv thiab cov cuab yeej tiv thaiv
6.1 Cov cai dav dav
- Siv acov cuab yeej nyob-kab (kub stick lossis phom phom stick)rau cov cuab yeej tsim los rau kev ua haujlwm zoo li no. Tsis txhob ua haujlwm ntawm tes.
- Txhua zaus de-energise thiab hauv av ua ntej ua haujlwm hloov lossis hloov fuses.

6.2 De-energised kais hloov pauv
Tsuas yog ua haujlwm thaum transformer yog de-energised.
Txheej txheem:
- De-energise thiab av.
- Disengage locking ntsia hlau (yog tias muaj).
- Tig tus tuav mus rau txoj haujlwm xav tau (saib rau daim ntawv teev npe thiab hu).
- Re-ntsuas ntswj ntsia hlau.
Lub Hoobkas teeb tsa feem ntau yog qhov ntsuas qhov ntsuas hluav taws xob.
6.3 Multi-voltage hloov
- Tsis tas li ntawd de-energized nkaus xwb.
- Kev teeb tsa Hoobkas feem ntau yog qhov chaw siab tshaj plaws.
- Yog hais tias ob qho tib si kais dej thiab ntau qhov hluav taws xob windings muaj, xyuas kom lub kais hloov nyob rau hauv txoj hauj lwm uas pom ntawm daim ntawv teev npe thaum muaj ntau qhov hluav taws xob hloov nyob rau hauv txoj hauj lwm sib npaug.
6.4 Tsawg-voltage Circuit Court breaker
- Nyob rau sab tank, ua haujlwm nrog lub pas kub.
- Khiav hauj lwm:O= Qhib,C= QHOV TSEEB,R= RESET.
- Tom qab taug kev: tig musR, ces toC.
- Optional overload lever thaum muaj xwm ceev: tig mus rau "EO" rau ib ntus overload muaj peev xwm (≈30% saum toj no rating). Tsawg siv kom tsis txhob txo lub neej transformer.
- Teeb liab teeb (yeem): illuminates tom qab hnyav dhau; rov pib dua thaum kov yog tig musR.
CEEB TOOM: Txawm tias nrog lub breaker qhib, capacitive coupling tej zaum yuav ua rau muaj kev poob siab ntawm ungrounded thib ob terminals. Txhua zaus hauv av theem nrab terminals ua ntej ua haujlwm.

6.5 Magnex cuam tshuam
Internal roj-immersed overcurrent thiab overtemperature ntaus ntawv rau HV sab.
Kev ua haujlwm nrog kub stick:
- Qhib: Tig kov sab saud (counter-clockwise) rau OPEN txoj hauj lwm.
- Kaw: tig tuav downward (clockwise) nrees tiv thaiv nres nyob rau hauv CLOSED txoj hauj lwm.
- Rov pib dua tom qab taug kev: ua ntej rau OPEN, tom qab ntawd rau CLOSED.
Kev xaiv thaum muaj xwm txheej ceev tshaj (EO): ntawm OPEN txoj hauj lwm, tig EO lever counter-clockwise rau EO, ces kaw.
Yeem qhov taw qhia mus txawv tebchaws: txiv kab ntxwv lens tshwm thaum tripped.
6.6 Fuse
Weak-link fuse: mounted ntawm HV bushing puag lossis ntawm kev hloov; tiv thaiv overloads thiab internal faults.
Ib nrab-nqi tam sim no-limiting fuse: nyob rau hauv series nrog weak-link; txwv lub zog rau cov kev ua txhaum sab hauv siab tam sim no.
Hloov:
- Txheeb xyuas thiab kho qhov laj thawj ntawm kev ua haujlwm ua ntej hloov.
- Siv qhov ntsuas thiab cov yam ntxwv zoo ib yam.
- De-energise, av, qhib tank (saib Tshooj 8.7) kom nkag mus.

