15 MVA Step Up Fais Fab Transformer-4.16/69 kV|Guyane xyoo 2023

15 MVA Step Up Fais Fab Transformer-4.16/69 kV|Guyane xyoo 2023

Lub teb chaws: Guyana 2023
Muaj peev xwm: 15MVA
Lub Zog: 4.16 / 69kV
Feature: nrog OLTC
Xa kev nug

 

 

step up power transformer

Lub zog ruaj khov, txhawb nqa lub neej yav tom ntej - xaiv peb lub zog hloov hluav taws xob los teeb tsa txhua lub zog watt!

 

01 General

1.1 Project Background

Qhov no 15 MVA fais fab roj immersed transformer yog tsim los ntawm peb nyob rau hauv 2023, rated zog ntawm lub transformer yog 15 MVA, thawj voltage yog 4.16 kV nrog +4 × 1.667% rau - 12 × 1.667% tapping ntau yam (OLTC), qhov tsawg voltage yog 69. Peb tau tsim lub OLTC kauj ruam ntawm lub zog hloov pauv hauv cov khoom siv tau ua ntau qhov kev hloov pauv loj, nrog lub teeb yuag, qhov loj me, me me, ib feem me me, poob qis, tsis tshua muaj suab nrov, muaj kev ntseeg siab, kev tiv thaiv tam sim luv luv, tuaj yeem txo cov nqi hluav taws xob ntau, cov nqi khiav lag luam thiab cov txiaj ntsig kev lag luam. YNd11 hom kev sib txuas muab cov kab sib txuas zoo sib xws, thaum tiv thaiv kev sib raug zoo thib peb thiab txhim kho daim phiaj ua haujlwm zoo. Qhov siab voltage sab (Y) yog lub hnub qub kev sib txuas nrog qhov nruab nrab ntawm qhov nruab nrab uas tuaj yeem txuas ncaj qha lossis los ntawm cov av tiv thaiv kom muab cov hluav taws xob ruaj khov.

 

1.2 Technical Specification

100 MVA fais fab transformer specification thiab cov ntaub ntawv

Xa rau
Guyane
Xyoo
2023
Qauv
SZ-15 MVA-69kV
Hom
Roj Immersed Fais Fab Transformer
Txuj
IEEE C57.12.00 Nws
Rated zog
15 MVA
Ntau zaus
60 tzs
Theem
Peb
Hom cua txias
ONAN
Thawj Voltage
69kv ua
Secondary Voltage
4, 16 kv
Cov khoom siv winding
Tooj
Vector Group
YNd11
Impedance
9.10%
Coj mus rhaub Changer
OLTC
Tapping Range
+4*1.667%~-12*1.667%@HV sab
Tsis Load Loss
10.234KW (20 degree)
Ntawm Load Loss
64.220KW (85 degree)
Khoom siv
Standard Configuration
Lus hais
N/A

 

1.3 Cov duab kos

15 MVA fais fab transformer daim duab kos duab thiab loj.

step up power transformer diagram step up power transformer nameplate

 

step up power transformer wiring diagram 15mva power transformer drawing

 

 

02 Kev tsim khoom

2.1 Core

Peb lub tuam txhab txais yuav high-conductive volt-oriented txias- dov silicon steel ntawv, tsis muaj- qhov khi, ncej qauv, d- zoo li tus yoke qauv rau coil es tsis txhob loj - cheeb tsam platform, stepped pob qij txha. Cov tub ntxhais muaj me me burr thiab qis lamination coefficient. Qhov tsis muaj-load poob, tsis muaj-load tam sim no thiab lub suab nrov tau txo qis los ntawm ntau- theem pob qij txha ntawm cov tub ntxhais hlau.

core of the transformer

 

2.2 Cua txias

Continuous winding design

1. Nruam winding tsim: Lub tangle ib tug nruam hom thiab cov phaj puab ib tug nruam hom tsim yog siv, uas yuav pab txhim kho lub longitudinal capacitance tis ntawm lub kauj nyob rau hauv lub impulse voltage. Qhov kev tsim no tuaj yeem txo qhov concentration ntawm cov hluav taws xob hauv hluav taws xob, kom lub kauj muaj hluav taws xob zoo dua ntawm kev kub siab.

2. Cov qauv kev coj noj coj ua ntawm cov roj: cov qauv coj cov roj ncig yog siv los pab txo qis cua kub nce. Qhov kev tsim no tswj qhov kub hauv lub kauj thiab pab txhim kho kev nyab xeeb thiab ruaj khov ntawm transformer.

