Cov hloov pauv tam sim no tau piav qhia txog: cov ntsiab cai, hom, thiab yuav siv lawv nyab xeeb li cas
Oct 17, 2025
Tso lus
Nyob rau hauv lub zog hluav taws xob niaj hnub nimno network, txhua theem {- los ntawm tiam kom tau txais kev xa mus {} Qhov no ua kom meej meej ruaj khov, muaj zog, thiab kev ua haujlwm nyab xeeb. Nkawv siab nyob rau hauv high - voltage Systems feem ntau ncav cuag ob peb txhiab amperes, ua ncaj qha ntsuas nrog cov twj paj nruag tsis yooj yim sua. Yog li no, cov hloov pauv tam sim no tau siv los nyab xeeb thiab muaj tseeb hloov cov dej ntws. Cov hloov pauv tam sim no ua raws li "sensors" thiab "tus saib xyuas" ntawm lub zog hluav taws xob. Lawv hloov pauv siab rau hauv cov qauv, muaj kev nyab xeeb qis qis, muab cov ntaub ntawv raug rau metering, tshuaj xyuas, thiab cov khoom siv tiv thaiv. Nyob rau tib lub sijhawm, lawv cais tawm ntau qhov hluav taws xob, tiv thaiv ob tus neeg ua haujlwm thiab khoom siv. Lawv qhov kev ua tau zoo thiab siv tau kom raug rau kev ntseeg tau thiab kev khwv nyiaj txiag ntawm lub zog hluav taws xob. Kab lus no yuav qhia cov qauv, kev cai, muaj nuj nqi, ntawv thov, xaiv, siv thiab kho cov kev hloov pauv tam sim no.
Tam sim no hloov pauv hloov pauv thiab cov kab ke ua haujlwm
Lub tsev: Ib qho hloov pauv tam sim no muaj cov hlau ua ke, muaj lub tshuab winding, muaj qhov kev txhawb nqa theem nrab, cov lus tsis txaus siab, thiab yeem) cov windings.
![]() |
Txoj Cai Kev Ua Haujlwm: Ib qho hloov pauv tam sim no ntawm kev induction electromagnetic induction. Nws muaj cov hlau kaw thiab windings. Tus thawj cua muaj ob peb tig. Qee qhov hloov pauv tam sim no tsis muaj ib qho cua daj cua dub sib cais. Tus thawj coj ntawm lub ntsej muag, zoo li lub chaw tos tsheb npav, tuaj yeem hla dhau tus tub ntxhais hlau thiab ua raws li kev ua haujlwm ntawm lub ntsej muag ua ntej (tig). Tus thawj coj tus thawj coj muaj tus ntoo khaub lig loj- seem} Tshooj thiab txuas rau hauv koob nrog qhov tam sim no tau ntsuas. Nws nqa cov kev tam sim no ntawm Circuit Court. Lub winder thib ob muaj ntau tus tig thiab ib tug neeg kos npe. Nws txuas rau qhov ntsuas ntsuas ntsuas lossis kev tiv thaiv. Lub Callcuit Court theem nrab nyob hauv lub sijhawm ua haujlwm. Cov kauj npog txuas nrog ntsuas ntsuas ntsuas thiab kev tiv thaiv Circuit muaj cov impedance tsawg heev. Tam sim no hloov pauv tam sim no yuav luag zoo li lub sijhawm luv luv. Nws hloov siab lub siab tam sim no mus rau hauv ib qho qis dua theem nrab tam sim no. |
Cov haujlwm thiab cov ntawv thov ntawm cov hloov pauv tam sim no (CTS)
![]() |
Lub cev muaj zog 1. Kev Ntsuas: Ua haujlwm nrog cov twj ntsuas ntsuas ntsuas ntsuas cov kab tam sim no thiab lwm yam tsis raug. Muab cov ntaub ntawv raug rau hluav taws xob cov khoom siv hluav taws xob thiab kev soj ntsuam system. 2. Kev tiv thaiv: Ua haujlwm nrog Relay Cov Khoom Tiv Thaiv kom tiv thaiv cov pa hluav taws thiab cov khoom siv los ntawm kev tshaj thiab overcurrent. Ua kom lub kaw lus nyab xeeb thiab ruaj khov. 3. Kev rho tawm: Ua cov ntsuas ntsuas thiab cov kev tiv thaiv cais tawm ntawm high- voltage zog. Tiv thaiv tib neeg thiab khoom siv.
Kev Lag Luam Kev Lag Luam Cov hloov pauv tam sim no siv nyob rau hauv lub zog hluav taws xob, kev lag luam, lub zog hluav taws xob, tsheb thauj mus los, ua lag luam thiab kev siv tshuab. Lawv ntsuas tam sim no, tshuaj saib khoom siv, tswj cov ris nra, thiab muab kev tiv thaiv. |
Cov hloov pauv hluav taws xob tam sim no hauv cov hloov pauv thiab cov tshuab siv rau:
1. Ntsuas lub ntsej muag zoo nkauj Winding Soj ntsuam: Ntsuas siab high- thiab qis} voltage windents. Muab tiag {{{{}} lub sijhawm thauj khoom thiab tiv thaiv overcurrent kev puas tsuaj.