6.7 Surge arrester
- Tus neeg ntes sab nraud: xyuas cov kab hlau lead thiab hauv av sib txuas yog nruj (torque Table 3).
- Internal MOV ntes (yeem): roj-immersed; Qhov nruab nrab ntawm cov kua dej yuav tsum tsis txhob siab tshaj 90 degree, max 125 degree.
- Ua ntej ua qhov kev ntsuam xyuas impulse lossis induced muaj peev xwm, disconnect tus ntes(ob leeg sab nraud thiab sab hauv). Rov ua dua tom qab kuaj.
7. Kev ua haujlwm ntawm Bushings, Gauges thiab Accessories
|
Ntaus ntawv |
Ib txwm qhia / siv |
Abnormal / kev ua |
|
Lub tshuab nqus tsev vacuum |
Nws txawv nrog load thiab kub; zoo thaum kub, tej zaum yuav tsis zoo thaum txias |
Tsis tu ncua xoom → tuaj yeem xau, tshawb xyuas |
|
Roj qib ntsuas |
Ntawm 25 degree, taw tes ntawm "H" thiab "L"; nce nrog kub |
Hauv qab "L" → ntxiv cov kua dej thiab kuaj xyuas cov dej xau |
|
Roj ntsuas kub |
Sab saum toj roj kub feem ntau Tsawg dua los yog sib npaug li 85 degree; liab luag tes cov ntaub ntawv max |
>95℃→ check load, txias, dej txias |
|
Drain valve / sampling ntaus ntawv |
Tshem tawm los yog nqa cov qauv los ntawm qab ntawm lub tank |
Pas → hloov gasket lossis valve |
|
Tsis siv neeg siab nyem valve (PRV) |
Qhib thaum lub siab sab hauv siab tshaj qhov taw tes, ces rov ua dua |
Tom qab ua haujlwm, tshawb xyuas qhov laj thawj |
|
Internal Fault Detector (IFD) |
Pops tus chij txiv kab ntxwv uas tsis tuaj yeem hloov dua tshiab thaum muaj teeb meem sab hauv arcing tshwm sim |
Txiv kab ntxwv chij pom → transformer yog faulted,tsis muaj zog |
IFD ceeb toom: IFD yog qhov taw qhia pom nkaus xwb, tsis yog hluav taws xob txiav. Txawm hais tias IFD tsis tau ua haujlwm, qhov hloov pauv tseem tuaj yeem ua txhaum. Tsis txhob cia siab rau nws ua ib qho kev ruaj ntseg de-energisation ntaus ntawv.

