1500 KVA Nruab Nrab Voltage Qhuav Hom Transformers-15/0.55 KV|South Africa 2025

1500 KVA Nruab Nrab Voltage Qhuav Hom Transformers-15/0.55 KV|South Africa 2025

Lub teb chaws: South Africa 2025
Muaj peev xwm: 1500kVA
Lub hwj chim: 15/0.55 kV
Feature: nrog cov kiv cua txias
Xa kev nug

 

image001

Cam khwb cia Coil Qhuav Hom Transformer: Ua Tau Zoo rau kev thov ib puag ncig.

 

 

01 General

1.1 Project Description

1500kVA cam khwb cia coil qhuav hom transformer raug xa mus rau South Africa hauv 2025. Lub zog ntsuas ntawm lub transformer yog 1500 kVA nrog KNAN / KNAF txias. Thawj qhov hluav taws xob yog 15 kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov nruab nrab voltage yog 0.55 kV, lawv tsim ib pawg vector ntawm Dyn11.

Cast Coil Dry Type Transformer sawv cev rau qhov tseem ceeb ntawm kev nyab xeeb, kev cia siab, thiab kev ruaj ntseg ib puag ncig hauv kev siv hluav taws xob faib hluav taws xob. Tsis zoo li cov kua tshuaj ib txwm muaj - puv lossis qhov cua qhuav- hom transformers, nws qhov siab -voltage thiab qis-voltage windings yog encapsulated nrog cov khoom epoxy resin nyob rau hauv lub tshuab nqus tsev. Cov txheej txheem casting qib siab no tsim lub tshuab hloov hluav taws xob uas muaj kev saib xyuas zoo -dawb thiab impervious rau ib puag ncig hnyav.

Peb Cast Coil Transformer yog tsim los rau kev ua haujlwm tshwj xeeb. Nws tsis yog-flammable, emits tsis muaj pa phem, thiab ua rau tsis muaj kev pheej hmoo ntawm cov roj to, ua rau nws yog qhov kev xaiv zoo tshaj plaws rau kev nyab xeeb hauv tsev, lub hom phiaj- cov ntawv thov tseem ceeb xws li siab- cov tsev nce siab, tsev kho mob, cov ntaub ntawv chaw, cov nroj tsuag muaj, thiab cov chaw nyob sab nraud.

Nrog kev tiv thaiv zoo tshaj rau cov dej noo, tshuaj lom neeg, thiab cov khoom paug, ua ke nrog lub zog dielectric siab thiab qhov tshwj xeeb luv luv -circuit tiv taus lub peev xwm, Cast Coil Dry Type Transformer ua kom tsis muaj kev cuam tshuam lub zog thiab lub neej ua haujlwm ntev, muab kev thaj yeeb nyab xeeb ntawm lub siab thiab txo tus nqi ntawm cov tswv cuab.

 

 

 

1.2 Technical Specification

1500 kVA cam khwb cia coil qhuav hom transformer specification thiab cov ntaub ntawv ntawv

Xa rau
South Africa
Xyoo
2025
Hom
qhuav hom transformer
Cov khoom siv tseem ceeb
Grain oriented silicon steel ntawv
Txuj
IEC60076
Rated zog
1500kVA ua
Ntau zaus
50 HZ
Vector pawg
Dyn 11
Theem
3
Hom cua txias
ONAN/ONAV
Thawj Voltage
15kv ua
Secondary Voltage
0,55kv :ua
Cov khoom siv winding
Aluminium
Impedance
6%
Coj mus rhaub Changer
NLTC
Tapping Range
± 2 * 2.5% @ thawj sab
Tsis Load Loss
2.45 KW TSI
Ntawm Load Loss
11.5 KW TSI
Basic impulse teeb pom kev zoo nrog voltage thawj sab (BIL)
95kv ua
Fais fab zaus tiv taus voltage- sab xub ntiag
38kv ua
Fais fab zaus tiv taus qhov voltage- sab thib ob
3kv ua
Winding kub nce @ ntsuas kev pabcuam
100K
Rwb thaiv tsev theem
F

 

1.3 Cov duab kos

1500 kVA cam khwb cia resin qhuav hom transformer daim duab kos duab thiab loj.

image003 image005

 

 

02 Kev tsim khoom

2.1 Core

Cov tub ntxhais ntawm cov cam khwb cia coil qhuav- hom transformer feem ntau yog tsim los ntawm qib siab -qib, txias-rolled grain-oriented (CRGO) silicon steel. Cov laminations yog precisely stacked thiab nruj nreem clamped los tsim ib tug robust, nruj magnetic Circuit Court. Qhov kev tsim no txo ​​qis kev poob qis (hysteresis thiab eddy tam sim no), ua kom muaj kev ruaj ntseg zoo heev los tiv thaiv luv luv - Circuit Court quab yuam.

 

2.2 Cua txias

Lub winding ntawm cam khwb cia coil qhuav hom transformer feem ntau yog ua los ntawm high -conductivity tooj liab lossis txhuas conductors, uas yog raug mob rau hauv coils thiab ces encapsulated nyob rau hauv epoxy resin los ntawm lub tshuab nqus tsev casting technology. Cov txheej txheem casting no tshem tawm qhov sib txawv ntawm huab cua, muab kev ua haujlwm zoo rwb thaiv tsev, noo noo tsis kam thiab lub zog ntawm lub zog, thaum ua haujlwm zoo los tiv thaiv ib feem ntawm qhov paug tawm thiab ua kom ruaj khov txawm tias nyob hauv ib puag ncig hnyav.

image007

 

2.3 Lub Rooj Sib Tham Kawg

image009

Qhov kawg sib dhos ntawm cam khwb cia coil qhuav hom transformer pib nrog tso lub laminated hlau core rau ntawm lub hauv paus ncej. Tom qab ntawd, lub tshuab nqus tsev- nrum siab-voltage thiab qis-voltage windings yog hoisted thiab concentrically mounted rau ntawm cov tub ntxhais kab, nrog rwb thaiv tsev spacers ntsia kom muaj qhov sib txawv. Tom ntej no, cov hlau lead txuas txuas nrog cov khoom siv davhlau ya nyob twg, cov kiv cua txias (yog tias nruab) thiab ntsuas kub ntsuas cov cuab yeej raug teeb tsa, ua raws li cov khoom siv tiv thaiv. Kev ntsuam xyuas hluav taws xob zaum kawg kom ua raws li kev sib dhos.

