1.25 MVA Cast Resin Hom Transformer-0.415/3.3*6.6 kV|Malaysia 2025
Muaj peev xwm: 1000/1250 kVA
Lub hwj chim: 0.415-3.3 / 6.6 kV +2 * 10% kV
Feature: nrog enclosure thiab log

Engineered rau Excellence - Resin Cast Dry Type Transformer, Kev Ua Haujlwm Siab!
01 General
1.1 Project Description
1000/1250 kVA resin cam khwb cia qhuav hom transformer raug xa mus rau Malaysia nyob rau hauv 2025. Lub zog ntawm lub transformer yog 1000/1250 kVA nrog ONAN / ONAF txias. Thawj qhov hluav taws xob yog 0.415d kV, qhov nruab nrab voltage yog 3.3 / 6.6+2 * 10% kV (3.3/3.63/3.96 los yog 6.6/7.26/7.92 kV) nrog ± 2 * 10% tapping ntau yam (NLTC), lawv tsim ib pawg vector ntawm Yd11.
Qhia peb lub siab -kev ua tau zoo 1000/1250kVA resin cam khwb cia qhuav- hom transformer, tsim los rau kev txhim khu kev qha cav thiab kev siv fais fab. Chav tsev muaj zog no nta ntau yam 0.415-3.3/6.6kV tso zis nrog ± 2 × 10% tsis muaj-load kais hloov muaj peev xwm thiab ib qho built-in 3.3kV / 6.6kV selector hloov rau kev hloov pauv hloov tau yooj yim.
Cov nplaim hluav taws-cov khoom siv retardant cam khwb cia ua kom muaj kev nyab xeeb zoo dua yam tsis muaj hluav taws kub lossis hluav taws xob, thaum sib xyaw ua ke cua txias kiv cua thiab ntsuas kub tswj kev ua haujlwm zoo thermal. Nyob rau hauv ib qho kev tiv thaiv enclosure nrog lub log txav mus los, qhov hloov pauv no ua ke muaj kev lag luam -qib durability nrog yooj yim txav mus los.
Qhov zoo tshaj plaws rau qhov xav tau ib puag ncig xws li cov chaw kuaj lub cev muaj zog, kev ua haujlwm tsuas, thiab cov tshuab hluav taws xob tauj dua tshiab, peb cov kev saib xyuas -dawb muab kev tswj hwm qhov hluav taws xob, kev ntseeg tau tshwj xeeb, thiab ua tiav kev thaj yeeb rau koj lub siab -voltage xav tau.
1.2 Technical Specification
1000/1250 kVA resin cam khwb cia qhuav hom transformer specification thiab cov ntaub ntawv ntawv
|
Xa rau
Malaysia
|
|
Xyoo
2025
|
|
Hom
Resin cam khwb cia qhuav hom transformer
|
|
Cov khoom siv tseem ceeb
Grain oriented silicon steel ntawv
|
|
Txuj
IEC60076
|
|
Rated zog
1000/1250 kVA
|
|
Ntau zaus
50 HZ
|
|
Theem
Peb
|
|
Vector pawg
Yd 11
|
|
Hom cua txias
ONAN/ONAV
|
|
Thawj Voltage
0,415d qw
|
|
Secondary Voltage
3.3/6.6+2* 10% Y kV
|
|
Cov khoom siv winding
Tooj
|
|
Impedance
6%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
± 2 * 10% @ theem nrab voltage
|
|
Tsis Load Loss
1.65 KW TSI
|
|
Ntawm Load Loss
8.8 kWs
|
|
Rwb thaiv tsev theem
F
|
1.3 Cov duab kos
1000/1250kVA resin cam khwb cia qhuav hom transformer daim duab kos duab thiab loj.
![]() |
![]() |
02 Kev tsim khoom
2.1 Core
Qhov no resin cam khwb cia transformer nta silicon steel laminated core nrog 45℃skewed pob qij txha thiab epoxy khi, txo tsis muaj -load poob los ntawm 20% piv rau cov qauv. Nrog optimized 1.65-1.72T flux ceev, Tsawg dua los yog sib npaug rau 75K kub nce (Class F), thiab tsawg dua los yog sib npaug rau 55dB suab nrov, nws yog qhov zoo tagnrho rau kev thov xws li kev kuaj cav, kom ntseeg tau tias 20+ xyoo txij nkawm-dawb ua haujlwm.
2.2 Cua txias

