Kev Taw Qhia

 

transformer tank

 

Lub taub roj hloov pauv hluav taws xob, raws li tus tseem ceeb tiv thaiv lub zog hloov pauv, tsis yog muab kev nyab xeeb rau kev ua haujlwm, thiab tseem muaj kev nyab xeeb los ntawm nws cov kev lag luam kev tsim qauv thiab kev ntseeg tau. Nrog txoj kev hloov kho lub zog rau cov kev siv hluav taws xob ntau dua, kev tsim khoom loj, thiab smarroster kev ua haujlwm, thiab smarrosion distance, thiab txhim kho kev sib khi ua haujlwm. Cov kab lus no ntsuas cov khoom xaiv, kev tsim qauv qauv, thiab cov ncauj lus kom ntxaws ntxiv xws li kev lag luam tshiab los ua kev siv rau kev tsim khoom lag luam thiab kev saib xyuas.

02 kev ua haujlwm ntawm lub tank transformer

 

Lub tshuab hluav taws xob hloov pauv yog thawj cov qauv sab nraud ntawm lub tshuab hloov pauv, ua haujlwm rau ntau txoj haujlwm tseem ceeb:

1. Cov Khoom thiab Kev Tiv Thaiv: Lub tsev nyob rau tus tub ntxhais hloov khaub ncaws hloov (hlau, thiab lwm yam) thiab cov roj av insulating, tiv thaiv cov kab mob sab nraud (hmoov av, noo noo).

2. Cua txias thiab rwb thaiv tsev: Kev pab roj roj rau cov cua sov dissipation los ntawm cov phab ntsa tank thiab radiators (lossis corrugated panels); Cov roj insulating kuj muab cov hluav taws xob hluav taws xob.

3. Kev pab txhawb: Dais qhov nyhav ntawm sab hauv thiab hluav taws xob rog thaum lub sijhawm luv - Circuit Court.

4. Kev Ntsuas Kev Nyab Xeeb: Nta ib lub cim kev tsim qauv los tiv thaiv cov roj to, nrog qee cov tso tsheb hlau luam tawm tawg {}} equepor pab kiag li).

 

Ntxiv kev tswv yim: Cov hlau hluav taws xob hloov pauv tshiab, xws li ntim cov roj kom txo qis roj {}} huab cua tiv thaiv thiab qeeb roj kev tsis txaus siab.

03 Khoom rau Transformer Tso Tsheb Hlau Luam

 

Cov kev xaiv ntawm cov kev tso tsheb hlau luam rau kev thauj hluav taws xob nyob ntawm cov yam xws li kev ua haujlwm, kav ntev, thiab tus nqi. Hauv qab no yog cov kev xaiv feem ntau siv thiab lawv cov yam ntxwv:

Me me hlau

 

Cov hlau me me yog cov khoom siv dav siv ntau vim nws lub zog siab, pheej yig, thiab yooj yim ntawm cov fabrication. Nws tuaj yeem tiv thaiv lub siab sab hauv los ntawm thermal nthuav ntawm cov roj insulating. Kev kho cov npoo npoo (piv txwv li, pleev xim lossis pleev xim) feem ntau siv los txhim kho huab cua tiv, ua rau haum rau sab nraum zoov.

Mild steel

Stainless Steel

Stainless hlau

 

Nyob rau hauv corrosive ib puag ncig (piv txwv, cov nroj tsuag ntug dej hiav txwv, lossis siab- av noo tso tsheb hlau luam yog nyiam. Lawv cov xeb zoo dua mus txuas ntxiv txuas ntxiv lub neej thiab txo cov kev xav tau txij nkawm, txawm tias ntawm tus nqi siab dua.

Lwm Yam Khoom

 

1.Galvanized steel: Muab kev txhim kho corrosion tsis kam los ntawm zinc txheej, ntsuas phaus thiab tus nqi.

 

2.Tooj dawb: Kev xaiv lub teeb yuag, tab sis yuav tsum ua tib zoo xav txog lub zog thiab roj compatibility.
Cov txheej txheem tiv thaiv ntxiv lossis cov rwb thaiv tsev tuaj yeem thov rau kev tso tsheb hlau luam rau huab cua huab lossis tshuaj lom neeg.

