Ib qho kev qhia dav dav rau qhov siab nrawm nce relay (RPRR)

Sep 11, 2025

Tso lus

Kev Taw Qhia

 

Lub siab ceev ceev nce rov qab ua cov khoom siv hluav taws xob tseem ceeb tsim hauv cov khoom siv roj hluav taws xob hauv ntau cov khoom siv hluav taws xob, muaj peev xwm hloov kho, thiab cov tshuaj tiv thaiv thiab cov tshuaj tiv thaiv. Cov relay no muaj ob lub ntsiab lus tseem ceeb: lub siab siab relay (lossis kiv cua gradient relay) thiab lub zoo li qub hydraulic relay. Cov txheej txheem no ua haujlwm ua ke los muab cov cim tseem ceeb rau kev tiv thaiv cov roj tso tsheb hlau.

 

Thaum lub siab sab hauv ntawm lub tank nce ntawm tus nqi tshaj li 3 ± 1 KPA / sec, sec, sec, sec, sec, sec, sec, sec, sec, sec, sec, sec, sec, sec, sec, sec, secthing uas lub tank tau txais kev pheej hmoo rau cov xwm txheej tseem ceeb. Tus relay's teb cov lus teb tau muab kho kom haum rau kev txhim kho nws cov yam ntxwv kev ua haujlwm, raws li qhia hauv cov duab muab. Cov kev hloov pauv tau zoo thaum lub siab hloov pauv yog nyob rau hauv qhov kev txwv tsis lees paub, kom ntseeg tau tias kev mob zoo nyab xeeb thaum lub sijhawm ua haujlwm.

 

Hauv cov xwm txheej uas lub siab nce tab sis tseem yog li qub (tsawg dua 3 ± 1 KPA / sec), cov relay functions raws li npaj, kom muaj kev nyab xeeb txuas ntxiv rau lub roj tsheb. Tsis tas li ntawd, cov relay sib xyaw ua ke zoo li qub hydraulic hloov mus uas muab lub tswb ntsuas thaum cov roj siab poob qis dua hauv qab kev txiav txim siab.

 

Qhov rhiab heev ntawm kev hloov siab nrawm nrawm tau teeb tsa los saib xyuas cov nyiaj siab rau cov roj tso tsheb hlau luam hauv qab 25 kpa ± 20%. Yog tias ntsuas cov qib siab tshaj cov qib no, lub sijhawm relay lub teb teb tsawg, pub rau nrhiav kom tau sai. Piv txwv li, yog lub siab nce mus rau gradient ntawm gradient ntawm gradient ntawm gradient ntawm gradient ntawm gradient ntawm gradient ntawm 500, sec, lub sijhawm relay lub zog teb tau lub sijhawm tsuas yog 0.05 vib nas this. Hauv kev sib piv, lub siab nce rau kev gradient ntawm 100 kpa / sec yuav ua rau lub sijhawm teb ntawm 0.25 vib nas this. Qhov kev kuaj nrawm nrawm no yog qhov tseem ceeb rau kev ua kom muaj kev nyab xeeb thiab kev ntseeg tau ntawm cov khoom siv.

 

image001

 

Thaum tus nqi ntawm kev nce siab nce yog qis dua 3 ± 1 KPA / sec, cov relay tsis qhib kev ua kom muaj kev ua tau zoo, raws li nws tau ua raws li cov kev ua tau zoo ntawm cov hluav taws xob sib txuam. Nyob rau hauv cov xwm txheej zoo li no, txoj kev pheej hmoo ntawm kev puas tsuaj los ntawm qhov xwm txheej yog tsawg heev, tso cai rau lub qub hydraulic mechanism los tswj lub siab zoo. Txoj hauv kev no pab tiv thaiv kev ua lag luam tsis tsim nyog uas yuav tshwm sim los ntawm cov roj siab tsis tshua muaj roj ntawm cov hloov roj. Yog li, nws raug nquahu kom vam khom rau cov roj roj zoo li qub pom kev pom ntawm cov cim kev taug kev rau kev nce siab rov qab thaum cov khoom lag luam no.

 

 Rapid Pressure Rise Relay

 

02 siv tau ntau

 

1. Ntau yam: haum rau cov roj -}}} Cov roj capacitors, cov tshuaj tua hluav taws thiab lwm yam xa hluav taws xob roj tank;

2. Ib puag ncig cov cai: -30℃~ +50 degree;

3. Tus txheeb ze cov av noo: +20 degree, tsawg dua 95%;

 

RPRR

 

03 sab nraud dimionion Teeb Duab

 

RPRR diagram

 

04 feature

 

● Cov siab zoo siab: RPRR yog ntsuas kom pom lub siab hloov pauv hauv cov khoom txhais tsis pub dhau ib qho, nrog Net nias nce nqi feem ntau tsis tshaj 25 KPA. Qhov kev nkag siab no yog qhov tseem ceeb rau kev cuam tshuam raws sijhawm thaum lub sijhawm hloov siab.

Tshuaj Dual tiv thaiv mechanism: Los ntawm kev sib koom ua ke ntawm ob qho tib si kev soj ntsuam sai thiab muaj txiaj ntsig

● Cov qauv hluav taws xob ruaj khov: RPRR NTA ob qho kev sib cais sib cais, uas ua rau nws txoj kev ntseeg tau thiab qhov tseeb, ua rau nws muaj kev vam meej xaiv rau kev siv hauv kev hloov pauv.