Lub transformer winding siv siab -purity tooj liab conductors nrog ntau- txheej rwb thaiv tsev, kom ntseeg tau zoo heev hluav taws xob thiab txhua yam kev ua tau zoo. Lub HV winding siv cov txheej txheej winding rau optimized electric teb tis, thaum lub LV winding siv cov ntawv ci tsim los txhim kho luv luv -circuit resistance.
Encapsulated los ntawm lub tshuab nqus tsev- nrum epoxy resin, lub winding tsim ib tug robust thiab thermally conductive rwb thaiv tsev system, resistant rau ya raws, plua plav, thiab ib nrab paug. Cov resin lub siab thermal conductivity, ua ke nrog ua - hauv cov kav dej txias thiab kiv cua, ua kom ruaj khov kub nce thiab muaj peev xwm tshaj.
2.3 Lub Rooj Sib Tham Kawg
Lub transformer nta modular sib dhos tsim, integrating lub nqus tsev vacuum- nrum epoxy windings nrog siab -permeability silicon steel cores, ruaj los ntawm insulating spacers thiab clamping mechanisms. Nruab nrog off-load kais hloov pauv (± 2 × 10%) thiab 3.3kV / 6.6kV voltage selector, nws suav nrog kev tswj qhov kub thiab txias thiab yuam- cua txias. Optional IP20 enclosures muab kev tiv thaiv zoo, muab kev co kuj, kev saib xyuas -kev ua haujlwm dawb thiab tsis muaj suab nrov.

03 Kev Xeem
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Kev txais txiaj ntsig |
Ntsuas Tus Nqi |
Xaus |
|||
|
1 |
Kev ntsuas ntawm winding kuj |
/ |
Maximum kuj unbalance tus nqi Kab tsis kam: Tsawg dua lossis sib npaug li 2% |
HV (kab) |
LV (kab) |
Hla |
||
|
0.96% |
0.68% |
|||||||
|
0.25% |
||||||||
|
2 |
Kev ntsuas qhov sib piv ntawm qhov voltage thiab xyuas cov theem hloov chaw |
/ |
Kev kam rau siab ntawm qhov sib piv ntawm tus thawj tapping: ± 1/10 Cov cim kev sib txuas: Yd11 |
-0.26% ~ 0.15% Yd 11 |
Hla |
|||
|
3 |
Kev ntsuas tsis muaj -load poob thiab tam sim no ntawm 90%, 100% thiab 110% ntawm qhov ntsuas hluav taws xob |
/ kW |
I0 :: muab ntsuas tus nqi P0: muab ntsuas tus nqi |
90% ua |
100% UA |
110% Yog |
Hla |
|
|
0.27 1.395 |
0.30 1.551 |
0.33 1.706 |
||||||
|
4 |
Load Losses, impedance Voltage |
/ kW kW |
t: 120 degree Z%: ntsuas tus nqi Pk: ntsuas tus nqi Pt: ntsuas tus nqi |
6.06% 6.173 8.148 |
Hla |
|||
|
5 |
Applied Voltage Test |
/ |
HV: 20kV 60s lwv: 3kv60 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|||
|
6 |
Induced Voltage Withstand Test |
/ |
Kev siv hluav taws xob (kV): 2 ua Induced voltage (kV): 0.83 Duration(s): 40 Zaus (HZ): 150 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|||
|
7 |
Kev kuaj qhov tso tawm ib nrab |
pC ua |
Qhov siab tshaj plaws ntawm kev tso tawm ib nrab yuav tsum yog 10 pC |
<10 |
Hla |
|||


04 Packing thiab Shipping


05 Site thiab Summary
SCOTECH Resin Cast Dry-Type Transformers teeb tsa cov qauv tshiab nrog kev saib xyuas- ua haujlwm pub dawb, lub zog dielectric zoo dua, thiab lub neej ntev.
Los ntawm cov chaw lag luam hnyav mus rau cov ntawv thov daim phiaj ntse, peb ISO- ntawv pov thawj kev tsim khoom thiab cov kev daws teeb meem ua kom muaj kev nyab xeeb, ua tau zoo, thiab hloov hluav taws xob ruaj khov. Hu rau peb pab pawg engineering hnub no rau koj qhov kev daws teeb meem!

Cim npe nrov: cam khwb cia resin hom transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
630 kVA Cast Resin Dry Type Transformer-66.6/0.55 kV...
630 kVA 3 Theem Qhuav Hom Transformer-6.6/0.55 kV|So...
2500 kVA Qhuav Transformer-10/0.4 kV|Georgia 2025
500 kVA Qhuav Resin Transformer-13.8/0.46 kV|South A...
160 kVA Sab Hauv Tsev Qhuav Hom Transformer-10/0.4 k...
630 kVA Peb Theem Qhuav Hom Transformer-10/0.4 kV|Ge...
Xa kev nug