Alternative Materials

04 Tank Tank

 

1. Tank Lub Cev Tsim:
o Cav -}} Sab saum toj Tso Tsheb Hlau Luam:Siv nyob rau hauv cov hloov pauv me me rau kev yooj yim.
o arched -}} Sab saum toj Tso Tsheb Hlau Luam:Feem ntau hauv nruab nrab / cov hloov pauv loj, nrog ib txoj kev nkhaus rau sab saum toj rau kev txhim kho siab tiv thaiv.
o corrugated tso tsheb hlau luam:Nta yoj {{0} Zoo li phab ntsa kom kho cov roj ntim ntawm cov hluav taws xob (txij nkawm {1} ywj pheej tsim).


2. Txuas:
o Cua txias tshuab:Welded cua txias, detachable radiators, lossis corrugated panels.
o Flanges thiab Sealing thaj chaw:Rau mounting bushings, roj gauges, thiab li qub.
o Pab cov tav su:Tiv thaiv deformation, feem ntau nyob rau sab nraud thiab puag.
o Lifting Lugs thiab cov shocks:Pab tsheb thauj mus los thiab installation.

05 Scalech {{{-}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}} Proge transformer roj tso tsheb hlau luam

 

Scotech yog lub chaw tsim tshuaj paus kev lag luam ntawm high- zoo transformer tso tsheb hlau luam, muab ntau cov kev daws teeb meem rau ntau yam kev hloov pauv. Peb cov khoom lag luam li cas suav nrog:

Tank For Single Phase Pad Mounted Transformer

TANK RAU TIB THEEM NCAS POUNTED Transformer

Tsim los rau kev cog lus, hauv av {{{{0} mounted ib {}}}}}}} kav dej tsis txaus ntseeg.

Tank For Three Phase Pad Mounted Transformer

Tank rau peb theem ncoo ntsia hloov pauv

Kev tsim kho rau peb {-}}}}} mounted chav nyob, haum rau nqi hluav taws xob, haum rau nqi hluav taws xob, siv.

Tank For Single Phase Pole Mounted Transformer

TANK rau tib theem ncej Mounted Transformer

Kev tso tawm lub teeb tseem ceeb tau ua kom zoo rau cov neeg ua haujlwm qub {}}}}}}}}} parsase transformers.

Tank For Three Phase Pole Mounted Transformer

Tank rau peb theem ncej sib hloov pauv

Engineered rau kev ntseeg tau nyob rau hauv peb -} paye Ncej - huab cua tiv thaiv, nrog huab cua zoo heev.

Tank For Substation Transformer

Tank rau hloov transformer

Hnyav {- Warty} Deart Trucks ua rau walland siab qhov kev xav tau, ua kom ntev}- lub sij hawm kev ua tau zoo.

Tank For Distribution Transformer

TANK rau kev faib khoom hloov pauv

Ua tau zoo thiab raug nqi -} Cov qauv tsim nyog rau kev txhim khu kev qha power network.

Tank For Power Transformer

Tank rau fais fab hloov hluav taws xob

Hnyav {{{0} Dosise tsim rau loj {1} {{{{{- term kev cia siab. Customizable kom tau raws li rwb thaiv tsev thiab yuav tsum ua kom txias.

Tank For Special Transformer

Tank rau kev hloov pauv tshwj xeeb

Kev daws teeb meem rau cov kev xav tau tshwj xeeb lossis tshwj xeeb transformer. (traction transformer, rauv hloov pauv, Rectifier Transformer, earrate transformer).

 

Scoteech's Transformer tso tsheb hlau luam yog tsim nrog kev ntsuas, siv siab {{0} {} txoj kev ua ncaj ncees, thiab kev txhawb nqa kev ua haujlwm. Txawm hais tias rau cov ntawv thov txheem lossis kev cai, peb xa cov tso tsheb hlau luam uas ua tau ntawv pov thawj hauv ntiaj teb thiab cov qhua tuaj noj mov- kev xav tau tshwj xeeb.

06 cov ncauj lus kom ntxaws kev tsim khoom

tank Cutting

1. Txiav

o Laser / Ntshav Txiav:Siab - precision steel phaj txiav nrog welded ntug beveling (piv txwv li v {{grooves).
o Tswjhwm Zoo:Tshawb xyuas cov burrs thiab flatness kom tsis txhob vuam tsis raug.

2. Drilling

O CNC DRILLING:Rau flange thiab fastener qhov (thev taus tsawg dua los yog sib npaug rau 0.5 mm los xyuas kom meej cov se).
Au Deburring:Tshem cov ntse ntse post -} drilling.

