4390 KVA Transformer-24/0.63 KV|Jamaica 2025
Peev xwm: 4390 kVA
Qhov hluav taws xob: 23.9GrdY / 13.8-0.63D kV
Feature: C5M Anti- qib corrosion

Xaiv lub ncoo mounted transformers kom muaj txiaj ntsig, kev sib cog lus zog.
01 General
1.1 Project Description
4390 kVA peb theem ncoo mounted transformer raug xa mus rau Jamaica hauv 2025. Lub zog ntsuas ntawm lub transformer yog 4390 kVA nrog ONAN txias. Qhov siab voltage yog 23.9GrdY / 13.8 kV nrog ± 2 * 2.5% tapping ntau yam (NLTC), qhov tsawg voltage yog 0.63D kV, lawv tsim ib pawg vector ntawm YNd1.
Engineered rau superior kev ua tau zoo nyob rau hauv niaj hnub hluav taws xob tes hauj lwm, peb Pad Mounted Transformer muab tshwj xeeb kev cia siab rau thiab efficiency. Chav tsev muaj zog no muaj peb theem -theem, peb-limb core optimized rau 50Hz kev ua haujlwm, ua tiav 99.2% kev ua haujlwm zoo nrog 7.5% impedance rau kev ua haujlwm ruaj khov. Sau nrog eco- phooj ywg FR3 dielectric kua, nws txhim khu kev nyab xeeb hluav taws thiab ua haujlwm ntev. Qhov tseem ceeb rau nws cov qauv tsim yog kev sib koom ua ke Grounding Shield thiab Isolation Screen Grounding Sleeve, uas ua kom muaj kev nyab xeeb siab tshaj plaws los ntawm kev siv hluav taws xob cuam tshuam thiab tiv thaiv cov neeg ua haujlwm. Nyob rau hauv ib tug resilient 304 stainless hlau enclosure tiav nyob rau hauv ib tug corrosion{12}}resistant, C5M-qib dawb hmoov tsho tiv no (RAL 9003), nws yog tsim los mus rau lub feem ntau xav tau ib puag ncig tej yam kev mob.
Nrog lub peev xwm ua haujlwm tau zoo ntawm 4330kVA ntawm 45℃thiab 4075kVA ntawm 50 degree, lub tshuab hloov pauv no yog qhov ruaj ntseg, ruaj khov, thiab ntse lub hauv paus rau koj lub zog faib khoom.
1.2 Technical Specification
4390 kVA ncoo mounted transformer specifications hom thiab cov ntaub ntawv ntawv
|
Xa rau
Jamaica
|
|
Xyoo
2025
|
|
Hom
Pad mounted transformer
|
|
Txuj
IEC 60076: Ua
|
|
Rated zog
4 390 kVA
|
|
Ntau zaus
50 HZ
|
|
Theem
3
|
|
Pub
Loop
|
|
Pem hauv ntej
Tuag
|
|
Hom cua txias
KNAN
|
|
Thawj Voltage
23.9 GrdY / 13.8 kV
|
|
Secondary Voltage
0 ,69kv
|
|
Cov khoom siv winding
Tooj
|
|
Vector Group
YNd1
|
|
Impedance
7.5%
|
|
Kev ua tau zoo
99.2%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
±2*2.5%
|
|
Tsis Load Loss
3.95 kWm
|
|
Ntawm Load Loss
28 kWm
|
1.3 Cov duab kos
4390 kVA ncoo mounted transformer daim duab kos duab thiab loj.
![]() |
![]() |
02 Kev tsim khoom
2.1 Core

Peb peb -limb core, crafted los ntawm premium silicon steel, yog engineered rau siab tshaj plaws kev txuag hluav taws xob thiab tsawg suab nrov. Nws ncaj qha xa cov nqi hluav taws xob qis dua thiab ua haujlwm ntsiag to, ua rau nws yog qhov zoo tshaj plaws, cov neeg nyob sib ze - kev xaiv tus phooj ywg rau tus nqi - faib hluav taws xob zoo thiab ruaj khov.
2.2 Cua txias
Peb txhua tus - tooj liab winding system ua ke HV ntawv ci thiab LV hlau rau kev ua haujlwm siab tshaj plaws thiab ua haujlwm kub. Qhov kev tsim zoo tshaj no ua kom tsis muaj zog poob qis, txhim kho luv luv - lub zog hluav taws xob, thiab txuas ntxiv lub neej transformer - xa tus nqi tseeb los ntawm kev txo nqi khiav haujlwm.