 

 

03 Kev Xeem

Kev ntsuam xyuas rau cam khwb cia coil qhuav hom transformers, xws li 1500kVA-15/0.55kV qauv, ua raws li IEC 60076 series cov qauv (1, 3, 11) thiab suav nrog cov khoom tseem ceeb: ntsuas kev tiv thaiv winding (tsim qhov tsis sib npaug tsawg dua lossis sib npaug li 2%), 1 qhov ntsuas qhov ntsuas qhov sib npaug / qhov sib piv ± 1/10), luv-circuit impedance/load poob thiab tsis-load poob/tam sim no kev ntsuam xyuas, dielectric tests (38kV siv voltage rau 60s, 1.1kV induced voltage ntawm 150Hz rau 40s), thiab ib nrab paug xeem (max tsawg tshaj li los yog sib npaug rau 10pC.), tag nrho cov ntaub ntawv pov thawj

Tsis muaj.

Cov khoom kuaj

Chav tsev

Txais

Tus nqi

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntawm winding kuj

/

Maximum kuj unbalance tus nqi

Kab tsis kam: Tsawg dua lossis sib npaug li 2%

HV (kab)

LV (kab)

Hla

0.17%

0.32%

2

Kev ntsuas qhov sib piv ntawm qhov voltage thiab xyuas cov theem hloov chaw

/

Kev kam rau siab ntawm qhov sib piv ntawm tus thawj tapping: ± 1/10

Cov cim kev sib txuas: Dyn11

0.03% ~ 0.19%

Dyn 11

Hla

3

Kev ntsuas luv- Circuit Court Impedance thiab Load Poob

/

kW

kW

t: 120 degree

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

6.01%

8.437

10.437

Hla

4

Kev ntsuas tsis muaj -load poob thiab tam sim no ntawm 90% thiab 110% ntawm qhov ntsuas hluav taws xob

/

kW

I0 :: muab ntsuas tus nqi

P0: muab ntsuas tus nqi

90% ua

0.27

2.331

Hla

100% Yog

0.30

2.59

110% Yog

0.33

2.849

5

Applied Voltage Test

/

HV: 38kV 60s

lwv: 5kv60

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

6

Induced Voltage Withstand Test

/

Kev siv hluav taws xob (KV):

2 ua

Induced voltage (KV): 1.1

Duration(s): 40

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Kev kuaj qhov tso tawm ib nrab

pC ua

Qhov siab tshaj plaws ntawm kev tso tawm ib nrab yuav tsum yog 10 pC

<10

Hla

 

image011001
image013

 

 

04 Packing thiab Shipping

4.1 Ntim

image015

Cov cam khwb cia coil qhuav hom transformer yog ntim rau hauv rooj plaub ntoo muaj zog. Sab hauv, nws yog qhwv nrog kev poob siab- nqus npuas kom tsis txhob muaj kev sib tsoo, ruaj ruaj nrog cov hlau fasteners los tiv thaiv kev hloov, thiab cov ntaub ntawv sab nrauv yog luam tawm nrog cov cim xa khoom, cov qauv khoom thiab qhov hnyav rau kev tuav tau yooj yim.

 

4.2 Shipping

Raws li CIF cov ntsiab lus, cov cam khwb cia coil qhuav hom transformer (hauv cov ntoo ruaj khov) raug xa mus rau Durban. Tus neeg muag khoom npaj kev thauj mus los hauv hiav txwv, them cov khoom thauj, thiab yuav kev pov hwm tiv thaiv kev poob / kev puas tsuaj thaum caij tsheb npav. Kev xa khoom tiav thaum cov khoom nyob rau ntawm lub nkoj nqa, thiab cov khoom thauj yuav raug xa mus rau qhov chaw nres nkoj Durban raws li tau teem tseg.

image017

 

 

05 Site thiab Summary

Nrog nws cov cam khwb cia resin encapsulation muaj zog, txhim khu kev qha qhuav- hom tsim, thiab kev ua tau zoo ib yam, peb cov cam khwb cia qhuav hom transformer sawv ua ib qho kev ntseeg siab rau kev daws teeb meem rau ntau hom kev lag luam, kev lag luam, thiab kev tsim kho vaj tse. Engineered rau kev nyab xeeb, tsis tshua muaj txij nkawm, thiab yoog raws rau kev ua haujlwm sib txawv, nws muab kev txhawb zog ruaj khov kom koj cov haujlwm ua haujlwm zoo. Txawm hais tias koj tab tom nrhiav kev ua haujlwm ntev, ua haujlwm tau zoo, lossis ua raws li cov qauv nruj, peb npaj txhij los pab- cia lub tshuab hloov pauv no txhawb koj lub zog kom ntseeg tau.

image019

 

Cim npe nrov: medium voltage qhuav hom transformers, chaw tsim tshuaj paus, tsum, nqe, nqi

Xa kev nug