Drilling
Bending And Rolling

3. Dab tsi yog khoov thiab dov

o Nias nres:Foos txoj cai - lub kaum sab xis khoov (piv txwv, sab panels); Khoov vojvoog ntau dua lossis sib npaug rau 2 × cov khoom tuab kom tiv thaiv cov kab nrib pleb.
o Dov Tshuab:Daim hlau arcs rau arched / corrugated tso tsheb hlau luam, kom muaj txiaj ntsig zoo sib ncig.

4.Clinder Rolling Txheej Txheem

Siv Kev Tsim Kho Siab - Precision Phaj Daus Khoom thiab nruj nruj Curvature tswj kom ntseeg tau Tank Roundness<0.2%,

Cylinder Rolling Process
Welding

5.Welding

o Cov hau kev:Submerged Arc Vuam (Cov Seam Ntev), CO₂ Roj - Cov hlau nplaum vuam (cov pob qij txha ua ke).
o Kev tshuaj xyuas:X - duab tshav lossis ultrasonic kuaj rau vsds fab tseem ceeb.

6.Grinding thiab slag tshem tawm

o Lub kaum sib tsoo:Tus Welds Daws Flush nrog lub hauv paus hlau.
o Sandblasting:Siv cov oxidization ntxuav (sa2.5 txuj ci) rau txheej nplaum.

Grinding And Slag Removal
Comprehensive Slag Removal Process

7.comRheistive slag Tshem cov txheej txheem

• Ntau -} theem huv si system (tshuab + tshuaj)
• 100% Veld Seam Soj Ntsuam thiab Kev Raug Tshem Tawm Slag
• Kev ntsuam xyuas ultrasonic rau cov tsis xws luag

8. Khawb

o Siab kuaj:0.03-0.05 MPA rau 24 teev; Tshawb nrhiav xau nrog xab npum daws lossis helium.
o Nqus mus kuaj:Khiav tawm mus<133 Pa to verify sealing.

Leak Testing
Surface Treatment

9. Kev Kho Mob

A) Hmoov Txheej / Painting:Epoxy Resin (80-120 μm), ci; UV {- Resistant txheej rau kev siv sab nraum zoov.
B) Kev kho mob sab hauv:Insulating vanish lossis passivation los tiv thaiv cov roj paug.

07 Cov Qauv Txheej Txheem thiab Txuj Ci

 

1. Corrugated Tank Tsim Kho:

O Hydroforming: Pwm Hlau rau hauv vuag, ua kom zoo qhov tob / txuas rau cua txias.

o nkees kuaj: Simulates cua sov (ntau dua lossis sib npaug rau 100,000) rau kev ua haujlwm ntev.

 

2. Eco - cades:

o Txheej - pub dawb: Huab cua {- Cov hlau tiv taus (piv txwv li, corten).

o modular tso tsheb hlau luam: Disassembled rau kev rov ua dua tshiab.

 

3. Tus ntse Raug:

o Robotic Vuam: Lub zeem muag - coj los qhia rau precision.

Robotic Welding

 

o Cov menyuam ntxwj: Simulate lub zog thiab kev ua tau zoo.

08 Tsim Yuav Tsum Tau Rau Transformer Tank

 

1. Cov khoom siv thiab kev thaiv: Lub tank yuav tsum tau tsim los ntawm high {{0} {}} lub zog hlau daim hlau los ntawm kev tiv thaiv vuam, nrog kev tiv thaiv sib nqus kom txo qis poob. Lub sib nqus daim thaiv npog yuav tsum tau nruab nrog kev ruaj ntseg thiab zoo-} one} insulated los tiv thaiv kev ua kom dhau los lossis kev tawm mus los ntawm kev sib tiv tauj. Txhua lub tshuab hluav taws xob yuav ua rau pom kev ua tau zoo tshaj plaws thiab txhim khu kev qha zoo kom tsis txhob muaj ntab tawm los yog kev cuam tshuam rau cov windings.