 

2.3 Tank

1. Sealing kev ua tau zoo: Lub tank roj tau ntim nrog kev txwv nres kom ntseeg tau tias cov roj hluav taws xob hloov hluav taws xob tuaj yeem raug kaw zoo hauv cov roj tank kom tsis txhob xau thiab oxidation ntawm cov roj insulating.

2. Anti- kev kho corrosion: Lub tank roj yog ua los ntawm corrosion- cov ntaub ntawv resistant, thiab cov xim yuav tsum tau siv rau cov khoom siv hauv tsev yog siv los txhim kho corrosion kuj ntawm cov roj tank thiab txuas lub neej kev pab cuam.

3. Kev kuaj xyuas cov dej xau: cov vuam thiab lub foob ntawm lub tank tau dhau los ua peb qhov kev kuaj pom cov pa tawm (fluorescence, zoo siab, qhov tsis zoo ntawm qhov ntsuas qhov tsis zoo) txhawm rau xyuas kom nruj thiab kev nyab xeeb.

oil tank

 

2.4 Kev sib dhos zaum kawg

oil conservator

Kev sib dhos zaum kawg ntawm cov roj-immersed fais fab transformer ua los ntawm lub tuam txhab transformer feem ntau muaj ob peb kauj ruam tseem ceeb:

1. Core Assembly: Cov tub ntxhais sib dhos feem ntau yog thawj kauj ruam hauv kev sib dhos zaum kawg. Qhov no muaj xws li stacking thiab clamping ntawm transformer core, uas yog tsim los ntawm high - qib hluav taws xob steel laminations. Cov tub ntxhais yuav tsum tau sib sau ua ke kom meej meej kom paub meej cov khoom sib nqus zoo thiab cov tub ntxhais poob tsawg.

2. Windings Installation: Cov txheej txheem suav nrog kev txhim kho qhov siab -voltage (HV) thiab qis-voltage (LV) windings mus rau qhov tseem ceeb. Cov windings feem ntau yog insulated tooj liab conductors uas tau ua tib zoo muab tso, txheej, thiab txuas raws li tus qauv transformer.

3. Tank thiab Radiator Installation: Lub tank transformer, nrog rau cov kev cuam tshuam cov radiators los yog txias fins, yog ntsia rau theem no. Lub tank muab vaj tse rau cov tub ntxhais thiab windings thiab tuaj yeem kaw kom muaj cov roj insulating.

4. Rwb thaiv tsev, kev sib txuas, thiab cov khoom siv: Cov khoom siv rwb thaiv tsev, xws li bushings, leads, kais changers, thiab lwm yam khoom siv tau nruab thiab txuas nrog cov windings. Kev rwb thaiv tsev thiab kev txhawb nqa ntxiv tau ntxiv los ua kom muaj kev nyab xeeb thiab txhim khu kev qha.

5. Roj Filling thiab Sealing: Lub transformer yog ntim nrog insulating roj los ntawm kev ua tib zoo tswj. Thaum ua tiav, lub transformer raug kaw kom tsis txhob ya raws ingress thiab tswj cov roj kev ncaj ncees.

 

 

03 Kev Xeem

Rwb thaiv tsev tiv thaiv: siv los xyuas qhov zoo ntawm cov ntaub ntawv rwb thaiv tsev kom tiv thaiv kev puas tsuaj. Nws yog ib qho tsim nyog los xyuas kom meej tias lub transformer yog offline thiab siv cov cuab yeej ntsuas ntsuas tsim nyog.

Kev ntsuas hluav taws xob zoo: Kev ntsuas hluav taws xob siab yog siv rau lub tshuab hluav taws xob thaum lub sijhawm kuaj sim nws cov kev ua haujlwm rwb thaiv tsev ntawm qhov ntsuas hluav taws xob. Qhov no yuav tsum tau ua raws li cov txheej txheem kev ua haujlwm nyab xeeb thiab lav tias cov cuab yeej kuaj tau raws li cov qauv.

Kev ntsuas qhov tsis zoo: Cov khoom ntsuas no tshuaj xyuas qhov kev ua haujlwm ntawm rwb thaiv tsev ntawm lub tshuab hluav taws xob qis. Nws kuj tseem yuav tsum tau ua cov kev ntsuas kev nyab xeeb kom tsim nyog los xyuas kom meej tias qhov kev sim ua tiav zoo.

Ac resistance test: Kuaj qhov kev tiv thaiv hauv av ntawm lub winding kom ntseeg tau qhov kev ntseeg ntawm cov av.

Lub zog poob thiab tsis muaj- kev ntsuas tam sim no: Cov kev sim no yog siv los ntsuas qhov tsis muaj -load kev ua haujlwm thiab kev ua haujlwm ntawm lub tshuab hloov pauv.

