75 kVA 3 Phase Ncej Transformer-13.8/0.22 kV|Guyane xyoo 2024

75 kVA 3 Phase Ncej Transformer-13.8/0.22 kV|Guyane xyoo 2024

Lub teb chaws: Guyana 2024
Peev xwm: 50kVA
Lub Zog: 13.8 / 0.22kV
Feature: nrog OCTC
Xa kev nug

 

 

75 kVA 3 phase pole transformer

Kev tshaj lij thiab txhim khu kev qha, Kev siv hluav taws xob zoo- Peb-theem ncej-mounted transformer, kom ruaj khov zog rau txhua kilowatt- teev.

 

01 General

1.1 Project Background

Lub 75 kVA peb theem ncej mounted transformer tau xa mus rau Guyana xyoo 2024. Lub zog ntsuas ntawm lub transformer yog 75 kVA. Thawj qhov voltage ntawm lub transformer yog 13.8 kV thiab theem nrab voltage yog 0.22 kV. Cov pab pawg sib txuas yog Dyn1, thiab cov cua txias yog ONAN. Peb theem ncej mounted transformers tsim los ntawm SCOTECH muaj ib tug tsim nyog rwb thaiv tsev qauv thiab muaj zog xob laim cuam tshuam kuj. Uniform flux faib, qis ntxiv poob, tsis muaj qhov tshwm sim hauv zos overheating. Tsawg electromagnetic quab yuam, tsis tshua muaj kev vibration thiab suab nrov. Kev faib tawm qhov kub thiab txias yog qhov sib xws thiab cov nyhuv txias yog qhov zoo. Cov yam ntxwv magnetization muaj siab linearity thiab siab linearity coefficient.

Peb 150 kVA peb theem ncej mounted transformer tau tsim los nrog cov cuab yeej siv siab heev thiab siv cov khoom zoo thiab cov khoom uas ua rau muaj kev ntseeg tau zoo thiab lub sijhawm ua haujlwm ntev. Peb lav tias txhua lub tshuab hluav taws xob peb xa tuaj tau dhau qhov kev lees paub lees paub los xyuas kom meej qhov ua tau zoo thiab kev ntseeg siab. Los ntawm kev sib tham thawj zaug thiab hais lus rau kev tsim khoom, kev teeb tsa, kev ua haujlwm, kev cob qhia, thiab tom qab- kev muag khoom, peb muab cov kev daws teeb meem ua tiav. Peb cov transformers tam sim no nyob rau hauv kev lag luam ruaj khov thoob plaws ntau tshaj 50 lub teb chaws thoob ntiaj teb. Kev cog lus rau kev ua tau zoo thiab kev pabcuam, peb siv zog ua koj tus neeg muag khoom hloov pauv uas ntseeg siab thiab ntev - tus khub ua lag luam.

 

1.2 Technical Specification

75 kVA peb theem ncej mounted transformer specification thiab cov ntaub ntawv ntawv

Xa rau
Guyane
Xyoo
2024
Hom
Peb Theem Ncej Mounted Transformer
Txuj
IEEE C57.12.00-2021
Rated zog
75kVA ua
Ntau zaus
60 tzs
Theem
3
Xim
ANSI Grey 70 #
Hom cua txias
ONAN
Thawj Voltage
13.8 kV 2
Secondary Voltage
0.22 / 0.127 kV
Cov khoom siv winding
Aluminium
Impedance
2%
Ua siab ntev
±7.5%
Kev ua tau zoo
Ntau dua lossis sib npaug li 98.63%
Tapping Range
± 2 * 2.5% @ thawj sab
Cov khoom siv tseem ceeb
Grain oriented silicon steel ntawv
Ua kua insulating
PCB dawb Transformer Mineral Roj
Tsis Load Loss
Tsawg dua lossis sib npaug li 0.32KW
Ntawm Load Loss
Tsawg dua lossis sib npaug li 0.98KW
Khoom siv
Standard Configuration

 

1.3 Cov duab kos

75 kVA peb theem ncej mounted transformer daim duab kos duab thiab loj.

75 KVA three phase pole mounted transformer diagram 75 KVA three phase pole mounted transformer nameplate

 

 

02 Kev tsim khoom

2.1 Core

Cov tub ntxhais yog ua los ntawm high-zoo txias- dov silicon steel ntawv, domestic zoo heev transverse shear kab, shear burr<0.02, full oblique joint, no punching, no stacking iron wheel process; The double H adhesive makes the three columns of the core become a tight, flat and compact whole, effectively reducing the no-load loss, no-load current and noise of the transformer.

silicon steel sheet iron core of 3 phase pole transformer

 

2.2 Cua txias

aluminum wire coil of 3 phase pole transformer

Lub transformer coil txais siab -purity aluminium hlau, uas zoo txo ​​qhov poob, lub ncoo thiab nyob twj ywm yog sib npaug, lub teb hluav taws xob yog ib yam, thiab kev ntseeg tau nce. Lub puab winding kev txhawb zog yog ntxiv dag zog rau nws stability thiab tiv thaiv instability thiab deformation.

Cov ntawv ci winding muaj cov ntawv ci sib txuas, feem ntau yog ua los ntawm tooj liab lossis txhuas. Cov foils no tau sib nrug deb thiab sib cuam tshuam los tsim cov qauv ntawm winding.

