01 General
1.1 Project Description
2400/3000 kVAqhuav hom transformerstau xa mus rau Jamaica xyoo 2025, qhov ntsuas hluav taws xob ntawm lub tshuab hluav taws xob yog 2400/3000 kVA. Qhov siab voltage ntawm no qhuav hom transformer yog 13.8kV, qhov tsawg voltage yog 0.48kV. Qhov no high voltage qhuav hom transformer yog txawm peem rau nrog ib tug tsis muaj load kais changer, tapping ntau yog ± 2 * 2.5% ntawm thawj sab, lub txias yog ONAN / ONAF.
Qhov no yog 2400/3000kVAcam khwb cia coil qhuav hom transformeryog tsim los rau cov tshuab hluav taws xob niaj hnub, kev sib txuas ua haujlwm siab, kev nyab xeeb, thiab kev tswj xyuas ntse. Nws siv lub kiv cua- pab tsim kom txias thiab tuaj nrog lub log hloov tau yooj yim, ua kom muaj kev xa mus sai thiab kev teeb tsa thaum hloov mus rau ntau yam kev thov. Lub kiv cua ua haujlwm ntawm lub zog hluav taws xob ntawm 220V, ua ke nrog lub zog tswj qhov kub thiab txias ntawm 125V, xa cov kev ua tau zoo thiab txhim kho lub zog.
Rau hluav taws xob daim ntawv lo, cov khoom siv tshwj xeeb kub shrink tubing thiab theem sib lawv liag cim npe nrog xim coding: liab rau theem A, daj rau theem B, xiav rau theem C, thiab dub rau nruab nrab. Qhov no ua kom pom kev ua haujlwm yooj yim thiab txhim kho kev nyab xeeb thaum siv.
Tsis tas li ntawd, lub tshuab hloov hluav taws xob tau nruab nrog lub siab - ua haujlwm kub tswj uas tsis tu ncua saib xyuas kev khiav hauj lwm kub, muab kev tiv thaiv ntse tiv thaiv overheating thiab ua kom ntev lub neej ntawm cov khoom siv. Cov yam ntxwv no ua kom muaj kev ruaj ntseg zoo nyob rau hauv siab -load thiab qhov chaw ua haujlwm tseem ceeb.
Txawm hais tias rau cov nroj tsuag kev lag luam, cov chaw lag luam, cov chaw khaws ntaub ntawv, lossis lwm lub zog- cov xwm txheej hnyav, qhov 2400/3000kVA qhuav- hom transformer muaj qhov ua tau zoo, txhim khu kev qha, thiab cov neeg siv- cov kev daws teeb meem zoo, xa kev nyab xeeb thiab ntse zog tswj.
1.2 Technical Specification
2400/3000 kVA qhuav hom transformers specification thiab cov ntaub ntawv ntawv
|
Xa rau
Jamaica
|
|
Xyoo
2025
|
|
Hom
Resin cam khwb cia qhuav hom transformer
|
|
Cov khoom siv tseem ceeb
Grain oriented silicon steel ntawv
|
|
Txuj
IEC60076
|
|
Rated zog
2400/3000 kVA
|
|
Ntau zaus
50 HZ
|
|
Vector pawg
Dyn 1
|
|
Theem
3
|
|
Hom cua txias
ONAN/ONAV
|
|
Thawj Voltage
13.8 kV 2
|
|
Secondary Voltage
0 ,48kv
|
|
Cov khoom siv winding
Aluminium
|
|
Impedance
6.04(±10%)%
|
|
Coj mus rhaub Changer
NLTC
|
|
Tapping Range
± 2 * 2.5% @ thawj voltage
|
|
Tsis Load Loss
3.5 kW tsi
|
|
Ntawm Load Loss
17.17 kWm
|
|
Rwb thaiv tsev theem
F
|
1.3 Cov duab kos
2400/3000 kVA resin cam khwb cia qhuav hom transformers daim duab kos duab thiab loj.

02 Kev tsim khoom
2.1 Core
Cov tub ntxhais hlau ntawm cov resin cam khwb cia qhuav hom transformers yog ua los ntawm high magnetic permeability txias -rolled grain-oriented silicon steel nplooj ntawv, ua tiav nrog laser txiav los yog precision stamping cov tswv yim, thiab siv ib tug laminated qauv los txo eddy tam sim no poob. Qhov saum npoo ntawm cov tub ntxhais yog coated nrog ib tug tshwj xeeb insulating txheej los txhim khu kev ya raws thiab rwb thaiv tsev kev ua tau zoo. Nws nta ib qho kev sib cog lus thiab meej, nrog cov khoom siv tsis yog- sib nqus siv los kho kom tsis txhob muaj suab nrov thiab kev ntxhov siab. Lub zuag qhia tag nrho cov qauv qhia txog kev ua haujlwm siab, tsis tshua muaj kev poob qis, thiab kev ua kom sov zoo, ua rau nws yog ib qho tseem ceeb rau kev ua haujlwm ruaj khov ntawm transformer.

