Dab tsi yog gis? Qhia rau Cov Roj Insulated Switchgear vs AIS
Jun 24, 2025
Tso lus
Dab tsi yog gis?
![]() |
Nws lub npe tag nrho yog cov roj insulated Switchgear. Roj insulated ntawm no yog hais txog sulfur hexafluoride (SF6). SwinGear yog cov lus luv ntawm cov kev sib xyaw nrog Circuit Court, Disconnectors, Cov Khoom Siv Tsis Txaus, Hloov, Chaw Nres Tsheb, cov chaw sib txuas thiab cov khoom sib txuas. Cov cuab yeej siv lossis cov khoom siv uas muaj nyob hauv cov hlau av uas muaj hlau, thiab muaj cov roj sf6 insulating, yog li nws tseem hu ua SF6 tag nrho cov kev sib xyaw ua ke. Yog li, gis yog los ua ke lub siab - cov hluav taws xob ntawm cov hluav taws xob raws li SF6 nrog cov hluav taws xob uas muaj peev xwm sib txuas tau los ua qhov siab kaw los ua qhov siab kaw. |
Cov yam ntxwv ntawm SF6

Sf6 yog ib qho synthesialized inert gas yug hauv Fabkis. Ntshiab SF6 roj yog xim tsis muaj xim,
Tsis tau, tsis muaj ntxhiab, tsis - pob zeb, thiab muaj cov tshuaj uas ruaj khov ntawm chav sov. Nws yog cov roj inert. Cov roj ceev yog 5.1 sijhawm uas saum huab cua.
SF6 cov roj muaj lub zog dielectric sib npaug li ntawd ntawm transformer roj ntawm lub siab ntawm 0.29 MPa, thiab nws lub arc tua hluav taws yog 100 npaug ntawm huab cua. Tam sim no nws yog cov roj hluav taws xob hluav taws xob ntau tshaj plaws.
Kev sib piv ntawm AIS thiab GIS
![]() |
![]() |
| Huab cua insulated switchgear | Roj Insulated Switchgear |
1. Cov chaw pem teb
![]() |
GIS, ib lub pob zeb ua tiav tag nrog cov qauv sib xyaw, nyob hauv av ntawm AIS rau AIS rau 500kv gis. Qhov no yog vim li cas GIS yog thawj qhov kev xaiv hauv cov chaw uas cov av xav tau siab, av muaj txiaj ntsig heev, tus nqi av lossis av muaj siab heev. Ntawm chav kawm, nws tsis txhais tau tias thaj av tsuas yog cov qauv rau xaiv GIS. Muaj ntau ntau lwm yam, thiab qhov no tsuas yog ib qho ntawm lawv. |
2. Qhov siab
![]() |
Kev sib raug zoo ntawm qhov siab thiab lub zog Dielectric: Raws li qhov siab nce, atmospheric siab poob siab dua, ua rau muaj kev txo qis hauv huab cua ntom ntom. Cov huab cua ua "nyias". Lub Dielectric lub zog ntawm huab cua (nws lub peev xwm los tiv thaiv hluav taws xob tawg thiab tiv thaiv kev sib tua) nyob ncaj qha rau ntawm nws qhov ntom ntom. Huab cua nrog qis dua ntom ntom (siab siab) tau loj dua molecular thiab ntev dua molecular dawb txoj kev. Qhov no ua kom yooj yim rau cov hluav taws xob kom nrawm rau hauv lub teb hluav taws xob thiab ua kom muaj zog txaus, ua rau nws ua rau hluav taws xob tawg (arc tiam). Yog li ntawd, ntawm tib qho hluav taws xob, cov rwb thaiv tsev rwb thaiv tsev ntawm huab cua ntawm cov huab cua siab yog qhov qis dua li qhov chaw qis lossis theem qis. Thaum lub Eargear yog ntsia ntawm qhov chaw siab dua, qhov ntau tshaj plaws yuav tau txo qis, yog li cov voltage ntau dua yog tseem yuav txo. Qhov no yog vim li cas, rau cov pa pa - Insulated Switchgear, yog tias nws yuav tsum tau nruab saum toj 1000 meters, khoom siv nrog lub zog siab dua. GIS yog kev tiv thaiv los ntawm SF6 roj, yog li nws cov kev teeb tsa yuav tsis cuam tshuam los ntawm qhov siab. |