 

2. Sab saum toj qauv: Lub tank saum yuav tsum tau yov los pab txhawb kev tso kua dej thiab roj ua kom zoo rau cov roj relay. Txhua qhov kev qhib ntawm sab saum toj yuav tsum tau nruab nrog tsa cov flanges. Cov Plugs yuav tsum muab nruab rau cov ntsiab lus siab tshaj plaws ntawm qee lub peev xwm cua muaj peev xwm ua ke, txuas nrog ntawm ib qho kev xa khoom xa mus rau cov roj relay. Lwm tus kav kav kav yuav tsum tau ntxiv rau qhov siab- {{{4 4 {4 4 {4 4} {{4 4} {{4 4} {{4 4} {{4 4} {{4 4} {{4 4} {{4 4} {{4 4} Lub raj xa dej rau cov roj Relay yuav tsum muaj 1.5% nqes hav. Cov roj relay yuav tsum muaj cov kev ntsuas nag, nrog nws cov yeeb nkab piv txwv txuas ntxiv rau hauv av.

 

3. Base Tsim: Sab nrauv ntawm lub tank hauv qab yuav tsum tau ua cov channel steel puag thav duab, ua kom lub transformer kom raug rub raws nws txoj kev sib tw ntev thiab txoj hlab. Lub hauv paus yuav tsum suav nrog cov cuab yeej siv taing thiab anchoring tshuab nrog lub hauv paus bolts los ruaj khov rau cov khoom sib xyaw los ntawm cov cuab yeej hnyav thiab cov seismic tsis muaj zog. Cov chaw tsim khoom yuav tsum xa cov pob zeb thiab txhim kho cov ntsiab lus rau kev pom zoo los ntawm cov chaw ua haujlwm.

 

4. Segmented Kev Tsim Kho: Lub tank yuav tsum saws ob -}}}} ntu seem. Yog Welded, Reusable Flanges thiab Sealing Gaskets yuav tsum ua haujlwm kom ntseeg tau huab cua.

 

5. Kev Ntsuas Av: Ob lub chaw hauv av yuav tsum muab cov txheej txheem ntawm lub tank hauv qab. Lub hom phiaj tseem ceeb ntawm kev lag luam lub lag luam yog cov neeg muaj kev nyab xeeb {} yuav tsum hloov chaw ntawm av los ntawm kev tiv thaiv hluav taws xob, tiv thaiv cov hluav taws xob muaj kev phom sij.

09 Yuav Tsum Tau Rau Transformer Tank Grounding System

 

1. Grounding Terminals
o tsawg kawgOb Thaj Av Ntawm Cov Khoom Sivyuav tsum muab ntsia daim tawv ntawm lub tank hauv qab.
o Terminals yuav tsum tau ua los ntawmgalvanized steel lossis tooj liablos tiv thaiv corrosion.


2. Cov neeg ua lag luam
o sivNtau - strand tooj liab tooj liab cable los yog galvanized ca hlauNrog rau tus ntoo khaub lig txaus -}} seem kom tiv thaiv cov neeg txhaum.
o Yam tsawg kawg nkaus Hla -} seem:50mm² (tooj liab) lossis 100mm² (hlau)ib tus qauv hauv tebchaws (piv txwv li, GB / T 50065).


3. Kev Ua Si
o Cov av tiv thaiv yuav tsum yogTsawg dua los yog sib npaug rau 4ω(ib txoj kev cai hluav taws xob hauv lub cev).
o Hauv siab - tsis kam av, sivav txhim kho cov ntaub ntawv, cov electrodes sib sib zog, lossis cov pas nrig ntxivkom txo kev tiv taus.


4. Kev sib txuas qauv
o Terminal thiab tus cwj pwm yuav tsumbolted lossis weldedRau qis -}} ovredance sib cuag.
o yog bolted,Xauv TxuasYuav tsum tau siv los tiv thaiv kom tsis txhob poob siab vim kev co.


5. Corrosion & Kev Tiv Thaiv Txhua Yam
o Cov khoom siv hauv av yuav tsum yogkub - dip galvanized los yog pleev ximrau corrosion tsis kam.
o Cov ntaub ntawv faus hluav taws xob yuav tsum muaj kev tiv thaiv los ntawmPvc Kav lossis kaum steelyog raug rau kev ntxhov siab txhua yam.


6. Kev Txuas Rau Hauv Paus Av
o Lub tank yuav tsum yogTxuas mus ncaj qha rau cov phiaj xwm loj hauv av(Tsis muaj cov kab sib txuas).
o Kev cog qib kev yuav tsum yogluv thiab ncajkom txo qis impedance.


7. Kev tshuaj xyuas & txij nkawm
o Tsis tu ncua kev ntsuas kev ntsuas kev tiv thaiv kom ntseeg tau.
o Tshawb xyuasxoob, corroded, lossis tawg sib txuasthiab kho kom sai.

 

 