Lub tshuab nqus tsev vacuum

Roj qib ntsuas

Roj ntsuas kub

Drain valve / sampling ntaus ntawv

Radiator

Internal Fault Detector (IFD)
8. Kev tu thiab kho
8.1 Pom zoo lub sijhawm txij nkawm
|
Lub sijhawm |
Kev ua si |
|
Txhua hli (lub luag haujlwm hnyav lossis ib puag ncig hnyav) |
Kev kuaj pom pom, roj qib, suab txawv txawv, IR thermography |
|
Txhua 6 lub hlis |
Kev tshuaj xyuas xim, rov kho cov bolts, huv radiators |
|
Txhua xyoo |
Roj sampling (dielectric zog, dej ntsiab lus, acidity, DGA) |
|
Txhua 3 xyoos |
Rwb thaiv tsev tsis kam, piv txwv kuaj, kev ntsuas fais fab |
|
Tom qab ua txhaum los yog txawv txav |
Kev soj ntsuam roj tam sim thiab ntsuas hluav taws xob |
8.2 Sab nrauv xim tiav
Yog hais tias primer los yog liab qab hlau raug, kho tam sim ntawd los tiv thaiv corrosion:
- Xuab zeb rau thaj tsam kom tshem tawm xeb thiab xoob xim.
- Ntxuav nrog hnyav (tshem roj, roj).
- Siv anti-xeb primer.
- Siv ob lub tsho tiv no sab saum toj (siv cov chaw tsim tshuaj pleev xim yog tias muaj).
8.3 Kev kho cov dej xau
Leak pov thawj:
- Ntxuav qhov chaw tsis txaus ntseeg, siv talc lossis cov kua dej tawm kom pom.
- Pressurize tank nrog cua qhuav lossis nitrogen rau 3-4 PSIG, tos 1-2 teev, tshuaj xyuas.
Txoj kev kho:
- Pinhole los yog weld seam leak on tank: de-energise, drain, weld (muaj peev xwm welder).
- Radiator leak: tsis welding (cov khoom nyias); hloov lossis siv cov khoom kho epoxy.
- Bushing to: sim zawm clamp bolts (torque Table 2); yog tias ua tsis tau, hloov gasket.
- Valve lossis gauge leak: hloov gasket lossis tag nrho cov khoom.
8.4 Insulating kua dej tu
Cov txheej txheem Sampling:
- De-energise thiab av.
- Flush ntws valve nrog me me roj.
- Nqa cov qauv hauv lub thawv huv, qhuav, tsis txhob tshav ntuj.
- foob tam sim ntawd thiab xa mus rau kev tshuaj ntsuam.
Hom kev lees txais (mineral oil):
|
Parameter |
Txais tus nqi |
|
Dielectric zog |
Ntau tshaj lossis sib npaug li 26 kV |
|
Cov ntsiab lus dej |
Tsawg dua lossis sib npaug li 35 ppm |
|
Acidity |
Tsawg dua lossis sib npaug li 0.1 mg KOH / g |
|
Lub zog muaj zog @ 25 degree |
Tsawg dua los yog sib npaug li 0.5% |
Lim:
- Siv lub tshuab lim xovxwm kom txog thaum lub zog dielectric Ntau dua lossis sib npaug li 26 kV.
- Tsis txhob sib tov cov kua dej; lub lim xovxwm yuav tsum tsis muaj paug los ntawm lwm cov kua.
Refilling:
- Siv raws nraim tib hom thiab hom kua.
- Twj maj mam los ntawm hauv qab ntawm lub tank kom tsis txhob muaj cua npuas.
- Sau rau kab cim hauv lub tank, tom qab ntawd cia 24 teev rau huab cua kom khiav tawm ua ntej muaj zog.
8.5 Kev ntsuam xyuas hluav taws xob (periodic lossis diagnostic)
|
Kuaj |
Txoj kev |
Txais |
|
Rwb thaiv tsev tsis kam |
1000V lossis 2500V megger |
Ntau dua lossis sib npaug rau 1 GΩ (qhuav) |
|
Ratio (TTR) |
TTR tester |
±0.5% |
|
Rwb thaiv tsev fais fab |
2.5 kV lossis 10 kV choj |
Tsawg dua lossis sib npaug li 0.5% @ 20 degree |
|
Winding DC tsis kam |
Micro-ohmmeter |
Deviation Tsawg dua lossis sib npaug li 2% ntawm theem |
8.6 Torque cov lus qhia
Table 1 – Sab nraud fasteners
|
Fastener hom |
Nominal torque (hauv-lbs) |
Torque ntau yam (hauv-lbs) |
|
3/8" bolts |
240 |
220‑260 |
|
Handhole npog bolt |
144 |
129‑158 |
|
Npog band bolt |
180 |
170‑185 |
|
Surge arrester mounting ntsia liaj qhov rooj |
420 |
372‑468 |
Table 2 – Sab nraud bushing mounting hardware
|
Bushing hom |
Nominal torque (hauv-lbs) |
Torque ntau |
|
LV molded Tri-Clamp (tsis muaj lub nplhaib clamp), 3/8 "stud |
60 |
40‑80 |
|
LV molded (nrog lub nplhaib clamp), 3/8 "stud |
120 |
90‑150 |
|
LV porcelain (nrog lub nplhaib clamp), 1/2 "stud |
80 |
70‑90 |
|
HV molded Tri-Clamp, 3/8 "stud |
60 |
40‑80 |
|
HV molded (nrog lub nplhaib clamp), 3/8 "stud |
120 |
90‑150 |
|
HV porcelain |
80 |
70‑90 |
Table 3 – External terminal txuas
|
Terminal hom |
Nominal torque (hauv-lbs) |
Torque ntau |
|
HV porcelain bushing eye-bolt |
210 |
180‑240 |
|
HV porcelain bushing kawg cap |
168 |
156‑180 |
|
LV bushing 5/8" jam txiv ntoo |
600 |
480‑720 |
|
LV bushing 1" jam txiv ntoo |
600 |
480‑720 |
|
LV bushing 1-1/4" jam txiv ntoo |
720 |
600‑840 |
|
Sab nraud arrester kab lead |
180 |
162‑198 |
|
Sab nraud arrester av lead |
180 |
162‑198 |