● Micro -} hloov thev naus laus zis: Kev siv ntawm cov txhim khu

 

Cov Lus Qhia 05 Installation

 

1. Lub siab thiab tawg nrawm relay yuav tsum txuas ntawm tus npauj npaim valve nrog ib qho 80 hli inch incer tau nruab rau sab phab ntsa ntawm cov roj tank. Nws raug nquahu kom ua kom qhov siab ntawm lub installation no ntawm h meters, raws li muaj nyob hauv daim duab 4. Yog tias qhov kev ncua deb ntawm lub valve ntau dua 3.

2. Kev tsim kho kom ruaj khov yog qhov tseem ceeb; Ua kom cov relay yog ruaj khov rau kev teeb tsa kev teeb tsa lossis misalignments.

3. Rau kev ua tau zoo tshaj plaws, lub siab thiab tawg nrawm relay yuav tsum tau muab cov roj tank kom tso cai rau cov roj ntxiv ntawm ntu ntu Upper. Nco ntsoov txuas nws rau cov roj teeb cov roj teeb, raws li qhia hauv daim duab 2.

4. Nws yog qhov tseem ceeb los txuas cov relay yog qhov tseeb rau lub zog loj thiab kom paub tseeb tias nws ua haujlwm hauv qab cov kev ua haujlwm tsim nyog.

5. Kev ntsuas hluav taws xob yog qhov tseem ceeb; Cov roj pipeline yuav tsum txuas ib qho kawg ntawm lub siab ntsuas thaum muaj lwm yam txuas rau kev saib xyuas. Cov teeb tsa no pab kom cov nqi khiav tsawg thiab tso cai rau kev soj ntsuam qhov tseeb.

6. Kev sim ua ntu zus ntawm cov khoom yog qhia, uas suav nrog kev soj ntsuam tshwj xeeb ntawm cov pab pawg sib dhos hauv daim duab 4. Qhov no yog ntsuas nws ua haujlwm. Puas yog cov relay tsis ua tiav cov lus qhia tshwj xeeb, kev tu kom raws sijhawm lossis hloov chaw yuav tsum tau txiav txim siab.

7. Thaum siv cov roj hluav taws xob cov yeeb nkab rau venting roj (saib seb txoj kab kom zoo ntawm kev sib txuas thiab khaws cov hluav taws xob tsis txhob ua kom tsis txhob muaj cov roj ntsha.

8. Nws yog ib qho tseem ceeb kom qhib lub valve kom muaj cov roj dej, kom cov relay tsis muaj kev cuam tshuam ib qho kev cuam tshuam thaum ua haujlwm no.

9. Thoob plaws cov txheej txheem hloov chaw, lub siab thiab tawg siab siab relay yuav tsum tsis txhob muab tso ncaj qha rau ntawm txhua lub siab apparatus. Yuav tsum ceev faj kom tsis txhob muaj xwm txheej uas yuav ua rau muaj kev puas tsuaj.

10. Lub siab thiab tawg siab rau kev hloov kho kom tsim qauv. Yog li ntawd, ib qho kev hloov uas tsis tau tso cai lossis tshem tawm cov neeg siv yog cov neeg siv nruj me ntsis.

 

Installation Guidelines

 

06 xa cov txheej txheem kuaj sim 06

 

Kev soj ntsuam xa tuaj yeem faib rau ob hom hom: Cov kev ntsuas ua tau zoo thiab ua tau zoo.

1. Rau cov kev ntsuas niaj hnub, kev sim ua kom yooj yim tuaj yeem siv tau cov khoom lag luam muag khoom nrog cov khoom siv (saib Daim Duab 5). Cov kauj ruam hauv qab no npaj cov txheej txheem kev sim cua:

(1) Pib los ntawm kom ntseeg tau tias lub valve txuas cov relay rau lub transformer raug kaw, lees tias qhov hluav taws xob feem ntau tsis tau;

(2) Txheeb xyuas cov kev sib txuas ntawm cov pob qij txha tso twj tso kua mis rau cov piping paug;

(3) Tshem tawm cov kev ruaj ntseg ntawm cov ntsaws thiab tshem nws kom nws nkag mus rau cov relay interface;

(4) Qhib lub twj tso kua mis tso pa tawm 4 txog 5 zaug, ua tib zoo saib cov tshuaj tiv thaiv ntawm Relay. Nws yuav tsum khiav haujlwm ib txwm tsis muaj kev ua txhaum ib lub tswb rau kev ua yuam kev.

 

2. Rau kev ntsuas ua tau zoo, ua raws cov kauj ruam no:

(1) Pib los ntawm kev kaw lub pob valve, tom qab ntawd kaw cov relay los ntawm cov roj txhuav thiab tshem tawm cov relay zoo rau nws;

(2) Ua cov tshuaj tiv thaiv kom huv ntawm kev xa tawm tom qab kev tshem tawm seb nws lub xeev ua haujlwm. Yog tias muaj teeb meem dab tsi uas tau txheeb xyuas thaum lub sijhawm no, cov relay tshiab yuav tsum tau nruab, thiab cov koog tsis tuaj yeem raug xa mus rau cov chaw tsim khoom rau kev ua haujlwm.

 

Relay testing

 

 