2.3 Tank

Peb 304 stainless hlau tank nrog C5M kev tiv thaiv tiv thaiv ib puag ncig hnyav hnyav. Kev ua tiav dawb huv nyob ruaj khov thiab xeb- pub dawb rau ntau xyoo, tshem tawm cov nqi tu thiab ua kom muaj kev txhawj xeeb- pov thawj kev ua haujlwm hauv ntug dej hiav txwv lossis chaw lag luam.
2.4 Kev sib dhos zaum kawg
Peb lub rooj sib txoos zaum kawg ua kom muaj kev sib koom ua ke zoo kawg nkaus ntawm lub siab -cov tub ntxhais ua haujlwm tau zoo, tag nrho - tooj liab windings, thiab stainless hlau tank. Qhov kev sib xyaw ua ke no muab kev lees paub kev ua haujlwm nrog cov nqi qis hauv lub neej, muab kev saib xyuas ntau xyoo- ua haujlwm dawb.

03 Kev Xeem
Ua raws li koj cov kev xav tau tseem ceeb rau kev ntseeg siab, kev ua tau zoo, thiab kev pom zoo, peb peb -theem pad mounted transformer tau dhau los ua kev sim ntsuas uas dhau mus dhau qhov kev ua raws cai. Ua raws li IEC cov qauv, cov kev ntsuam xyuas tseem ceeb suav nrog cov kev kuaj xyuas qhov ua kom tsis muaj zog (max unbalance rate 4.59%), qis tsis muaj-load poob (3.564kW), robust dielectric withstand, thiab 24-teev xau{12}} pov thawj pov thawj. Peb sawv tawm los ntawm kev xa cov kev ntsuas tau zoo: 99.28% kev ua haujlwm zoo (dhau li 99.2% yam tsawg kawg nkaus), kev sib raug zoo theem (YNd1). Peb muab cov ntaub ntawv qhia meej, ua tau zoo thiab kev nug kom sai, muab kev ntseeg siab rau koj tias koj lub tshuab hloov hluav taws xob muaj zog, ruaj khov, thiab txhawb nqa los ntawm cov chaw tsim khoom cog lus rau koj txoj haujlwm ua tiav.
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Txais Tus nqi |
Ntsuas Tus Nqi |
Xaus |
|
1 |
Kev ntsuas ntsuas |
% |
Maximum kuj unbalance tus nqi |
4.59 |
Hla |
|
2 |
Kev ntsuas ntsuas |
% |
Qhov sib txawv ntawm qhov sib piv ntawm qhov hluav taws xob ntawm tus thawj coj tapping: Tsawg dua lossis sib npaug li 0.5% Cov cim kev sib txuas: YNd1 |
-0.05% ~ -0.03% |
Hla |
|
3 |
theem- kev xeem sib txheeb |
/ |
YNd1 |
YNd1 |
Hla |
|
4 |
Tsis muaj -load poob thiab excitation tam sim no |
/ |
I0 :: muab ntsuas tus nqi |
0.23% |
Hla |
|
P0: muab ntsuas tus nqi |
3, 564 kWm |
||||
|
qhov kam rau tsis muaj load poob yog +15% |
/ |
||||
|
5 |
Load poob impedance voltage thiab efficiency |
/ |
t:75 ua Qhov kam rau ua impedance yog ± 10% lub kam rau tag nrho load poob yog +10% |
/ |
Hla |
|
Z%: ntsuas tus nqi |
7.06% |
||||
|
Pk: ntsuas tus nqi |
28.162 kWm |
||||
|
Pt: ntsuas tus nqi |
31.726 kWm |
||||
|
Kev ua haujlwm tsis tsawg dua 99.2% |
99.28% |
||||
|
6 |
Applied Voltage Test |
kV ua |
LV/: 10kV 60s |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
7 |
Induced Voltage Withstand Test |
kV ua |
Kev siv hluav taws xob (KV): 2Ur |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
|
Duration(s): 40 |
|||||
|
Zaus (HZ): 150 |
|||||
|
8 |
Kev Xeem Leakage |
kPa ua |
Kev siv siab: 50kPA |
Tsis muaj leakage thiab tsis muaj Kev puas tsuaj |
Hla |
|
Duration: 24h |
|||||
|
9 |
Rwb thaiv tsev Resistance Measurement |
GΩ |
HV-LV to Av |
1.87 |
/ |
|
LV-HV to Av |
1.15 |
||||
|
HV&LV to Av |
0.832 |