Table 4 – Accessories
|
Cheebtsam |
Nominal torque (hauv-lbs) |
Torque ntau |
|
Bushing-mounted tsis muaj zog-link fuse bolts |
85 |
80‑90 |
|
Fluid Level Sight Plug |
960 |
900‑1020 |
|
Fill ntsaws |
960 |
900‑1020 |
|
Drain plug |
960 |
900‑1020 |
|
Dej valve |
600 |
480‑720 |
|
PRV 1/4" NPT |
180 |
160‑200 |
|
PRV 1/2" NPT |
360 |
324‑396 |
|
Tsis siv neeg pluaj fastener (hauv av ncoo) |
160 |
140‑180 |
|
Coj mus rhaub hloov mounting txiv ntseej |
120 |
96‑144 |
Vim lub gasket so, ntsuas torque yuav qis dua nominal. Tsis txhob overtighten - kev pheej hmoo ntawm tawg los yog over-compression.
8.7 Qhib lub tank transformer
Tsuas yog thaum tsim nyog kiag li(xws li kev hloov fuse sab hauv, LV reconfiguration, kev hloov kho sab hauv).
Txheej txheem:
- De-energise, hauv av, txo qhov siab (ua haujlwm PRV nrog cov pas kub kub - ceev faj ntawm cov dej kub).
- Ntxuav thaj chaw nyob ib ncig ntawm lub hau los yog lub qhov tes kom tiv thaiv cov khib nyiab nkag.
- Tshem cov bolts, ua tib zoo nqa lub hau (tiv thaiv gasket).
- Yog tias cov kua dej yuav tsum tau qis dua, tso rau hauv cov ntim huv si, qhuav (tsis txhob txo cov dej hauv qab cov tub ntxhais / coil clamp pan - coils yuav tsum nyob twj ywm).
- Thaum ua haujlwm: siv cov npog huv, tsis muaj lint-dawb; khi cov cuab yeej nrog txoj hlua ruaj ntseg kom tsis txhob poob rau hauv lub tank.
- Tsis txhob cia lub tank qhib rau ntau tshaj 2 teev.Yog tias cuam tshuam, rov ua dua thiab sau nrog cua qhuav lossis nitrogen.
- Ua ntej rov txhim kho lub hau, hloov cov gasket puas. Tighten bolts rau Table 1 torque.
- Rov ua dua maj mam, tso cai rau 24 teev, tom qab ntawd ua qhov ntsuas kev tiv thaiv kev tiv thaiv ua ntej lub zog.
9. Phau ntawv qhia kev daws teeb meem
|
Cov tsos mob |
Ua tau |
Kev ua |
|
Secondary voltage tsis raug |
Txoj haujlwm kais tsis raug, tsis raug HV txuas, tshuab fuse |
De-energise, xyuas kais hloov, xaim, hloov fuse |
|
Kub kub |
Overload, thaiv radiators, qis roj theem, sab hauv txhaum |
Txo cov load, huv si radiators, ntxiv roj, qauv roj |
|
PRV ua haujlwm |
Internal arc, hnyav dhau, roj tsim |
De-energise, xyuas IFD, ua DGA - tsis txhob rov ua kom lub zog dig muag |
|
IFD txiv kab ntxwv chij pom |
Internal arcing txhaum |
Transformer yog faulted - hloov unit |
|
Tsawg rwb thaiv tsev tsis kam |
Moisture nyob rau hauv roj, qias neeg bushings, laus rwb thaiv tsev |
Ntxuav bushings, lim los yog hloov roj, qhuav tawm |
|
Suab nrov txawv txav (tsis yog ib txwm hum) |
Lub hauv paus xoob, winding txav, over-excitation |
De-energise, check ratio thiab tsis muaj-load tam sim no |
|
Roj theem maj mam poob |
Leak |
Nrhiav thiab kho cov dej xau, sab saum toj |
|
Lub tshuab nqus tsev ntsuas ntsuas ib txwm xoom |
Tank foob poob |
Kev ntsuam xyuas, kho, ces khiav tawm thiab rov ua dua |
10. Hais txog Transformer Installation & Kev Qhia Kev Ua Haujlwm
Ncej mounted transformers pab nyiaj siv ua haujlwm faib cov kab, tab sis ntau daim ntawv thov hluav taws xob xav tau lwm yam kev sib txuas los yog cov ntaub thaiv npog. Txhawm rau ua tiav cov txheej txheem ntawm kev teeb tsa transformer thiab kev ua haujlwm, saib cov lus qhia ntxiv hauv qab no.
- Substation Transformer Installation and Operation Guide
- Fais fab Transformer Installation and Operation Guide
- Pad Mounted Transformer Installation thiab Kev Qhia Ua Haujlwm
- Dry Type Transformer Installation and Operation Guide
- Compact Substation Installation thiab Kev Qhia Ua Haujlwm
11. Khoom seem, Warranty thiab pov tseg
10.1 Ordering spare qhov chaw
Muabtransformer serial tooj(ntawm nameplate), ib feem piav qhia, thiab kom muaj nuj nqis.
Hu rau cov chaw tsim khoom muag lossis kev pabcuam.
10.2 Warranty
Qhia rau cov chaw tsim khoom tam sim yog tias muaj teeb meem tshwm sim thaum lub sijhawm lav.
Tag nrho cov kev kho warranty yuav tsum tau pom zoo los yog ua los ntawm cov chaw tsim khoom.
10.3 Pov tseg
Tshem tag nrho cov dej insulating ua ntej scrapping lub transformer.
Pov tseg cov kua raws liib puag ncig kev cai hauv zos(tsis txhob nchuav).
Lub tank steel, core thiab tooj liab windings tuaj yeem siv dua.
Cov kua dej los ntawm cov hloov pauv qub (ua ntej xyoo 1970s) tuaj yeem muaj cov PCBs - ua rau cov khib nyiab pov tseg.