2. Repay Kev Tiv Thaiv: Muab cov cim tam sim no los tiv thaiv cov khoom siv. Cov cuab yeej ua tau sai sai thaum kev ua yuam kev tshwm sim. Faulty kab raug txiav sib txuas ua kom lub kaw lus zoo.
3. Metering thiab Kev Them Nyiaj: Hloov chaw siab siab rau tus qauv xeb rau meters. Ua kom ntseeg tau tias qhov ntsuas tau yog thiab kev them nqi ncaj ncees.
4. Overload thiab kev ua txhaum tshuaj xyuas: ntes cov khib nyiab tsis sib xws. Nrhiav kev nce qib ntau dhau, cov teeb meem luv luv, thiab lwm yam teeb meem sai sai. Tiv thaiv kev puas tsuaj rau kev hloov pauv thiab lub kaw lus.
5. Kev tiv thaiv zoo: Pom cov khoom yuam kev sab hauv. Sib piv cov dej ntws ntawm qhov siab - thiab qis {{{voltage sab. Colate sib foob sai.
6. Av qeeg Soj ntsuam: Ntsuas cov xoom tshaj plaws - ntu ntu lossis seem tam sim no. Nrhiav cov rwb thaiv tsev kev puas tsuaj lossis cov teeb meem hauv paus. Tiv thaiv tib neeg thiab khoom siv.
7. Busbar / Bushing CT (sab hauv): nruab rau transformer bushings lossis busbars. Tseg chaw thiab muab cov kev ntsuas kho kom zoo. Ua rau kev soj ntsuam yooj yim dua.
8. Transformer kev sim thiab kuaj mob: Muab cov ntaub ntawv raug rau kev sim, kev saib xyuas, thiab kev ntsuas yuam kev. Pab soj ntsuam kev ua tau zoo thiab ua kev saib xyuas kev tiv thaiv.
Kev faib tawm ntawm cov hloov pauv tam sim no
Cov hloov pauv tam sim no (CTS) Siv rau hauv cov khoom siv fais fab tau tsim los hloov cov khoom lag luam siab ua ntu zus rau kev ntsuas, kev tiv thaiv thiab tswj. Lawv ua kom muaj kev saib xyuas zoo ntawm kev ua haujlwm hloov pauv, muaj tseeb ntsuas, thiab txhim khu kev qha kev tiv thaiv. Ua raws li lawv cov hom phiaj, cov qauv, thiab txoj kev rwb thaiv tsev, cov cts no tuaj yeem faib ua hauv qab no:
| Kev Qhia Tawm | Ntaus | Kev piav txog |
| Los ntawm kev ua haujlwm | Ntsuas ct | Muab cov cim qhia meej tam sim no rau meters thiab cov twj paj nruag; Cov chav kawm yog (piv txwv li, 0.2, 0.5). |
| Kev Tiv Thaiv CT | Tsim los ua haujlwm kom raug thaum lub sijhawm ua txhaum yam tsis muaj kev sib nqus; siv rau relay tiv thaiv (piv txwv li, 5p, 10p). | |
| Ua ke ct | Kev sib txuas ua ke ntsuas ntsuas thiab kev tiv thaiv ua haujlwm nyob hauv ib chav. | |
| Los ntawm cov qauv | Qhov txhab hom | Thawj winding muaj ob peb lub qhov txhab loj ntawm cov tub ntxhais; Nws yog qhov haum rau cov ntawv thov me tam sim no. |
| Bar hom (bushing hom) | Tus transformer's bushing tus neeg xyuas pib ua tus thawj winding, dav siv hauv cov fais fab hloov. | |
| Ntiv Nplhaib Hom | Tag nrho cov tub ntxhais ua ke; Thib ob winding puag ncig lub thawj coj, muab cov khoom zoo thiab rwb thaiv tsev. | |
| Los ntawm rwb thaiv tsev nruab nrab | Hom qhuav | Siv huab cua lossis epoxy resin rwb thaiv tsev; mas rau cov ntawv thov sab hauv tsev. |
| Roj -}}} itected hom | Immersed in transformer oil for cooling and insulation, common in oil-filled power transformers. | |
| Sf₆ roj -} insulated hom | Siv hauv gis los yog ntim transformer hloov nrog cov hluav taws xob ntau ntau. | |
| Los ntawm kev teeb tsa qhov chaw | Ua - hauv ct | Mounted sab hauv lub thoob ultrasonic thiab raus hauv cov roj; feem ntau ntsia rau ntawm bushing ua. |
| Sab nraud ct | Ntsia nraum zoov sab nraum lub thawv hloov hluav taws xob rau ntawm kev sib txuas lossis cable; yooj yim rau kev saib xyuas. |
Yuav ua li cas xaiv ib qho hloov pauv tam sim no