Load test: Los ntawm kev siv lub ntsuas load, qhov kev ua haujlwm tsis zoo ntawm lub tshuab hloov pauv raws li qhov ntsuas ntsuas tau ntsuas.

 

transformer type test

 

 

04 Packing thiab Shipping

4.1 Ntim

Kev ntim khoom thiab kev thauj mus los ntawm cov roj-immersed fais fab transformer uas tsim los ntawm lub tuam txhab transformer muaj ob peb kauj ruam tseem ceeb los xyuas kom meej qhov kev nyab xeeb thiab ruaj ntseg ntawm cov khoom. Hauv qab no yog cov lus piav qhia dav dav ntawm cov txheej txheem:

1. Kev ntim khoom: Thaum lub tshuab hloov pauv tau dhau los ua qhov kawg, suav nrog kev kuaj thiab kev kuaj xyuas zoo, nws tau npaj rau kev ntim khoom. Cov khoom siv hluav taws xob hloov pauv, suav nrog lub tank, tub ntxhais, windings, thiab cov khoom siv sib txuas, tau ua tib zoo saib xyuas thiab tiv thaiv kev thauj mus los. Cov khoom ntim khoom, xws li ntoo crates, ua npuas ncauj padding, thiab strapping, raug xaiv los muab cov cushioning txaus thiab kev tiv thaiv.

2. Kev Tiv Thaiv Kev Tiv Thaiv thiab Kev Tiv Thaiv Corrosion: Cov khoom siv hluav taws xob hloov pauv tau raug kho nrog cov tshuaj tiv thaiv tsim nyog los tiv thaiv corrosion thaum thauj thiab khaws cia.

power transformer specification

 

4.2 Shipping

15mva power transformer manufacturer

Kev ruaj ntseg rau kev thauj mus los: Cov khoom siv hluav taws xob hloov pauv tau ruaj ntseg hauv lub ntim kom tsis txhob txav mus los thiab ua kom muaj kev ruaj ntseg thaum lub sijhawm thauj mus los. Kev ruaj ntseg thiab sib npaug yog tswj xyuas kom tsis txhob muaj kev ntxhov siab rau txhua qhov ntawm lub transformer.

Kev Qhia Txog Tus Kheej thiab Cov Ntaub Ntawv: Txhua qhov ntim cov khoom tau sau npe, thiab cov ntaub ntawv ntxaws ntxaws tau npaj, suav nrog cov npe ntim khoom, cov lus qhia thauj khoom, thiab cov ntawv tso cai lossis ntawv pov thawj xav tau rau kev thauj mus los.

Kev Thauj Khoom thiab Kev Thauj Khoom: Cov khoom ntim tau ntim rau hauv cov tsheb thauj khoom tsim nyog, xws li cov tsheb thauj mus los lossis cov thawv thauj khoom, siv cranes lossis lwm yam khoom siv. Kev thauj mus los tshwj xeeb yuav xav tau rau cov hloov pauv loj lossis hnyav.

Kov thiab Unloading: Thaum lub sij hawm thauj mus los, lub transformer Cheebtsam yog ua tib zoo saib xyuas kom tsis txhob muaj kev puas tsuaj. Thaum tuaj txog ntawm qhov chaw, saib xyuas thaum lub sijhawm thauj khoom kom muaj kev nyab xeeb thiab kev tuav tau zoo

 

 

05 Site thiab Summary

Kev npaj: xyuas kom lub hauv paus tiaj tus thiab ruaj khov, thiab tag nrho cov cuab yeej tau npaj txhij.

Kev Thauj Mus Los thiab Hoisting: Thauj lub transformer mus rau qhov chaw, hoist nws mus rau hauv txoj hauj lwm, thiab ruaj ntseg.

Kev Txuas Txuas: Txhim kho cov khoom siv xws li cov khoom siv cua txias, cov roj khaws cia, thiab cov bushings.

Kev Sib Txuas Hluav Taws Xob: Ua kom tiav cov kev sib txuas rau cov kab hluav taws xob siab thiab tsis tshua muaj hluav taws xob lossis cov busbars thiab xyuas kom muaj av zoo.

Roj Filling thiab Kev Tshuaj Xyuas: Sau lub tshuab hluav taws xob nrog cov roj insulating thiab xyuas cov roj qib thiab qhov zoo.

Kev Ntsuas thiab Kev Ua Haujlwm: Ua cov kev ntsuas hluav taws xob xws li rwb thaiv tsev, kev tiv thaiv, thiab kev ntsuas piv.

Kev sim ua haujlwm: Ua haujlwm sim ua haujlwm raws li kev thauj khoom thiab paub meej tias txhua yam tsis ua ntej ua haujlwm zaum kawg.