2.2 Cua txias

Lub coil ntawm cov cam khwb cia qhuav hom transformers yog ua los ntawm high conductivity aluminium windings, tag kaw nrog epoxy resin rau zoo heev rwb thaiv tsev, tshav kub tsis kam, thiab noo noo tiv thaiv, zoo tiv thaiv luv luv circuits thiab ib nrab paug. Lub coil nta cov qauv compact nrog cov neeg kho tshuab siab zog, thiab kev tsim kho cua sov kom zoo kom tswj tau qhov kub thiab txias thiab kev ua haujlwm ruaj khov. Cov txheej txheem casting resin kuj muaj cov yam ntxwv zoo ib puag ncig, txo kev co thiab suab nrov, tso cai rau lub kauj kom muaj kev ntseeg siab thiab kev ua haujlwm zoo tshaj plaws hauv thaj chaw nyuaj.
2.3 Lub Rooj Sib Tham Kawg
Coil installation: Txhim kho cov txheej txheem uas twb tau nchuav rau hauv cov tub ntxhais hlau. Raws li qhov yuav tsum tau ua ntawm kev tsim cov duab kos, xyuas kom meej tias txhua lub kauj yog ua kom raug thiab ruaj khov. Cov txheej rwb thaiv tsev ntawm cov coils thiab nruab nrab ntawm cov coils thiab cov tub ntxhais yuav tsum tsis txhob muaj kev tiv thaiv luv luv.
Txuas lub davhlau ya nyob twg: Txuas cov hlau lead- tawm kawg ntawm lub kauj mus rau lub davhlau ya nyob twg ntawm lub transformer. Xyuas kom qhov kev sib txuas yog ruaj khov thiab ua tiav cov txheej txheem rwb thaiv tsev tsim nyog los tiv thaiv kev xau thiab luv luv Circuit Court.
Kev teeb tsa cua txias: Nruab lub kiv cua raws li tus qauv tsim los xyuas kom meej tias lub tshuab hluav taws xob tuaj yeem cuam tshuam cov cua sov thaum lub sijhawm ua haujlwm thiab tswj qhov kub thiab txias ua haujlwm.

03 Kev Xeem
|
Tsis muaj. |
Cov khoom kuaj |
Chav tsev |
Kev txais txiaj ntsig |
Ntsuas Tus Nqi |
Xaus |
||||
|
1 |
Kev ntsuas ntawm winding kuj |
/ |
Maximum kuj unbalance tus nqi Kab tsis kam: Tsawg dua lossis sib npaug li 4% |
HV (kab) |
LV (kab) |
Hla |
|||
|
0.09% |
0.9% |
||||||||
|
2 |
Rwb thaiv tsev Resistance Measurement |
MΩ |
HV-LV & E |
R15 |
R60 |
/ |
|||
|
2500 |
2500 |
||||||||
|
LV-HV & E |
R15 |
R60 |
|||||||
|
2500 |
2500 |
||||||||
|
Core-E |
R15 |
R60 |
|||||||
|
2500 |
2500 |
||||||||
|
3 |
Kev ntsuas qhov sib piv ntawm qhov voltage thiab xyuas cov theem hloov chaw |
/ |
Kev kam rau siab ntawm qhov sib piv ntawm tus thawj tapping: ± 1/10 Cov cim kev sib txuas: Dyn1 |
-0.08% ~ 0.07% Dyn 1 |
Hla |
||||
|
4 |
Kev ntsuas tsis muaj -load poob thiab tam sim no ntawm 90%, 100% thiab 110% ntawm qhov ntsuas hluav taws xob |
/ kW |
I0 :: muab ntsuas tus nqi P0: muab ntsuas tus nqi |
90% ua |
100% UA |
110% Yog |
Hla |
||
|
0.27% 2.684 |
0.30% 2.983 |
0.33% 3.281 |
|||||||
|
5 |
Load Losses, impedance Voltage |
/ kW kW |
t: 120 degree Z%: ntsuas tus nqi Pk: ntsuas tus nqi Pt: ntsuas tus nqi |
2400 kVA ua |
3000kVA ua |
Hla |
|||
|
6.18% 13.555 17.219 |
7.73% 21.370 27.285 |
||||||||
|
6 |
Applied Voltage Test |
/ |
HV: 38kV 60s lwv: 3kv60 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
||||
|
7 |
Induced Voltage Withstand Test |
/ |
Kev siv hluav taws xob (kV): 2 ua Induced voltage (kV): 0.96 Duration(s): 40 Zaus (HZ): 150 |
Tsis muaj kev sib tsoo ntawm qhov ntsuas hluav taws xob tshwm sim |
Hla |
||||
|
8 |
Kev kuaj qhov tso tawm ib nrab |
pC ua |
Qhov siab tshaj plaws ntawm kev tso tawm ib nrab yuav tsum yog 10 pC |
<10 |
Hla |
||||
|
9 |
Kub nce |
/ |
Winding kub nce Tsawg dua los yog sib npaug rau 100K |
HV winding |
LV winding |
Hla |
|||
|
88 |
92 |
||||||||