3. Kev Nyab Xeeb
![]() |
Hais txog kev nyab xeeb, tag nrho cov siab - voltage cov khoom siv tau muab ntim rau ntawm cov hlau uas tau muab ntim nrog. Tus Casing Ua Ib Lub Tebchaws Mev Electromagnetic Shield (Faraday Lub Pob Tawb AIS tau txais cov qauv qhib, thiab qhov siab- voltage tus neeg coj ncaj qha raug rau huab cua. Thaum kev ua haujlwm lossis nce kev ua yuam kev, cov neeg ua haujlwm yuav tsum ua kom muaj kev deb (feem ntau tshaj li ntau meters). Muaj kev pheej hmoo txaus ntshai ntawm kev sib txig sib luag, thiab kev sib cais ntawm lub cev thiab kev ua haujlwm ntawm lub cev thiab cov haujlwm ua haujlwm yuav tsum tau txais kev tiv thaiv. Tab sis qhov no tsis txhais tau tias AIS tsis muaj kev nyab xeeb dua lossis tsis muaj kev nyab xeeb txhua. Qhov tseeb, 70% ntawm cov kev hloov thoob ntiaj teb yog tsim ntawm cov thev naus laus zis thev naus laus zis. Kev ntxuav cov neeg tsis tu ncua, kev teeb tsa cov noog pab pawg, thiab tsib {{} i}} Cov khoom siv iching tseem tuaj yeem ua haujlwm zoo. |
4. Hloov nthuav dav
Thaum tsim qauv hloov, engineers feem ntau khaws cov cheeb tsam thaj av kom tau raws li qhov kev xav tau ntawm kev tsim kho yav tom ntej. Nyob rau hauv cov pa -} istulated kev hloov (AIS), qhov nthuav dav no feem ntau yog qhov ncaj thiab yoog raws. Txij li cov cuab yeej siv AIS (xws li cov khoom sib txuas sib cav, cov tshuab tsis sib xws, cov pob hluav taws xob, thiab lwm yam) qhib kev teeb tsa huab cua thiab lub cev sib npaug ntawm ib leeg. Ntxiv cov bays tshiab lossis txuas cov tsheb busbars feem ntau tsuas yog xav tau cov khoom siv tshiab uas muaj feem cuam tshuam nrog hluav taws xob. Nws tsis muaj tsawg dua nyob ntawm cov qauv tshwj xeeb lossis cov chaw tsim khoom ntawm cov khoom siv ntxiv tshiab ntxiv. Cov khoom siv ntawm cov hom sib txawv lossis cov qauv (ntev npaum li lawv tau raws li cov kev ua tau yooj yim) feem ntau tuaj yeem yooj yim ua ke lossis khiav hauv kev sib tw.
Txawm li cas los xij, rau cov roj -} Cov khoom siv insulated (GIS), nthuav dav ntau dua nyuaj thiab nyob ntawm cov tuam ntxhab tshwj xeeb. Qhov no yog vim GIS heev sib xyaw siab siab- voltage cov tsev thiab muab ntsaws rau hauv cov vaj tsev modular hlau uas muaj roj (xws li SF6). Kev nthuav dav feem ntau txhais tau tias cov roj uas tshiab, tau sib phim roj zoo nkauj-} beeted spacer modules yuav tsum tau ntxiv. Cov modules no yuav tsum tau nruj me ntsis sib xws nrog cov khoom siv loj, interface (xws li ntsaws {} hauv kev sib chwv), kev tsim vaj tse sab hauv, thiab kev soj ntsuam vaj tse nyob rau hauv. Qhov kev ua tau zoo no ua rau nws yuav luag tsim nyog kom siv cov qauv qauv tshwj xeeb, lossis cov qauv kev txhawb nqa kom ntseeg tau tias qhov kev ntseeg tau zoo, cov neeg kho tshuab txuam thiab kev sib xyaw ua ke. Yog li no, kev nthuav dav npaj ntawm GIS yog heev nyob ntawm thawj cov cuab yeej xaiv thiab ntev} lub sij hawm txhawb nqa ntawm cov khw.