 

Qhov kev tsim no ua rau cov ntawv ci winding tuaj yeem ua kom cov cua sov zoo dua thaum raug cov tam sim no siab, tab sis kuj txo qhov tsis kam thiab inductance ntawm winding, thiab txhim kho cov hluav taws xob kev ua tau zoo ntawm winding. Qhov loj tshaj plaws ntawm cov ntawv ci winding yog tias nws yog dov rau ntawm lub tshuab tshwj xeeb winding, uas muaj cov qib siab ntawm automation thiab muab cov khoom tsim tau zoo thiab cov khoom zoo. Lub lem, uas yog, lub interlayer thiab longitudinal capacitance yog loj, lub kauv lub kaum yog tshem tawm, luv luv - Circuit Court tej yam kuj muaj zog, mechanical zog yog siab, kev tsim yog yooj yim, axial thiab radial yuam kev yog me me, lub geometric loj yog ib qho yooj yim los xyuas kom meej, lub tig yog kuj nruj nreem bubbles. Cov ntawv ci winding kuj tseem tuaj yeem txo qhov tso tawm ib nrab thiab txhim kho kev ua haujlwm rwb thaiv tsev ntawm winding.

2.3 Tank

Rau thawj cov qauv kev sib khi, tshwj xeeb tshaj yog nyob rau hauv qhov chaw uas cov roj to tau yooj yim tshwm sim, pib los ntawm cov khoom siv tswj xyuas kom ntseeg tau tias cov hlau tsis xeb, pob, khawb, rauj, kev ua haujlwm tshwj xeeb ntawm cov roj tank sealing ib feem, thiab tag nrho cov tha xim ntawm lub thawv, tshem tawm lub kaum ntse ntse burrs thiab vuam slag tsim nyob rau hauv kev ua ntawm lub thawv, thiab ntxiv dag zog rau adhesion ntawm cov xim.

75 kVA 3 phase pole transformer oil tank

 

2.4 Kev sib dhos zaum kawg

75 kVA 3 phase pole transformer active part
inside of 75 kVA 3 phase pole transformer

 

 

03 Kev Xeem

Tsis muaj.

Cov khoom kuaj

Chav tsev

Txais

Tus nqi

Ntsuas Tus Nqi

Xaus

1

Kev ntsuas ntsuas

%

Kev tiv thaiv siab tshaj plaws tsis sib npaug tsawg dua lossis sib npaug li 4%

0.43

Hla

2

Kev ntsuas ntsuas

%

Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5%

-0.08~-0.01

Hla

3

Theem -Kev Ntsuas Kev Sib Txuas

/

Dyn 1

Dyn 1

Hla

4

Tsis muaj -Load Losses thiab Excitation Current

%

kW

I0 : muab ntsuas tus nqi

P0: muab ntsuas tus nqi

qhov kam rau tsis muaj load poob yog +0%

1.21

0.266

Hla

5

Load Losses Impedance Voltage thiab Efficiency

%

kW

kW

t:85 ua

Z%: ntsuas tus nqi

Pk: ntsuas tus nqi

Pt: ntsuas tus nqi

Qhov kam rau ua impedance yog ± 7.5%

lub kam rau tag nrho load poob yog +0%

Kev ua haujlwm tsis tsawg dua 98.74%

2.17

0.832

1.098

98.80

Hla

6

Applied Voltage Test

kV ua

HV/: 34kV 60s

LV/: 10kV 60s

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

7

Induced Voltage Withstand Test

kV ua

Kev siv hluav taws xob (kV):

2 ua

Duration(s): 48

Zaus (HZ): 150

Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim

Hla

8

Kev Xeem Leakage

kPa ua

Kev siv siab: 20kPA

Duration: 12h

Tsis muaj leakage thiab tsis muaj

Kev puas tsuaj

Hla

9

Rwb thaiv tsev Resistance Measurement

HV-LV to Av:

LV-HV to Av:

HV&LV to Av

53.4

50.6

48.8

/

10

Roj Dielectric Test

kV ua

Ntau dua lossis sib npaug li 45

52.83

Hla

 

75 kVA 3 phase pole mounted transformer testing
75 kVA 3 phase pole transformer testing

 

 

04 Packing thiab Shipping

75 kVA 3 phase pole transformer packing

75 kVA 3 phase pole transformer transportation

 

05 Site thiab Summary

Ua tsaug rau koj siv sijhawm los kawm txog peb Ib Leeg -Phase Ncej-Mounted Transformer! Hauv cov tshuab hluav taws xob niaj hnub no, peb cov khoom tsis yog ib qho khoom siv hluav taws xob zoo xwb tab sis kuj yog lub hauv paus ruaj khov rau kev ua haujlwm ruaj khov. Peb tau cog lus los muab cov kev daws teeb meem zoo rau peb cov neeg siv khoom, sib koom ua ke cov cuab yeej txhim khu kev qha nrog cov tswv yim zoo ib puag ncig kom ua kom muaj zog sib kis tau zoo. Kev xaiv peb txhais tau hais tias xaiv lub zog ruaj khov rau yav tom ntej. Peb tos ntsoov yuav ua haujlwm nrog koj los tsim kom muaj lub zog ntse dua thiab ruaj khov dua qub ua ke!

75 kVA 3 phase pole mounted transformer

 