04 Packing thiab Shipping
4.1 Ntim
Cov cam khwb cia coil qhuav-hom transformer yog ntim rau hauv ib lub thawv ntoo, npog nrog cov dej noo-cov ntaub ntawv pov thawj aluminium foil hnab los tiv thaiv plua plav thiab av noo thaum thauj thiab khaws cia. Cov ntoo crate muaj zog muaj xws li cushioning sab hauv los tiv thaiv kev poob siab thiab kev co puas tsuaj.

4.2 Shipping

Kev thauj mus los ntawm lub tshuab hloov pauv siv lub thawv naj npawb CSNU7745546 mus rau qhov chaw nres nkoj ntawm Kingston muaj kev ruaj ntseg ntawm kev hloov pauv hauv lub thawv. Tom qab kev thauj khoom, lub thawv yuav raug thauj mus rau qhov chaw nres nkoj thiab nyab xeeb rau hauv lub nkoj. Thaum lub sij hawm kev thauj mus los hauv hiav txwv, cov xwm txheej ntawm cov khoom xa tuaj yuav raug saib xyuas kom ntseeg tau tias lub thawv muaj kev nyab xeeb. Thaum tuaj txog hauv Kingston, lub thawv yuav raug tshem tawm siv cov khoom nqa nqa, ua raws li kev tshuaj xyuas. Kev lis kev cai yuav ua kom tiav ua ntej thauj lub transformer mus rau nws qhov chaw kawg. Thoob plaws hauv cov txheej txheem, yuav tsum tau saib xyuas kev nyab xeeb ntawm kev thauj mus los, thiab kev tuav pov hwm yuav tsum tau yuav cov khoom siv los txo cov kev pheej hmoo ntawm kev thauj mus los.
05 Site thiab Summary
Nyob rau hauv xaus, resin cam khwb cia qhuav hom transformers sawv cev rau ib tug tseem ceeb kev nce qib nyob rau hauv transformer technology, muab kev ruaj ntseg, kev cia siab, thiab ib puag ncig compatibility. Lawv cov kev tsim tshwj xeeb uas siv epoxy resin tsis tsuas yog muab cov rwb thaiv tsev zoo thiab tiv thaiv kom ya raws, tab sis kuj tso cai rau cov qauv tsim kom haum rau ntau qhov chaw teeb tsa. Nrog rau kev saib xyuas tsawg kawg nkaus thiab muaj zog dua, cov hloov pauv no yog qhov kev xaiv zoo tshaj plaws rau kev siv hauv kev lag luam, kev lag luam, thiab kev siv hluav taws xob tauj dua tshiab. Raws li kev lag luam tseem ceeb tshaj qhov ua tau zoo thiab kev ruaj khov, resin cam khwb cia qhuav hom hloov pauv yuav tsis muaj qhov xav tau ua lub luag haujlwm tseem ceeb hauv cov tshuab hluav taws xob niaj hnub no, ua rau lub zog ntsuab thiab txhim khu kev qha rau yav tom ntej.

Cim npe nrov: qhuav hom transformers, chaw tsim tshuaj paus, tsum, nqe, nqi
You Might Also Like
630 kVA 3 Theem Qhuav Hom Transformer-6.6/0.55 kV|So...
500 kVA Qhuav Resin Transformer-13.8/0.46 kV|South A...
400 kVA Qhuav Hom Hluav Taws Xob Transformers-0.55/0...
160 kVA Sab Hauv Tsev Qhuav Hom Transformer-10/0.4 k...
250 kVA Qhuav Cast Resin Transformers-10/0.4 kV|Geor...
630 kVA Peb Theem Qhuav Hom Transformer-10/0.4 kV|Ge...
Xa kev nug