|
1. Volfage thiab xaiv tam sim no - Cov ntsuas hluav taws xob ntawm ib qho hloov pauv tam sim no yuav tsum tsis txhob qis dua li cov hluav taws xob ntawm lub Circuit Court ntawm lub installate. -} Cov rated tam sim no ntawm thawj qhov cua txawv (piv txwv li 5a, 15a, 20a, 20a... 1500 a). Thaum xaiv cov hloov hluav taws xob tam sim no, cov qhab nia tseem ceeb tam sim no tau pom zoo tam sim no ntawm kev sib dhos tam sim no ntawm 5A, nrog ob peb lub sijhawm thauj khoom tam sim no. 2. Xaiv cov qhab nia raug - Tus hloov pauv tam sim no yuav tsum tau raws li cov cai kawm kom raug. Ntawd yog, nws theem theem qub S₂ yuav tsum tsis txhob muaj ntau tshaj li qhov ntsuas cov qib qis theem nrab thauj mus rau qib ntawd: S₂ₙ> S₂ |
![]() |
Yuav ua li cas siv tus hloov pauv tam sim no kom raug
1. Cov sab thib ob yuav tsum tsis txhob qhib - circuited
Yog hais tias lub voj voog theem ob tau raug txiav tawm thaum lub sijhawm ua haujlwm, qhov ua rau voltage nyob rau sab nraud yuav nce ntau yam ntxiv hauv kev sib nqus flux. Qhov no tuaj yeem nyeem cov tub ntxhais thiab tsim kom muaj siab- voltage spikes, muaj kev puas tsuaj rau kev ntsuas ntsuas thiab cov neeg ua haujlwm. Yog tias muaj ib sab theem nrab qhib Circuit Court yog kuaj pom, lub Circuit Court yuav tsum raug kaw tam sim ntawd thiab tus txhaum kho.
2. Load txuam thiab kev tiv thaiv
Thaum xaiv cov hloov pauv tam sim no, xav txog cov cuab yeej tawm tswv yim, thiab lwm yam kev tiv thaiv rov qab cuam tshuam nrog, thiab lwm yam kev tiv thaiv kev cuam tshuam Z_b yog nyob hauv qhov ntsuas ntsuas. Txog kev tiv thaiv cov tshuab xav tau kev kub ceev thiab ntseeg tau, ib qho CT nrog qhov kev tiv thaiv kab ke tsawg- Circuit Court tiv thaiv cov yam ntxwv yog pom zoo.
3. Kev teeb tsa txoj haujlwm thiab kev taw qhia
Qhov kev taw qhia ntawm CT yuav tsum ua kom haum nrog cov kev taw qhia kom tsis txhob muaj theem thim rov qab thiab teeb liab yuam kev. Thaum txhim kho nplhaib lossis lub qhov rais {{{- Hom CTS, xyuas kom cov tub ntxhais ua kom raug ntawm lub sijhawm thiab hauv kev tsim nyog, raws li tau teev tseg hauv kev tsim.
4. Qhov kub thiab cua
Cov khoom siv siab lossis qhov chaw huab cua siab tuaj yeem nce ct kub nce, cuam tshuam tooj liab thiab cov khoom poob hlau. Ua kom zoo cua nyob rau hauv cov khoom siv cov khoom siv, thiab tsis txhob txhim kho lub CT ze rau cov kev ua haujlwm kub muaj zog los xyuas kom ntev.
Txij Nkawm Transformer
Thaum lub sijhawm ua haujlwm, ntawm {{{{{0} Diseitish cov neeg ua haujlwm yuav tsum tau kuaj tam sim no hloov tam sim no kom ntseeg tau tias muaj kev nyab xeeb. Thaum soj ntsuam, them sai sai rau cov ntsiab lus hauv qab no:
1. Tus hloov pauv tam sim no yuav tsum tsis muaj suab nrov txawv txawv lossis hlawv cov ntxhiab tsw.
2. Tshawb xyuas cov chaw hloov pauv tam sim no rau overheating.
3. Lub plooj (porcelain rwb thaiv tsev ntawm cov hloov pauv tam sim no yuav tsum yog huv thiab tsis huv, pub dawb ntawm cov kab nrib pleb thiab tawm.
4. Tshawb xyuas cov roj hloov roj hloov tam sim no rau kev ua haujlwm ib txwm muaj thiab tsis muaj roj xau.
5. Nquag sim cov rwb thaiv tsev cov khoom ntawm cov roj hloov roj hloov tam sim no. Rau roj -} Cov hloov pauv tau tam sim no, cov roj zoo yuav tsum tau ua kom tsis txhob muaj peev xwm los tiv thaiv kev ua kom muaj cua sov muaj peev xwm thiab ua rau tawg lossis hluav taws.
Xa kev nug