04 Packing thiab Shipping
4.1 Ntim

Peb xa txhua chav nyob rau hauv kev cai - ua ntoo crates, engineered rau kev tiv thaiv siab tshaj plaws thaum caij tsheb npav. Kev ntim khoom ruaj khov no ua kom koj lub tshuab hloov pauv tuaj txog ntawm qhov chaw zoo meej, npaj tau - rau - nruab qhov xwm txheej, tshem tawm cov kev pheej hmoo nyiaj txiag thiab qhov project qeeb cuam tshuam nrog kev puas tsuaj ntawm kev thauj mus los.
4.2 Shipping
Peb txawj tswj tag nrho DDU thauj saw ntawm koj peb -theem ncoo-mounted transformer rau PAC Kingston Airport Ltd. (KIN). Peb qhov kev npaj ua kom zoo, los ntawm cov ntoo tshwj xeeb- lub thawv ntim khoom uas tshaj li cov qauv kev lag luam mus rau KIN cov txheej txheem thauj khoom tshwj xeeb thiab 24/7 hluav taws xob kev lis kev cai, ua kom koj cov khoom muaj nqis tseem ceeb tuaj txog nyab xeeb thiab raws sijhawm. Qhov no seamless, hassle - xa dawb rau koj qhov chaw uas tau teev tseg txo cov kev pheej hmoo ntawm kev puas tsuaj thiab qhov project qeeb, muab kev thaj yeeb nyab xeeb rau koj.

05 Site thiab Summary
Thaum koj qhov project qhov kev vam meej nyob ntawm qhov tsis hloov pauv lub zog thiab ntawm - lub sijhawm xa khoom, koj xav tau qhov tseeb ntawm koj cov khoom siv thiab koj tus neeg xa khoom. Peb peb -phase pad mounted transformers yog engineered rau raws nraim uas - xa unmatched kev ntseeg tau kom koj cov kev khiav hauj lwm. Tab sis peb qhov zoo dua mus ntxiv: nws yog peb txoj kev cog lus rau koj lub sijhawm. Nrog rau kev nruj me ntsis ua ntej- kev xa khoom xa tuaj thiab cov khoom siv thoob ntiaj teb ua tau zoo, peb xyuas kom koj lub tshuab hloov pauv tuaj txog ntawm qhov chaw raws li tau cog lus tseg, npaj rau qhov teeb meem - kev teeb tsa dawb. Tsis txhob cia qhov kev pheej hmoo ua haujlwm lossis ncua sij hawm ua rau koj qhov project. Xaiv qhov kev ntseeg siab uas tuaj nrog peb cov ntaub ntawv pov thawj thiab qhia txog lub tshuab hluav taws xob uas ntseeg tau los ntawm kev siv hluav taws xob thiab kev lag luam thoob ntiaj teb.

Cim npe nrov: 4390 kva transformer, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
75 kVA 3 Phase Distribution Transformer-13.8/0.208 k...
75 kVA Pad Mount Transformer-22.86/0.208 kV|USA 2024
2500 kVA Pad Mounted Transformer-13.2/0.48 kV|Canada...
4000 kVA 3 Phase Pad Mounted Transformer-24.94/0.6 k...
500 kVA Peb Theem Distribution Transformer-4.16/0.6 ...
2000 kVA Pad Mounted Distribution Transformer-4.16/0...
Xa kev nug