5. Kev tiv thaiv ib puag ncig
![]() |
Thaum muaj kev tiv thaiv ib puag ncig, AIS thiab GIS muaj lawv tus kheej zoo thiab qhov tsis zoo. AIS siv cov pa rwb thaiv tsev thiab tsis muaj kev pa roj carbon monissions. Piv nrog SF₆ roj siv hauv GIS, nws muaj tsawg dua rau ib puag ncig, tshwj xeeb tshaj yog hauv kev tswj lub tsev cog khoom nyhuv. Nyob rau tib lub sijhawm, cov qauv ntawm AIS kuj yooj yim, uas ua rau nws tau yooj yim thiab rov ua dua tshiab thaum so haujlwm, thiab muaj lub nra hnyav dua. Txawm li cas los xij, GIS yog ib puag ncig ib puag ncig thaum lub sijhawm kev tsim kho thiab kev ua haujlwm. Nws nyob qhov chaw me me thiab haum rau av - tsis muaj chaw xws li cov nroog. Nws muaj lub sijhawm tsim kho luv luv thiab tsim cov hmoov av tsawg. Tus qauv kaw kom zoo txo qis lub suab nrov thiab muaj tsawg kev cuam tshuam nrog ib puag ncig ib puag ncig. Yog li, zuag qhia tag nrho, AIS muaj ntau lub zej zog ua phooj ywg hauv kev ua pa roj av, thaum GIS ua tau zoo dua hauv kev txuag av, kev txo cov suab nrov thiab kev tsim kho. Nrog rau kev txhim kho cov roj cua tshiab ib puag ncig, kev ua haujlwm ib puag ncig ntawm GIS yuav tsum tau txuas ntxiv txhim kho yav tom ntej. |
6. Tus nqi
Cov cuab yeej ua lag luam ntawm AIS khoom yog li 30%-}}}}}}}} ntawm gis, uas yog tus nqi sib txuas ntxiv. Cov av raug nqi siab yog qhov tseem ceeb: Kev nyab xeeb hluav taws xob kev nyab xeeb yuav tsum tau tshwj tseg rau cov neeg coj kev, ua rau muaj thaj chaw loj. Hauv nroog loj lossis thaj av uas tau txais txiaj ntsig zoo, lub tebchaws tau txais nqi yuav ntau tshaj cov khoom peev. Cov lus hauv qab no yog qhov sib piv ntawm cov peev txheej pib, kev ua haujlwm thiab cov nqi txij nkawm, thiab tag nrho lub neej lub neej ntawm AIS thiab GIS.
| Qho loj dav | Ib | Gis |
| Thawj zaug kev nqis peev | Tsawg cov khoom siv nqi (li 30% -50% ntawm GIS) tus nqi av siab | Cov cuab yeej siv cov khoom siv siab (suav nrog cov roj hauv chav / SF₆) av txuag 50-70% |
| Kev ua haujlwm thiab txij nkawm cov nqi | Nquag Tu ntawm Insulators nquag - fouling txheej txheem / de- iching khoom siv peev | Yeej, txij nkawm -} Free SF₆ roj xyuas yog tus nqi tseem ceeb |
| Tag nrho lub neej | Tsawg cov txheej txheem ntsuas pib, yooj yim tab sis kev tu ncua | Kev ua haujlwm siab pib, kev ua haujlwm thiab cov nqi tswj xyuas tuaj yeem txo los ntawm 40% + hauv 20 xyoo |